- Overview
- Hot Selling Models
- Recommended Products
Overview
- Set the input range selector before applying the AC supply.
- Provide feeder protection appropriate to the single- or two-phase arrangement and startup current.
- Keep 50 mm clear above and below the housing and apply the required high-temperature derating.
- Select the overload characteristic and check load startup current before commissioning the DC distribution.
6EP1334-3BA00 SITOP PSU200M 24 V 10 A Power Supply
SITOP modular supply delivering 24 V DC at 10 A, with selectable wide-range AC input and configurable overload behavior.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1334-3BA00 |
| Product Type | Stabilized DIN-rail power supply |
| Core Function | Regulated 24 V DC supply for industrial control loads |
| Application | Control cabinets with single- or two-phase AC supply |
Wide AC input selection
The input selector supports 120–230 V and 230–500 V nominal supply ranges with corresponding wide operating ranges.
Adjustable DC output
The 24 V output can be adjusted to 28.8 V using the potentiometer for the planned DC distribution arrangement.
Selectable overload response
The supply offers constant-current behavior or latching shutdown, with separate output, overload and shutdown LEDs.
Product Overview
6EP1334-3BA00 provides a stabilized, isolated 24 V DC output rated at 10 A for industrial cabinet loads.
Selectable AC input ranges cover single- and two-phase supply arrangements, while output adjustment and switchable overload behavior support integration into the control power distribution.
Key Functions
Wide AC input selection
The input selector supports 120–230 V and 230–500 V nominal supply ranges with corresponding wide operating ranges.
Adjustable DC output
The 24 V output can be adjusted to 28.8 V using the potentiometer for the planned DC distribution arrangement.
Selectable overload response
The supply offers constant-current behavior or latching shutdown, with separate output, overload and shutdown LEDs.
Official Specifications
| Nominal AC input ranges | 120–230 V or 230–500 V; selector switch |
|---|---|
| Permissible AC input ranges | 85–264 V or 176–550 V |
| Input frequency | 47–63 Hz |
| Rated DC output | 24 V, 10 A, 240 W |
| Adjustable output voltage | 24–28.8 V |
| Maximum residual ripple | 50 mV |
| Maximum output voltage peak | 200 mV |
| Minimum mains bridging | 25 ms at 120/230 V and rated output current |
| Typical efficiency | 87% |
| Typical power loss at rated load | 36 W |
| Maximum inrush current | 35 A at 25 °C |
| Overload behavior | Approximately 12 A constant current or latching shutdown |
| Short-circuit current boost | Typically 30 A for 25 ms during operation |
| Parallel operation | Up to 2 units for increased output power |
| Degree of protection | IP20; protection class I |
| Electrical connections | Screw terminals, 0.2–2.5 mm² |
| Required ventilation clearance | 50 mm above and below |
| Mounting | 35 mm DIN rail to EN 60715 |
| Dimensions (W × H × D) | 90 × 125 × 125 mm |
| Net weight | 1.4 kg |
Frequently Asked Questions
Can 6EP1334-3BA00 run from a 400 V two-phase supply?
The upper input range supports 230 to 500 V nominal AC, provided the selector and two-pole feeder protection are arranged correctly.
Can the output of 6EP1334-3BA00 be raised above 24 V?
The output voltage can be adjusted from 24 to 28.8 V with the potentiometer.
What clearance is required around 6EP1334-3BA00?
Reserve at least 50 mm above and below the housing for ventilation.
Can two units of 6EP1334-3BA00 be paralleled for more current?
Up to two units can be connected in parallel for increased output power using the appropriate operating arrangement.
Why does 6EP1334-3BA00 remain shut down after an overload?
The selected overload characteristic can latch the output off instead of maintaining constant-current operation.
Which indicator on 6EP1334-3BA00 shows normal DC output?
The green 24 V OK LED indicates normal output operation.
What conductor size can be connected to 6EP1334-3BA00?
The input and output screw terminals accept conductors from 0.2 to 2.5 mm².