- Overview
- Specifications
- Description
- Applications
- Operation
- FAQ
- Recommended Products
Overview
Place of Origin: |
USA |
Brand Name: |
GE |
Model Number: |
IC670MDL740 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Module Name |
IC670MDL740 Positive Output Module |
|
Dimensions |
5.5 x 8.6 x 8.2 cm |
|
Weight |
0.22 kg |
|
User Input Voltage |
10–30 VDC, 24 VDC nominal, 4 A maximum |
|
Output Voltage Range |
9.2–29.5 VDC |
|
Output Current |
0.5 A max per point, 4 A max per module |
|
Outputs per Module |
16 |
|
Indicators |
Logic side LEDs indicate on/off status, blown fuse fault, and user supply below 9.8 VDC |
|
Isolation |
User input to logic, user input to frame ground, group to group: 250 VAC continuous / 1500 VAC for 1 min; no isolation between points in a group |
|
Current Drawn from BIU Power Supply |
111 mA maximum |
|
Inrush Current |
2 A max for 100 ms |
|
Maximum Load Current (Resistive) |
0.5 A from 10 VDC to 30 VDC |
|
Minimum Load Current |
1 mA per point |
|
Output Voltage Drop |
0.5 V maximum |
|
Output Leakage Current |
0.5 mA at 30 VDC |
|
Response Time-On |
200 µs max with 0.5 A resistive load |
|
Response Time-Off |
200 µs max with 0.5 A resistive load |
|
Protection (Each Output) |
Fuse: Metric 5 x 20 mm – 5 A, 250 V, Slow Acting, common to all outputs |
Description
The 12/24 VDC Positive Output Module (IC670MDL740) provides a single group of 16 discrete outputs. The outputs are positive logic or sourcing-type outputs. They switch the loads to the positive side of the DC supply, and thus supply current to the load. The power that runs the module itself comes from the power supply in the Bus Interface Unit. An external source of DC power must be provided for the switches that power the loads. Within the module, the external power supply is connected to a 5A fuse. During operation, the module monitors this power to be sure it is above 9.8 VDC. If not, it is interpreted as a fault by the Bus Interface Unit.
Applications
Automotive manufacturing plants: Controlling solenoid valves, cylinders, small conveyor motors, and indicator lights on assembly lines.
Food and packaging industries: Driving packaging machine forks, sealing heater contactors, and sorting levers.
Water treatment facilities: Controlling the start and stop of dosing pumps and the on/off status of electric valves.
Warehouse and logistics automation: Sensor-driven actuators for sorting systems.
Textile and plastics machinery: Precisely controlling heating element drivers and mold locking devices.
Operation
After checking the Board ID and verifying that the module is receiving appropriate logic power from the Bus Interface Unit (as reflected by the state of the module’s Power LED), the Bus Interface Unit then sends output data to the module in serial format. During transmission, the module automatically loops this data back to the Bus Interface Unit for verification. Serial to parallel converters convert this data into the parallel format needed by the module. Opto-isolators isolate the module’s logic components from field outputs. Power from the external power supply is used to drive the FETs that source current to the loads.
FAQ
Q: Does the IC670MDL740 come with a warranty?
A: Yes, the IC670MDL740 includes a 1-year warranty.
Q: What wiring configuration is supported by the IC670MDL740?
A: The IC670MDL740 supports positive logic wiring.
Q: How many output channels does the IC670MDL740 have?
A: The IC670MDL740 has a single group of 16 positive logic output channels.
Q: What is the output current per point of the IC670MDL740?
A: The IC670MDL740 delivers 0.5 Amperes per point and 4 Amperes per module.