- Keep the -2 single-port version distinct from the -1 two-port version and the -0 High Performance unit.
- Plan the network without relying on MRP or an integrated second Ethernet port.
- Select only one supported GP expansion module for the required additional function.
- Match the current-measuring range and SIMOCODE ES parameter set to the motor and feeder.
SIEMENS SIMOCODE pro 3UF7
3UF7011-1AU00-2 SIMOCODE pro V PN GP Motor Management Basic Unit
110–240 V AC/DC General Performance basic unit with one RJ45 PROFINET connection, four binary inputs, three relay outputs and a thermistor input.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3UF7011-1AU00-2 |
| Product Type | SIMOCODE pro V PN GP basic unit |
| Core Function | Motor protection and starter control |
| Application | PROFINET motor-feeder control systems |
Single network port
One Ethernet port distinguishes the -2 version from the two-port GP version.
Motor feeder control
Configure direct-on-line, reversing or star-delta starter functions.
Modular system
Combine the basic unit with current measurement and one optional expansion module.
Product Overview
3UF7011-1AU00-2 provides SIMOCODE pro V PN GP motor management over PROFINET in the 110–240 V AC/DC supply version, with one Ethernet connection.
The basic unit combines freely assignable binary inputs and monostable relay outputs with a thermistor connection, and works with a current-measuring module for motor-feeder protection and control.
Key Functions
Starter control
Supported control functions include direct-on-line, reversing and star-delta starters, as well as circuit-breaker and soft-starter control.
Networked motor management
The PROFINET interface exchanges motor-feeder information with the control system, with OPC UA server and web-server functions available.
Motor temperature and local signals
A binary PTC thermistor input and four 24 V binary inputs complement three freely assignable monostable relay outputs.
Official Specifications
| Rated control supply | 110–240 V AC/DC; 50/60 Hz for AC |
|---|---|
| Supply operating range | 0.85–1.1 × Us for startup and operation |
| Ethernet connection | 1 RJ45 port; 100 Mbit/s |
| Binary process inputs | 4; common reference potential; 24 V DC |
| Relay outputs | 3 monostable normally open outputs |
| Relay contact grouping | 2 outputs share a common potential; 1 separate output |
| Maximum binary-input cable length | 300 m single length |
| Thermistor sensor type | Binary PTC |
| Maximum thermistor cold resistance | 1.5 kΩ total |
| Thermistor trip resistance | 3.4–3.8 kΩ |
| Thermistor reset resistance | 1.5–1.65 kΩ |
| Sensor short-circuit threshold | Below 9 Ω |
| Thermistor cable limits | 250 m at 2.5 mm²; 150 m at 1.5 mm²; 50 m at 0.5 mm² |
| Relay switching capacity | AC-15: 3 A at 230 V AC; DC-13: 2 A at 24 V DC |
| Rated uninterrupted relay current | 5 A; 6 A at maximum +50 °C |
| Rated insulation voltage | 300 V at pollution degree 3 |
| Rated impulse withstand voltage | 4 kV |
| Typical power-failure backup | 20 ms |
Frequently Asked Questions
Can I continue a PROFINET line through 3UF7011-1AU00-2?
The single-port version has only one RJ45 connection, so line continuation requires suitable external network equipment.
Does 3UF7011-1AU00-2 support Motor feeder control for mobile equipment?
MRP is not supported by the single-port PN GP version.
Which starter functions can I configure with 3UF7011-1AU00-2?
The GP basic unit supports direct-on-line, reversing and star-delta starters plus circuit-breaker and soft-starter control.
Do I need a current-measuring module with 3UF7011-1AU00-2?
The GP basic unit is used in combination with a current-measuring module and an optional operator panel.
How many expansion modules can I add to 3UF7011-1AU00-2?
One expansion module can add digital signals, temperature sensing or residual-current detection.
Can I connect a PTC motor sensor to 3UF7011-1AU00-2?
A binary PTC thermistor input is provided for motor-temperature protection.
Which software can I use to parameterize 3UF7011-1AU00-2?
SIMOCODE ES in the TIA Portal supports parameterization through the system interface using a suitable PC cable.