Siemens 6ES7141-1BF30-0XB0 SIMATIC ET 200X EM 141 Digital Input Extension
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Inspectio arrangementis extensionis ET 200X et usus assignationis pinorum EM 141 pro connexione sensorum.
- Select the input delay and hardware-interrupt behavior required by the connected sensor.
- Keep unshielded input wiring within 30 m.
- Size the sensor loads against both the per-output and total supply-current limits at the actual ambient temperature.
6ES7141-1BF30-0XB0 SIMATIC ET 200X EM 141 Digital Input Extension
Octo-channelis 24 V DC EM 141 extension cum quattuor quinque-polari connectionibus M12, cum configurabili temporis dilatione ingressus et diagnosticis canalium.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7141-1BF30-0XB0 |
| Typus Producti | Modulus extensionis digitalis ingressus |
| Functio principalis | Acquisitio distributa statuum sensorum |
| Applicatio | Statio ET 200X |
Filtratio Intrationis Regulabilis
Dilatio ingressus configurabilis est ad 0,5, 3, 15 aut 20 ms, ut conveniat necessitatibus temporis signorum et filtrationis.
Localisatio defectuum in nivello canalis
Diagnostics configurabiles referunt interruptiones filorum et circuitus breves per singulos canales, cum indicatione defectus speciali.
Interruptus eventus ingressus
Interruptus hardware parameterizabiles permittunt controlleri ad eventus input respondere per stationem ET 200X.
Product Overview
6ES7141-1BF30-0XB0 extendit stationem ET 200X cum octo canalibus input digitalibus per quattuor connectores M12 quinque-polares.
Filtratio input configurabilis et interruptus hardware suadent acquisitionem sensorum, dum diagnosices specificae pro canalibus de ruptura fili et corto circuitu iuvant locare defectus in connexionibus campi.
Key Functions
Filtratio Intrationis Regulabilis
Dilatio ingressus configurabilis est ad 0,5, 3, 15 aut 20 ms, ut conveniat necessitatibus temporis signorum et filtrationis.
Localisatio defectuum in nivello canalis
Diagnostics configurabiles referunt interruptiones filorum et circuitus breves per singulos canales, cum indicatione defectus speciali.
Interruptus eventus ingressus
Interruptus hardware parameterizabiles permittunt controlleri ad eventus input respondere per stationem ET 200X.
Official Specifications
| Banca intrantium digitalium | 8 input, 24 V DC, Typus IEC 61131-2 |
|---|---|
| Sensor Connections | 4 connectores M12 quinque-polares |
| Currentis dorsalis | 30 mA maximum ex 5 V DC |
| Exitus Alimentationis Sensorum | 4 output electronicam protegentur |
| Supplicatio sensorum usque ad 40°C | 0.5 A maximum per output; 0.9 A totalis |
| Alimentatio sensoris usque ad 55 °C | 0,4 A maximum per outputum; 0,7 A totalis |
| Perditio potentiæ typica | 1.5 W |
| Ambang Tegangan Sinyal | Signum 0: −3 ad +5 V; signum 1: +13 ad +30 V |
| Currentis Ingressus Typicus | 10 mA pro signo 1 |
| Ritardo d’Ingresso Selezionabile | 0.5, 3, 15 aut 20 ms |
| Cavea campi non scutata | 30 m maximum |
| Currens Quiescens Sensoris Duo-Filarii | 1,5 mA maximus |
| Capacitates interrumpendi | Interruptus diagnosticus et interruptus hardware parametrizabiles |
| Detectio defectus canalium | Ruptura fili et curtus circuitus, canalibus singulis |
| Indicationes locales | Rubra LED de error del grupu SF, verde LED de estatus d'entrada y rubra LED de fallu del canal F |
| Separación d'entrades | Nun hai aislamientu ente les entrades dixitales |
| Differentia de potential permitte in le circuito | 75 V CC ou 60 V CA |
| Testis voltagii isolationis | 500 V DC |
| Dimensiones | 87 × 110 × 55 mm (A × A × P); anchu del cuerpu del módulu: 60 mm |
| Massa approximata | 250 g |
Quaestiones Frequenter Rogatae
¿Puedo escoyer un retardu más curtio na entrada del 6ES7141-1BF30-0XB0 pa un sensor rápidu?
El retardu pue ser parametrizáu a 0,5, 3, 15 o 20 ms.
¿Cómo puede el 6ES7141-1BF30-0XB0 indicame qué circuitu de campu falló?
Los diagnósticos específicos per canal pa rotura de cable y curtiu circuitu funcionen cola indicación rubra de fallu del canal F.
¿Pue'l 6ES7141-1BF30-0XB0 xenerar una interrupción cuando asocede un eventu d'entrada?
Les interrupciones de hardware pueden activase per mediu d'asignación de parámetros.
Quomodo temperatus influent in subministram sensoris 6ES7141-1BF30-0XB0?
Limites mutantur ab 0.5 A per output et 0.9 A totali ad temperaturam usque ad 40°C ad 0.4 A per output et 0.7 A totali ad temperaturam usque ad 55°C.
Quot connexiones sensorum M12 habet 6ES7141-1BF30-0XB0?
Quattuor connexiones M12 quinque-polares servient octo input digitalia.
Potestne 6ES7141-1BF30-0XB0 accipere sensorem bi-filarem qui perdit 2 mA cum est ex?
Maxima permittenda currentis quiescentis pro sensore bi-filari est 1.5 mA.
Quae est minima altitudinis input level in 6ES7141-1BF30-0XB0?
Input altitudinis debet esse inter +13 V et +30 V.