Siemens SIWAREX U 7MH4601-1AA01 Single-Channel Weighing Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Confirm the application requires one weighing channel for one scale.
- Verify the S7-300 slot or ET 200M and IM 153-1 integration route.
- Provide 24 V DC auxiliary power and the required S7 backplane supply.
- Check load-cell sensitivity, bridge resistance and four- or six-wire wiring.
- For the successor 7MH4950-1AA01, verify its 6 V excitation and restore calibration or recalibrate.
Siemens · SIWAREX U
7MH4601-1AA01 Single-Channel Weighing Module
Siemens 7MH4601-1AA01 is the SIWAREX U single-channel weighing module for integrating one strain-gauge scale directly into SIMATIC S7-300 or through an ET 200M distributed I/O station.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7MH4601-1AA01 |
| Product Type | Single-Channel Weighing Module |
| Core Function | Integrates one strain-gauge scale into SIMATIC control |
| Application or Compatible Series | SIMATIC S7-300 and ET 200M systems |
Exact Channel Identification
Use the one-channel hardware for one weighing scale.
Sensor and Serial Interfaces
Plan the load-cell input together with the SIMATIC backplane, RS232 and TTY interfaces.
Integration Route
Install directly in S7-300 or distribute through ET 200M with an IM 153-1 interface module.
Product Overview
Siemens 7MH4601-1AA01 is the SIWAREX U single-channel weighing module for integrating one strain-gauge scale directly into SIMATIC S7-300 or through an ET 200M distributed I/O station.
Sixteen-bit A/D conversion supports selectable 1, 2 and 4 mV/V measuring ranges. The 10.3 V DC excitation circuit supports approved sensor wiring up to 1,000 m. SIWATOOL commissioning through RS232 is combined with battery-free EEPROM parameter storage.
Key Functions
Configurable Weight Conversion
Sixteen-bit A/D conversion supports selectable 1, 2 and 4 mV/V measuring ranges.
Long-Distance Load-Cell Connection
The 10.3 V DC excitation circuit supports approved sensor wiring up to 1,000 m.
Service and Data Retention
SIWATOOL commissioning through RS232 is combined with battery-free EEPROM parameter storage.
Official Specifications
| Auxiliary Supply | 24 V DC; static 20.4 to 28.8 V; dynamic 18.5 to 30.2 V |
|---|---|
| Module Current and Power Loss | 220 mA maximum; 4.8 W typical |
| Backplane Current | 100 mA typical at 5 V |
| Accuracy Class | 0.05% at 20 °C ±10 K |
| Minimum Signal per Division | 1.5 µV |
| Update Rate | 20 ms; 100 ms up to release status 4 |
| ADC Resolution | 16 bit; 65,535 parts |
| Measuring Ranges | 0 to 1, 0 to 2 and 0 to 4 mV/V |
| Permissible Signal Range | −1.5 to 42.5 mV |
| Maximum Load-Cell Distance | 1,000 m |
| Load-Cell Excitation | 10.3 V DC typical; 240 mA maximum |
| Load Resistance without Ex-i | Greater than 41 Ω and less than 4,010 Ω |
| RS232 Interface | 9,600 baud; 15 m maximum |
| TTY Interface | 9,600 baud; 1,000 m maximum with external supply |
| EEPROM Endurance | 100-year retention; 100,000 write cycles |
| Degree of Protection | IP20 in an S7 rack; IP10 as a standalone module |
| Operating Temperature | 0 to +60 °C horizontal; 0 to +40 °C vertical |
| Dimensions and Weight | 40 × 125 × 130 mm; approximately 325 g |
Frequently Asked Questions
Can 7MH4601-1AA01 connect two weighing channels?
No, the single-channel module is intended for one scale.
Where can I install 7MH4601-1AA01 in a SIMATIC system?
Install it directly in an S7-300 station or use ET 200M for distributed integration.
Which load cells can I connect to 7MH4601-1AA01?
Use strain-gauge Wheatstone-bridge load cells with a characteristic value up to 4 mV/V and a suitable four- or six-wire connection.
How should I commission 7MH4601-1AA01 from a PC?
Connect SIWATOOL through the RS232 interface at 9,600 baud and keep the cable within 15 m.
Can 7MH4601-1AA01 drive a remote weight display?
Yes, the TTY interface can transmit to a remote display over a loop up to 1,000 m with an external supply.
What supply should I provide for 7MH4601-1AA01?
Provide a safely isolated 24 V DC supply within the specified static or dynamic tolerance range.
What should I check before replacing 7MH4601-1AA01 with the newer module?
Confirm load-cell compatibility with the successor 6 V excitation and restore saved calibration data or recalibrate the scale.