Siemens 6ES7136-6RA00-0BF0 SIMATIC ET 200SP F-RQ Relay Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select the type F0 BaseUnit and an appropriate fail-safe controlling output.
- Design and validate the complete safety circuit for the required performance level.
- Apply contact-load, temperature derating and external protection requirements together.
- Keep the control cable within ten metres and observe the separate load-contact cable limits.
6ES7136-6RA00-0BF0 SIMATIC ET 200SP F-RQ Relay Output Module
F-RQ module with one relay output containing two normally open contacts, a 24 V DC coil and a temperature-dependent five-ampere load rating.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7136-6RA00-0BF0 |
| Product Type | Safety relay output module |
| Core Function | Relay contact expansion for fail-safe output control |
| Application | ET 200SP safety circuits with suitable F-DQ control |
Fail-safe controlled relay stage
Suitable F-DQ control allows the module to serve safety-related relay switching applications.
Two normally open contacts
One relay output provides two normally open contacts for the connected circuit arrangement.
Diagnostic integration
A status byte and local DIAG and channel indicators support station diagnostics.
Product Overview
6ES7136-6RA00-0BF0 provides a relay-output stage for ET 200SP safety circuits controlled by an appropriate fail-safe digital output.
The module has two normally open contacts in one relay output, uses a type F0 BaseUnit and requires load-current derating, external contact protection and the specified control-cable limit.
Key Functions
Fail-safe controlled relay stage
Suitable F-DQ control allows the module to serve safety-related relay switching applications.
Two normally open contacts
One relay output provides two normally open contacts for the connected circuit arrangement.
Diagnostic integration
A status byte and local DIAG and channel indicators support station diagnostics.
Official Specifications
| BaseUnit and color code | BU type F0; CC42 |
|---|---|
| Relay output arrangement | 1 output with 2 normally open contacts |
| Coil supply | 24 V DC rated; 20.4–28.8 V DC permitted |
| Maximum relay coil current | 70 mA |
| Typical power loss | 1 W |
| Backplane power consumption | 100 mW |
| Input address space | 1 byte |
| Rated contact switching voltage | 24 V DC / 230 V AC |
| Maximum thermal continuous current | 5 A |
| Horizontal total-current limits | 5 A at up to 40°C; 4 A at up to 50°C; 3 A at up to 60°C |
| Vertical total-current limit | 3 A at up to 50°C |
| Minimum contact current | 1 mA; 10 mA after previously exceeding 300 mA |
| Maximum lamp load | 25 W |
| External contact protection | Required; 6 A |
| Switching-frequency limits | 2 Hz resistive; 0.1 Hz DC13 inductive; 2 Hz AC15 inductive |
| Cable-length limits | Load contacts: 500 m shielded or 300 m unshielded; control input: 10 m |
| Achievable safety classification | Up to PL e / Category 4 / SIL 3 with suitable F-DQ control and the required safety application |
| Operating ambient | 0 to +60°C horizontal; 0 to +50°C vertical |
| Diagnostic indication | Green/red DIAG LED and green channel-status LED |
| Dimensions and approximate weight | 20 × 73 × 58 mm (W × H × D); 56 g |
Frequently Asked Questions
Does 6ES7136-6RA00-0BF0 contain two independently controlled relay outputs?
The module provides one relay output with two normally open contacts.
Can I claim SIL 3 from 6ES7136-6RA00-0BF0 without a suitable fail-safe controlling output?
The stated achievable safety class requires control by an appropriate F-DQ within the safety application.
Which BaseUnit must I use with 6ES7136-6RA00-0BF0?
Use a type F0 BaseUnit with the CC42 module identification.
Can 6ES7136-6RA00-0BF0 carry five amperes at a horizontal ambient temperature of sixty degrees Celsius?
The horizontal total-current limit at sixty degrees Celsius is three amperes.
What external protection is specified for the contacts of 6ES7136-6RA00-0BF0?
External relay-output protection of six amperes is required.
How long may the control-input cable to 6ES7136-6RA00-0BF0 be?
The maximum control-input cable length is ten metres.
Can a previously heavily loaded contact of 6ES7136-6RA00-0BF0 later switch a one-milliampere signal?
After a contact has exceeded three hundred milliamperes, its stated minimum switching current becomes ten milliamperes.