Siemens SIMATIC S5 6ES5460-4UA13 460 Analog Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
Siemens · SIMATIC S5-135U/155U
6ES5460-4UA13 460 Floating Eight-Channel Analog Input Module
Siemens 6ES5460-4UA13 is a SIMATIC S5-135U/155U floating eight-channel analog input module that uses plug-in measuring-range submodules for voltage, current and resistance-sensor applications.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES5460-4UA13 |
| Product Type | Floating eight-channel analog input module |
| Core Function | Acquires analog process signals through selectable measuring-range submodules |
| Application or Compatible Series | SIMATIC S5-135U and S5-155U systems |
Range Submodules
Identify every installed measuring-range submodule and reproduce its channel position.
Acquisition Settings
Record line-frequency selection, scan mode, gain, compensation and wire-break settings.
Migration Planning
Compare signal type and wiring with the approved Siemens adapter or replacement module before conversion.
Product Overview
Siemens 6ES5460-4UA13 is a SIMATIC S5-135U/155U floating eight-channel analog input module that uses plug-in measuring-range submodules for voltage, current and resistance-sensor applications.
Plug-in range submodules adapt the inputs for voltage, current, two-wire or four-wire transmitters and resistance sensors. The analog input design supports isolated process-signal acquisition in S5-135U and S5-155U racks. Line-frequency integration, single or cyclic scanning, gain and wire-break monitoring can be set for the application.
Key Functions
Selectable Measurement Types
Plug-in range submodules adapt the inputs for voltage, current, two-wire or four-wire transmitters and resistance sensors.
Floating Channel Design
The analog input design supports isolated process-signal acquisition in S5-135U and S5-155U racks.
Configurable Conversion
Line-frequency integration, single or cyclic scanning, gain and wire-break monitoring can be set for the application.
Official Specifications
| Scanning Hardware | Relay multiplexer |
|---|---|
| Cycle Time for Eight Inputs at 50 Hz | 0.48 s |
| Integration Time at 50 Hz | 20 ms |
| Integration Time at 60 Hz | 16.67 ms |
| Maximum Shielded Cable Length | Less than 200 m |
| Rack Space Requirement | 1 slot |
| Maximum Input Voltage | 18 V |
| Selectable Scan Modes | Single or cyclic scanning |
| Selectable Line-Frequency Rejection | 50 Hz or 60 Hz |
| Selectable Gain Modes | Normal x1 or special x4 |
| Data Representation | Two’s complement |
| Wire-Break Monitoring | Configurable for channel groups 0 to 3 and 4 to 7 |
| Current Measuring Range | 0 to 20 mA or 4 to 20 mA with the applicable range submodule |
| Current Overload Range | 0 to 40 mA or 4 to 40 mA |
| Current-Range Scaling | 0 mA = 0 units; 4 mA = 512 units; 20 mA = 2,048 units |
| S7-1500 Voltage/Resistance Adapter | 6EZ2041-8UG11-0AE0 |
| S7-1500 Two-Wire Current Adapter | 6EZ2041-8UG11-2AE0 |
| S7-1500 Four-Wire Current Adapter | 6EZ2041-8UG11-3AE0 |
Frequently Asked Questions
Which measuring ranges can I use with 6ES5460-4UA13?
The available voltage, current and resistance ranges depend on the plug-in measuring-range submodule fitted to each channel.
What should I record before replacing 6ES5460-4UA13?
Record every range submodule, channel wire, polarity, shield, gain, scan and monitoring setting.
Can 6ES5460-4UA13 scan all eight inputs cyclically?
Yes, the module can be set for cyclic scanning and completes an eight-input cycle in 0.48 seconds at 50 hertz.
How should I set line-frequency rejection on 6ES5460-4UA13?
Select 50 or 60 hertz to match the local mains frequency and required integration time.
What should I check if 6ES5460-4UA13 reports a broken wire?
Inspect the affected channel group, field cable, transmitter supply, terminals and the configured monitoring switch.
Can 6ES5460-4UA13 be migrated to newer Siemens I/O?
Yes, Siemens lists signal-specific adapters and S7-1500 or ET 200SP modules, but the exact range submodule and wiring must be matched.
Which data format should my program expect from 6ES5460-4UA13?
Interpret converted values in the configured two’s-complement representation and apply the selected range scaling.
Compatibility & Ordering Notes
Compatibility Checklist
- Inventory the fitted measuring-range submodule in each channel position before ordering a replacement.
- Preserve the S5 rack slot, shield routing, transmitter supplies and acquisition switch settings.
- For migration, select the Siemens adapter and successor I/O according to the actual voltage, current or resistance signal type.