Siemens SIMATIC PN/PN Coupler 6ES7158-3AD10-0XA0
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
Siemens • SIMATIC PROFINET Couplers
6ES7158-3AD10-0XA0 SIMATIC PN/PN Coupler
The SIMATIC PN/PN Coupler transfers I/O, safety and record data between two separate PROFINET networks, supporting up to four controllers per subnet, redundant 24 V supply and replaceable SIMATIC BusAdapters.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7158-3AD10-0XA0 |
| Product Type | PROFINET subnet-to-subnet data coupler |
| Core Function | Exchanges deterministic I/O and records between separate PROFINET networks |
| Application or Compatible Series | Machines and plant cells requiring controller data exchange while keeping PROFINET subnets separated |
Exact Identification
Match 6ES7158-3AD10-0XA0 character by character and confirm the complete SIMATIC PN/PN Coupler designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The SIMATIC PN/PN Coupler transfers I/O, safety and record data between two separate PROFINET networks, supporting up to four controllers per subnet, redundant 24 V supply and replaceable SIMATIC BusAdapters.
The coupler transfers configured data without merging the two Ethernet subnets. I/O, MSI/MSO, PROFIsafe and data-record mechanisms support machine-to-machine and cell-to-cell coordination. Redundant power connections and replaceable BusAdapters support maintainable network installations.
Key Functions
Separated PROFINET Networks
The coupler transfers configured data without merging the two Ethernet subnets.
Flexible Controller Exchange
I/O, MSI/MSO, PROFIsafe and data-record mechanisms support machine-to-machine and cell-to-cell coordination.
Service-Oriented Hardware
Redundant power connections and replaceable BusAdapters support maintainable network installations.
Official Specifications
| Maximum Controllers per Subnet | 4 |
|---|---|
| PROFINET Device ID | 0604H |
| Vendor ID | 002AH |
| I&M Data | I&M0 to I&M3 |
| Minimum Isochronous Cycle | 500 µs |
| PROFIsafe Data Exchange | Supported |
| MSI and MSO | Supported |
| Data-Record Communication | Supported |
| Maximum Record Length | 4,096 bytes |
| Record FIFO Depth | 8 |
| Record-Coupling Modules | Up to 16 |
| Local I/O Coupling Modules | Up to 16 in non-isochronous operation |
| Rated Supply Voltage | 24 V DC |
| Permissible Supply Range | 19.2 to 28.8 V DC |
| Maximum Input Current | 360 mA |
| Power Failure Buffer | 10 ms |
| Degree of Protection | IP20 |
| Mounting Rail | 7.5 mm or 15 mm profile |
Frequently Asked Questions
How does 6ES7158-3AD10-0XA0 keep the two PROFINET networks separate?
Each side is configured as its own device on an independent subnet while only the assigned process data crosses the coupler.
Can safety data pass through 6ES7158-3AD10-0XA0?
Yes; configure and validate the PROFIsafe transfer and complete safety program on both sides.
Which BusAdapters are required for 6ES7158-3AD10-0XA0?
Select compatible SIMATIC BusAdapters for the physical media and port arrangement because they are ordered separately.
How should controller ownership be assigned on 6ES7158-3AD10-0XA0?
Map each module and submodule to the intended controller and keep the assignment consistent on both engineering projects.
What should be backed up before replacing 6ES7158-3AD10-0XA0?
Save both hardware configurations, device names, IP settings, module mapping, safety data and record-transfer setup.
Can 6ES7158-3AD10-0XA0 use redundant 24 V power?
Yes; wire the approved redundant supply arrangement and test each feed independently.
What should be tested after commissioning 6ES7158-3AD10-0XA0?
Verify device names, controller connections, byte mapping, quality status, record transfers, safety exchange and diagnostics on both subnets.
Compatibility & Ordering Notes
Compatibility Checklist
- Engineer each side as a separate PROFINET device on its own subnet.
- Match BusAdapters, controller ownership and the exact module or submodule mapping.
- Validate standard data, records and PROFIsafe exchange on both networks.