Siemens 6ES7134-6HD01-0BA1 SIMATIC ET 200SP AI 4xU/I 2-wire ST Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select the correct voltage or current range and wire the compatible A0/A1 BaseUnit accordingly.
- Use the CC03 identification and account for the additional quality-information byte in the controller project.
- For the FS22/V3.0.0 data-sheet configuration, engineering support starts with TIA Portal V21.1 or the listed STEP 7 V5.7 updates and HSP0348 V3.0.
- Enable wire-break diagnosis for 4–20 mA loops and select suppression and smoothing to suit the process response time.
6ES7134-6HD01-0BA1 SIMATIC ET 200SP AI 4xU/I 2-wire ST Module
Four differential voltage/current inputs with up to 16-bit conversion, configurable smoothing and module diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-6HD01-0BA1 |
| Product Type | Analog input module |
| Core Function | Acquisition of voltage and two-wire current transmitter signals |
| Application | Distributed process value acquisition in ET 200SP stations |
Voltage and current channels
Four differential channels accept 0–10 V, 1–5 V, ±10 V, ±5 V, 0–20 mA or 4–20 mA according to parameterization.
Configurable measurement filtering
Selectable 16.6, 50 or 60 Hz suppression and four smoothing levels balance interference rejection and response time.
Module-level diagnostics
Supply monitoring, 4–20 mA wire-break detection and range diagnostics support commissioning and maintenance of analog loops.
Product Overview
6ES7134-6HD01-0BA1 acquires four differential analog signals in an ET 200SP station using Sigma-Delta conversion.
Voltage ranges include bipolar and unipolar signals, while two-wire current transmitter operation supports loop measurements with a short-circuit-protected transmitter supply.
Key Functions
Voltage and current channels
Four differential channels accept 0–10 V, 1–5 V, ±10 V, ±5 V, 0–20 mA or 4–20 mA according to parameterization.
Configurable measurement filtering
Selectable 16.6, 50 or 60 Hz suppression and four smoothing levels balance interference rejection and response time.
Module-level diagnostics
Supply monitoring, 4–20 mA wire-break detection and range diagnostics support commissioning and maintenance of analog loops.
Official Specifications
| Analog input channels | 4 differential inputs |
|---|---|
| Voltage ranges | 0–10 V, 1–5 V, -10 to +10 V and -5 to +5 V |
| Current ranges | 0–20 mA and 4–20 mA |
| Resolution | 15 bits for unipolar ranges; 16 bits including sign for bipolar ranges |
| Voltage input resistance | 120 kΩ |
| Current input resistance | 100 Ω plus approximately 0.7 V diode forward voltage |
| Measurement method | Sigma-Delta |
| Conversion time per channel | 180, 60 or 50 ms |
| Interference suppression | 16.6, 50 or 60 Hz |
| Smoothing factors | 1, 4, 8 or 16 times conversion time |
| Rated supply and range | 24 V DC; 19.2–28.8 V DC |
| Current consumption | Rated 30 mA; maximum 117 mA |
| Typical power loss | 0.85 W |
| Transmitter supply capacity | 20 mA per channel; up to 50 mA for less than 10 s |
| Process data | 8 bytes plus 1 byte of quality information |
| Basic error at 25 °C | ±0.3% for voltage and current |
| Operating error over temperature | ±0.5% for voltage and current |
| Maximum shielded cable length | 1,000 m for current; 200 m for voltage |
| Dimensions (W × H × D) | 15 × 73 × 58 mm |
| Weight | Approximately 31 g |
Frequently Asked Questions
Can 6ES7134-6HD01-0BA1 read a bipolar ±10 V signal?
The -10 to +10 V range is supported with 16-bit resolution including the sign.
Will 6ES7134-6HD01-0BA1 detect a broken 0–20 mA loop?
Wire-break diagnostics apply to the 4–20 mA range rather than the 0–20 mA range.
Which BaseUnit should I pair with 6ES7134-6HD01-0BA1?
Use a compatible type A0 or A1 BaseUnit and the CC03 terminal identification for the selected two-wire connection.
Why does stronger smoothing slow the response of 6ES7134-6HD01-0BA1?
The highest smoothing setting uses sixteen times the conversion time, increasing the settling time of a changed input value.
How much address space is required by 6ES7134-6HD01-0BA1?
Reserve eight bytes for analog values and one additional byte when quality information is used.
Can 6ES7134-6HD01-0BA1 generate a process limit-value alarm?
The module provides diagnostic alarms but does not provide a limit-value alarm function.
Can voltage and current channels on 6ES7134-6HD01-0BA1 use equally long field cables?
Shielded current loops may reach 1,000 m while shielded voltage measurement cables are limited to 200 m.