Siemens 6ES7141-1BF30-0XB0 SIMATIC ET 200X EM 141 Digital Input Extension
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Check the ET 200X extension arrangement and use the EM 141 sensor-connector pin assignment.
- Select the input delay and hardware-interrupt behavior required by the connected sensor.
- Keep unshielded input wiring within 30 m.
- Size the sensor loads against both the per-output and total supply-current limits at the actual ambient temperature.
6ES7141-1BF30-0XB0 SIMATIC ET 200X EM 141 Digital Input Extension
Eight-channel 24 V DC EM 141 extension with four five-pole M12 connections, configurable input delay and channel diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7141-1BF30-0XB0 |
| Product Type | Digital input extension module |
| Core Function | Distributed acquisition of sensor states |
| Application | ET 200X stations |
Adjustable input filtering
Input delay can be set to 0.5, 3, 15 or 20 ms to suit signal timing and filtering needs.
Channel-level fault location
Configurable diagnostics report wire breaks and short circuits per channel, with dedicated fault indication.
Input-event interrupts
Parameterizable hardware interrupts allow the controller to respond to input events through the ET 200X station.
Product Overview
6ES7141-1BF30-0XB0 extends an ET 200X station with eight digital input channels through four five-pole M12 connectors.
Its configurable input filtering and hardware interrupts support sensor acquisition, while channel-specific wire-break and short-circuit diagnostics help locate field-wiring faults.
Key Functions
Adjustable input filtering
Input delay can be set to 0.5, 3, 15 or 20 ms to suit signal timing and filtering needs.
Channel-level fault location
Configurable diagnostics report wire breaks and short circuits per channel, with dedicated fault indication.
Input-event interrupts
Parameterizable hardware interrupts allow the controller to respond to input events through the ET 200X station.
Official Specifications
| Digital input bank | 8 inputs, 24 V DC, IEC 61131 Type 2 |
|---|---|
| Sensor connections | 4 five-pole M12 connectors |
| Backplane current | 30 mA maximum from 5 V DC |
| Sensor supply outputs | 4 electronically protected outputs |
| Sensor supply at up to 40°C | 0.5 A maximum per output; 0.9 A total |
| Sensor supply at up to 55°C | 0.4 A maximum per output; 0.7 A total |
| Typical power loss | 1.5 W |
| Signal voltage thresholds | Signal 0: −3 to +5 V; signal 1: +13 to +30 V |
| Typical input current | 10 mA for signal 1 |
| Selectable input delay | 0.5, 3, 15 or 20 ms |
| Unshielded field cable | 30 m maximum |
| Two-wire sensor quiescent current | 1.5 mA maximum |
| Interrupt capabilities | Parameterizable diagnostic and hardware interrupts |
| Channel fault detection | Wire break and short circuit, channel by channel |
| Local indications | Red SF group-error LED, green input status and red F channel-fault LED |
| Input separation | No isolation between digital inputs |
| Permissible circuit potential difference | 75 V DC or 60 V AC |
| Insulation test voltage | 500 V DC |
| Dimensions | 87 × 110 × 55 mm (W × H × D); module-body width 60 mm |
| Approximate mass | 250 g |
Frequently Asked Questions
Can I choose a shorter input delay on 6ES7141-1BF30-0XB0 for a fast sensor?
The delay can be parameterized to 0.5, 3, 15 or 20 ms.
How can 6ES7141-1BF30-0XB0 tell me which field circuit has failed?
Channel-specific wire-break and short-circuit diagnostics work with the red F channel-fault indication.
Can 6ES7141-1BF30-0XB0 generate an interrupt when an input event occurs?
Hardware interrupts can be enabled through parameter assignment.
How does temperature affect the sensor supply of 6ES7141-1BF30-0XB0?
The limit changes from 0.5 A per output and 0.9 A total at up to 40°C to 0.4 A per output and 0.7 A total at up to 55°C.
How many M12 sensor connectors are fitted to 6ES7141-1BF30-0XB0?
Four five-pole M12 connections serve the eight digital inputs.
Can 6ES7141-1BF30-0XB0 accept a two-wire sensor that leaks 2 mA when off?
The maximum permitted quiescent current for a two-wire sensor is 1.5 mA.
What is the minimum high-state input level on 6ES7141-1BF30-0XB0?
A high-state input must be between +13 and +30 V.