Siemens 6ES7193-0CB30-0XA0 ET 200B TB4/DC Spring-Terminal Block
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Compatible wider arrangements include 32DI, 32DI 0.2 ms, 32DO, 16DI/16DO, 24DI/8DO and 16DO/2A electronics.
- The fourth additional ground tier belongs to TB4M/DC rather than this TB4/DC base.
- Use coding-slide position 1 for the 24 V digital module class.
- With an IM 308-C or S7/M7 DP master, use station addresses 1–99; with IM 308-B, use 3–99.
- Make address changes effective with the required STOP/RUN transition.
- Use the TR5-T 2.5 A, 250 V fuse; the replacement order number is 6ES7193-0DB00-0XA0.
- For fuse replacement, set STOP and remove the electronics block before replacing F1 and returning the station to RUN.
6ES7193-0CB30-0XA0 ET 200B TB4/DC Spring-Terminal Block
The 235 mm wide TB4/DC base with three-tier spring-latch wiring, station addressing, module-class coding and a 2.5 A sensor-supply/logic-protection fuse.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-0CB30-0XA0 |
| Product Type | Digital-station terminal block |
| Core Function | Retains the permanent station field wiring |
| Application | SIMATIC ET 200B digital I/O stations |
Wide digital base
The 235 mm terminal field supports the TB4/DC electronics arrangements.
Station identity stays on the base
The address selectors and coding slide are located on the terminal block.
Fused internal supply
The TR5-T 2.5 A fuse protects the sensor supply and internal-logic supply.
Product Overview
6ES7193-0CB30-0XA0 provides the permanent spring-terminal wiring base for the wider ET 200B digital electronics arrangements.
Its three-tier terminal field includes the station address selectors, module-class coding and fused internal supply, while the compatible electronics block determines the signal assignment and diagnostics; the base is 235 mm wide.
Key Functions
Keep station wiring in place
The terminal block retains the permanent wiring when the plug-on electronics block is removed.
Set the station and module class
Two decimal selectors set the station number, while the six-position coding slide prevents an electronics block of the wrong class from being fitted.
Protect the sensor and logic supplies
The replaceable F1 fuse protects the sensor supply against short circuits and the internal logic against reversed supply polarity and voltage spikes.
Official Specifications
| Rated DC supply and permissible range | 24 V DC nominal; 18.5–30 V DC including ripple |
|---|---|
| Electronics current consumption | 100 mA typical; 200 mA maximum |
| Galvanic isolation | Between the electronics block and PROFIBUS DP |
| Operating temperature | 0 to +60 °C |
| Dimensions (W × H × D) | 235 × 130 × 59 mm |
| Approximate terminal-block weight | 800 g |
| Conductor cross-section without ferrule | 0.08–2.5 mm² for supply and signal conductors |
| Conductor cross-section with ferrule | Up to 1.5 mm² for supply and signal conductors |
| Sensor-supply and logic-protection fuse | TR5-T 2.5 A, 250 V miniature fuse |
| Mechanical module-class coding | Six-position coding slide; position 1 for 24 V digital modules |
| Station-address selector setting range | Two decimal digits, 00–99 |
| Fieldbus connector | 9-pin PROFIBUS DP interface |
| Field-terminal layout | Three-tier spring-latch connections, numbered 1–32, 33–64 and 65–96 |
| Mounting options | Standard sectional rail or direct mounting on a flat surface |
Frequently Asked Questions
Can 6ES7193-0CB30-0XA0 accept the ET 200B 16DO/2A electronics block?
The wide TB4/DC base is one of the supported terminal bases for the 16DO/2A electronics block.
Does 6ES7193-0CB30-0XA0 include the extra fourth ground tier of the TB4M/DC version?
The extra fourth terminal tier belongs to the separate TB4M/DC version.
How much supply ripple is allowed within the voltage range of 6ES7193-0CB30-0XA0?
The complete supply waveform, including ripple, must remain between 18.5 and 30 V DC.
Can supply conductors be connected to 6ES7193-0CB30-0XA0 without ferrules?
Supply and signal conductors without ferrules may have cross-sections from 0.08 to 2.5 mm².
What happens to the internal logic if the F1 fuse in 6ES7193-0CB30-0XA0 opens?
Opening the fuse de-energizes the module internal logic.
Why does a new station number on 6ES7193-0CB30-0XA0 not take effect immediately?
The selected station number becomes effective only after a STOP-to-RUN transition of the ET 200B station.
How much electronics current should be budgeted for 6ES7193-0CB30-0XA0?
The terminal-block current consumption is 100 mA typical and 200 mA maximum.