Overview
- Use a feeder protective device appropriate to the selected mains connection.
- Account for the output-power limit when raising the output voltage above 24 V.
- Keep 50 mm clear above and below the DIN-rail-mounted enclosure.
- Include ambient-temperature and low-input-voltage derating in the load calculation.
6EP3334-8SB00-0AY0 SITOP PSU8200 24 V 10 A Power Supply
A compact single-phase supply with automatic input-range selection, adjustable DC output and selectable overload behavior.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP3334-8SB00-0AY0 |
| Product Type | Stabilized power supply |
| Core Function | Isolated DC power conversion |
| Application | Industrial automation cabinets |
Automatic mains-range selection
The input selects between the 120 V and 230 V ranges automatically.
Short-duration load reserve
The supply delivers 150% of rated output current for up to five seconds per minute.
Local and remote status
A green output-OK indicator and a normally open relay provide operating status.
Product Overview
6EP3334-8SB00-0AY0 converts single-phase mains power into a regulated DC supply for automation loads.
Its front potentiometer, selectable protection characteristic and status relay support commissioning and monitoring, while the narrow enclosure mounts on a standard DIN rail.
Key Functions
Automatic mains-range selection
The input selects between the 120 V and 230 V ranges automatically.
Short-duration load reserve
The supply delivers 150% of rated output current for up to five seconds per minute.
Local and remote status
A green output-OK indicator and a normally open relay provide operating status.
Official Specifications
| AC input ranges | 85–132 V or 170–264 V; single phase |
|---|---|
| Input frequency | 47–63 Hz |
| Rated DC output | 24 V, 10 A, 240 W |
| Output adjustment | 24–28.8 V; maximum 240 W |
| Mains buffering | At least 35 ms at rated current and 120/230 V input |
| Rated input current | 4 A at 120 V; 1.9 A at 230 V |
| Maximum inrush current | 10 A at 25 °C |
| Output ripple and peaks | Maximum 50 mV ripple and 200 mV peaks |
| Typical efficiency | 94% |
| Typical rated-load dissipation | 18 W |
| Overload reserve | 150% of rated current for up to 5 s per minute |
| Short-circuit characteristic | Approximately 12 A constant current or selectable latching shutdown |
| Output-OK relay | Normally open contact rated 60 V DC, 0.3 A |
| Protection | IP20; Class I |
| Operating temperature | −25 to +70 °C; 2%/K current derating above +60 °C |
| Power terminals | Screw terminals for 0.2–2.5 mm² conductors |
| Dimensions | 55 × 125 × 125 mm (W × H × D) |
| Net weight | 1 kg |
Frequently Asked Questions
Can 6EP3334-8SB00-0AY0 handle both 120 V and 230 V mains without a manual selector?
The input changes between its two mains ranges automatically.
How far can I raise the output of 6EP3334-8SB00-0AY0?
The potentiometer adjusts the output from 24 V to 28.8 V while the maximum output power remains 240 W.
Can 6EP3334-8SB00-0AY0 support a brief current surge when a load starts?
The supply provides 150% of its rated output current for up to five seconds per minute.
Which trip behavior can I select on 6EP3334-8SB00-0AY0 for a shorted branch?
The available characteristics are approximately 12 A constant current or latching shutdown.
How can a controller monitor the output of 6EP3334-8SB00-0AY0?
A normally open output-OK relay provides a signaling contact rated for 60 V DC and 0.3 A.
What free space should I leave above and below 6EP3334-8SB00-0AY0?
Allow 50 mm above and 50 mm below the enclosure for convection cooling.
Must I reduce the load on 6EP3334-8SB00-0AY0 in a cabinet hotter than 60 °C?
Reduce the rated output current by 2% per kelvin between 60 °C and 70 °C.