Overview
Place of Origin: |
USA |
Brand Name: |
HONEYWELL |
Model Number: |
8C-PAIN01 51454356-175 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Part Number |
8C-PAIN01 51454356-175 |
|
Part Type |
Analog Input Module |
|
Dimensions |
6 x 15.5 x 14.3 cm |
|
Weight |
0.3 kg |
|
Series |
Series 8 |
|
Channels |
16 single-ended analog input channels |
|
Signal Types |
Current: 4–20 mA, ±40 mA range; Voltage: 0–10 V |
|
Input Impedance |
>10 MΩ |
|
Accuracy |
±0.196% of full scale |
|
Resolution |
16-bit ADC |
|
Isolation |
1000 VAC RMS or ±1000 VDC |
|
Overload Protection |
120% for 2 seconds; 150% for 0.1 seconds |
|
Common Mode Rejection |
>60 dB at 120 Hz |
|
Operating Temperature |
-40°C to +70°C |
|
Storage Temperature |
-40°C to +85°C |
|
Classification |
High-level, G3 |
Description
The Honeywell 8C-PAIN01 51454356-175 is an analog input module. This module receives and processes high-level current signals from various transmitters and sensors in the field. Through its built-in signal conversion and self-diagnostic circuits, it converts these continuous analog signals representing field physical quantities into digital codes that the system's main control unit can recognize, continuously uploading them to the controller to assist the system in automating the monitoring and status determination of the production process.
Applications
Petroleum refinery: Collects long-distance high-level voltage signals for precise process control in complex refining operations.
Pulp and paper plant: Monitors equipment status under corrosive gas environments to ensure stable operation.
Precision manufacturing plant: Provides real-time sensor voltage feedback for high-speed closed-loop control systems.
Mining and washing plant: Monitors current load of crushing and conveying equipment to prevent overload damage.
Features
High Precision Measurement: 16-bit resolution ensures accurate process data acquisition
Multi-signal Capability: Supports both current and voltage inputs
Robust Isolation: 1000 VAC isolation protects system and ensures safety
Overload Protection: Built-in safeguards against signal surges
Noise Immunity: Strong common mode rejection for reliable operation in noisy environments
Industrial Reliability: Wide operating temperature range for harsh conditions
FAQ
Q: How many channels does 8C-PAIN01 51454356-175 analog input module support and what signal types does it accept?
A: 16 single-ended channels, supporting 4–20 mA current and 0–10 V voltage signals.
Q: What is the conversion resolution and measurement accuracy of 8C-PAIN01 51454356-175?
A: 16-bit ADC, accuracy ±0.196% of full scale.
Q: What is the electrical isolation rating of 8C-PAIN01 51454356-175?
A: 1000 VAC RMS or ±1000 VDC isolation.
Q: What is the corrosion rating and operating temperature range of 8C-PAIN01 51454356-175?
A: G3 high-level corrosion rating, operating temperature -40°C to +70°C.
Q: What is the input impedance and overload protection of 8C-PAIN01 51454356-175?
A: Input impedance >10 MΩ, supports 120% overload for 2 s or 150% overload for 0.1 s.