- Use a compatible S7-22X CPU and include both module supply currents in the station budget.
- Select the common input range with power off and allow the selected switch settings to be read at power-on.
- Allow fifteen minutes of stabilization before calibration and use the specified input averaging.
- Respect the distinct voltage-output and current-output load limits and the absence of field-to-logic isolation.
6ES7235-0KD22-0XA8 SIMATIC S7-200 CN EM 235 Analog I/O Module
EM 235 CN with four differential analog inputs, one voltage or current output and DIP-switch input-range selection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7235-0KD22-0XA8 |
| Product Type | Combined analog I/O module |
| Core Function | Analog signal acquisition and command output |
| Application | Compatible S7-22X CPU stations |
Four-channel analog acquisition
Differential channels accept the selected voltage range or zero-to-twenty-milliampere current signals.
Analog actuator command
The single output generates a bipolar voltage or unipolar current command.
Hardware range and calibration
DIP switches select the shared input range while offset and gain adjustments calibrate the input amplifier.
Product Overview
6ES7235-0KD22-0XA8 adds four differential analog inputs and one analog output to a compatible S7-22X CPU.
The module uses a common input range and format across its input channels, with gain and offset calibration affecting the shared amplifier stage and separate voltage/current output load limits.
Key Functions
Four-channel analog acquisition
Differential channels accept the selected voltage range or zero-to-twenty-milliampere current signals.
Analog actuator command
The single output generates a bipolar voltage or unipolar current command.
Hardware range and calibration
DIP switches select the shared input range while offset and gain adjustments calibrate the input amplifier.
Official Specifications
| Analog input channels | 4 differential inputs |
|---|---|
| Current input range | 0–20 mA |
| Voltage input selection | DIP-selected unipolar or bipolar voltage ranges, up to ±10 V |
| Input resolution | 12 bits unipolar; 11 bits plus sign bipolar |
| Input impedance | At least 2 MΩ voltage; 250 Ω current |
| Maximum input limits | 30 V DC or 32 mA |
| A/D conversion time | Less than 250 µs |
| Input step response | 1.5 ms to 95% |
| Common-mode rejection | 40 dB, DC to 60 Hz |
| Input common-mode constraint | Signal voltage plus common-mode voltage must remain within ±12 V |
| Analog output | 1 channel; ±10 V or 0–20 mA |
| Output resolution | 11 bits for voltage and current |
| Output load limits | Voltage: minimum 5000 Ω; current: maximum 500 Ω |
| Output settling time | 100 µs voltage; 2 ms current |
| Output accuracy | Typical ±0.5% full scale at 25°C; worst-case ±2% from 0 to +55°C |
| DC supply range | 20.4–28.8 V DC |
| Power requirements | 30 mA at 5 V DC; 60 mA at 24 V DC with the output at 20 mA |
| Typical power loss | 2 W |
| Field-to-logic isolation | None |
| Dimensions and approximate weight | 71.2 × 80 × 62 mm (W × H × D); 186 g |
Frequently Asked Questions
Can each input on 6ES7235-0KD22-0XA8 use a different DIP-selected signal range?
All four inputs use the same selected analog range and format.
Will a DIP-switch range change take effect immediately while 6ES7235-0KD22-0XA8 is powered?
The switch settings are read only when power is turned on.
Does adjusting the offset and gain of 6ES7235-0KD22-0XA8 calibrate only one input channel?
The adjustments affect the amplifier after the multiplexer and therefore affect all input channels.
What input filtering is needed to meet the stated performance of 6ES7235-0KD22-0XA8?
Enable analog input filtering for all module inputs and average at least sixty-four samples.
Can I use a one-kilohm voltage-output load with 6ES7235-0KD22-0XA8?
Voltage-output operation requires a load impedance of at least five thousand ohms.
Can I connect an RTD or thermocouple directly to 6ES7235-0KD22-0XA8?
The module accepts voltage and current input signals rather than direct RTD or thermocouple measurements.
Does the analog output of 6ES7235-0KD22-0XA8 have the same twelve-bit resolution as a unipolar input?
The analog output has eleven-bit resolution in both voltage and current modes.