Overview
- Configure the correct module and output addresses in the STEP 7 project.
- Keep redundant parallel outputs within the same output group.
- Account for the short switch-on pulse where connected equipment detects fast signals.
- Use channel LEDs for local status checks and do not expect module diagnostic interrupts.
SIEMENS SIMATIC S7-300
6ES7322-1BL00-0AA0 SIMATIC S7-300 SM 322 Digital Output Module
Provide 32 transistor outputs for DC solenoid valves, contactors and signal lamps, with electrically isolated groups and per-channel status indication.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7322-1BL00-0AA0 |
| Product Type | Digital output module |
| Core Function | Switch DC field actuators |
| Application | S7-300 automation stations |
Grouped output circuits
Four groups of eight outputs separate the load circuits.
Front connector wiring
A 40-pin front connector carries the actuator connections.
Load-aware installation
Group-current limits depend on cabinet temperature and mounting position.
Product Overview
6ES7322-1BL00-0AA0 is an SM 322 output module for operating 24 V DC field loads from a SIMATIC S7-300 station. Its 32 channels are electrically isolated in groups of eight and provide a rated output current of 0.5 A per channel.
Electronic short-circuit protection limits output faults, while individual green LEDs show channel status; the module does not provide diagnostic interrupts or readable channel diagnostics.
Key Functions
Drive DC switching loads
The outputs operate solenoid valves, DC contactors and signal lamps within the specified current and lamp-load limits.
Separate field potential groups
Groups of eight channels are isolated from one another and from the backplane bus for grouped load-circuit wiring.
Indicate active channels locally
A green LED per channel provides a direct view of the output state during commissioning and maintenance.
Official Specifications
| Output Channel Arrangement | 32 channels in 4 electrically isolated groups of 8 |
|---|---|
| Rated Load Voltage | 24 V DC |
| Rated Output Current | 0.5 A per channel; permitted ON-state range 5 mA to 0.6 A |
| Group Current, Horizontal Mounting | 4 A up to 40 °C; 3 A up to 60 °C |
| Group Current, Vertical Mounting | 2 A up to 40 °C |
| Backplane Current Consumption | Maximum 110 mA |
| No-Load Load-Supply Current | Maximum 160 mA |
| Typical Power Dissipation | 6.6 W |
| Output ON-State Voltage | At least L+ minus 0.8 V |
| OFF-State Residual Current | Maximum 0.5 mA |
| Output Switching Delay | Maximum 100 µs OFF to ON; maximum 500 µs ON to OFF for resistive loads |
| Permitted Load Resistance | 48 Ω to 4 kΩ |
| Lamp Load | Maximum 5 W per output |
| Maximum Switching Frequencies | 100 Hz resistive; 0.5 Hz inductive DC13; 10 Hz lamp loads |
| Electronic Short-Circuit Protection | Typical response threshold 1 A |
| Isolation Test Voltage | 500 V DC |
| Actuator Connection | 40-pin front connector |
| Module Dimensions | 40 × 125 × 120 mm (W × H × D) |
Frequently Asked Questions
How many solenoid-valve outputs does 6ES7322-1BL00-0AA0 provide?
The module provides 32 outputs rated at 24 V DC and 0.5 A per channel.
Does 6ES7322-1BL00-0AA0 support Front connector wiring for mobile equipment?
Use a 40-pin front connector for the output and load-supply connections.
How should I derate 6ES7322-1BL00-0AA0 in a horizontally mounted rack at 60 °C?
Limit the total output current of each group to 3 A at 60 °C.
Can I parallel outputs of 6ES7322-1BL00-0AA0 to obtain a higher current?
No, parallel outputs are allowed only for redundant load control within the same group and cannot be used to increase output capacity.
Will 6ES7322-1BL00-0AA0 send a diagnostic interrupt for a channel fault?
No, the module provides channel-status LEDs but has no diagnostic interrupt or readable diagnostic function.
What lamp load can I connect to an output of 6ES7322-1BL00-0AA0?
Each output can switch a lamp load of up to 5 W.
What should I consider when switching the 24 V supply to 6ES7322-1BL00-0AA0 with a mechanical contact?
The circuit design can produce an ON signal of approximately 50 µs at the outputs when the load supply is switched on.