Siemens 6ES7132-4HB00-0AB0 SIMATIC ET 200S 2RO NO Relay Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Apply external 6 A output fuse protection.
- Use a maximum 4 A per channel at +60 °C.
- Preserve SELV/PELV separation across both channels.
- Review the bridge arrangement when changing product level.
6ES7132-4HB00-0AB0 SIMATIC ET 200S 2RO NO Relay Output Module
A two-channel normally open relay module for loads up to 120 V DC or 230 V AC, with a 24 V DC module supply and temperature-dependent current limits.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4HB00-0AB0 |
| Product Type | Relay output module |
| Core Function | Isolated switching of field loads |
| Application | ET 200S 24 V DC potential groups |
Isolated relay contacts
The two relay channels are electrically isolated from each other and from the backplane.
Temperature-dependent current
Each output permits up to 5 A at 50 °C and up to 4 A at 60 °C.
External output protection
The relay outputs need external 6 A fuse protection.
Product Overview
6ES7132-4HB00-0AB0 switches two field circuits through normally open relay contacts in an ET 200S station.
Its module electronics require a 24 V DC potential group even when the isolated relay contacts switch an AC load, and the selected load voltage and category determine contact life.
Key Functions
Switch AC or DC field loads
The isolated relay-contact arrangement accepts loads up to 120 V DC or 230 V AC within the permitted switching capacity.
Separate the two output circuits
The relay channels are electrically isolated from one another and from the module supply and backplane.
Indicate output state
A green LED for each channel shows its commanded state without a module diagnostic function.
Official Specifications
| Output contact arrangement | 2 normally open relay outputs |
|---|---|
| Rated module-electronics supply | 24 V DC |
| Maximum switched load voltage | 120 V DC or 230 V AC |
| Maximum channel current by temperature | 5 A up to +50 °C; 4 A up to +60 °C |
| Minimum switching load | 17 V and 8 mA |
| Maximum current from L+ | 30 mA |
| Typical module power loss | 0.6 W |
| Maximum load-cable length | 600 m unshielded; 1,000 m shielded |
| Relay isolation | Between channels and between outputs, module supply and backplane |
| Output-to-bus and output-to-supply isolation test | 1,500 V AC |
| Supply-to-backplane isolation test | 500 V DC |
| Maximum switching frequencies | 2 Hz resistive or lamp loads; 0.5 Hz inductive loads |
| External output fuse | 6 A required |
| Internal inductive-voltage limitation | None |
| Parallel output connection | Not permitted for redundancy or current increase |
| Status indication | Green LED per channel |
| Dimensions (W × H × D) | 15 × 81 × 52 mm |
| Approximate module weight | 50 g |
Frequently Asked Questions
May I put 6ES7132-4HB00-0AB0 in an ET 200S power group supplied with 230 V AC?
No, the module electronics must be supplied from a 24 V DC potential group.
Can each output of 6ES7132-4HB00-0AB0 carry 5 A at an ambient temperature of 60 °C?
No, the permitted channel current at 60 °C is limited to 4 A.
Do I need a fuse outside 6ES7132-4HB00-0AB0 for the relay outputs?
Yes, each relay output requires external 6 A fuse protection.
Can I parallel the two contacts of 6ES7132-4HB00-0AB0 to increase load current?
No, parallel output connection is not permitted for current increase or redundant load control.
Can I mix an SELV circuit with a non-SELV circuit on the two channels of 6ES7132-4HB00-0AB0?
No, when one channel carries SELV or PELV low voltage, the other channel must also carry SELV or PELV low voltage.
What wiring difference should I account for when replacing an earlier product level of 6ES7132-4HB00-0AB0?
From product level 2 the internal bridge between terminals 2 and 6 is absent and any required replacement bridge is made externally between terminals 3 and 7.
Can 6ES7132-4HB00-0AB0 switch a 5 V low-current signal directly?
No, the specified minimum switching load is 17 V and 8 mA.