Siemens 6ES7232-0HB22-0XA8 SIMATIC S7-200 CN EM 232 Analog Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the module only with a supported S7-22X CPU.
- Keep the CN article suffix XA8 when maintaining the specified equipment.
- Wire the voltage or current terminal for the intended signal on each channel.
- Use the signed voltage scale or nonnegative current scale as appropriate.
- Provide 24 V DC within the 20.4–28.8 V range.
- Apply the separate voltage-load and current-loop impedance limits.
6ES7232-0HB22-0XA8 SIMATIC S7-200 CN EM 232 Analog Output Module
A two-channel S7-200 CN analog output module for bipolar voltage or current commands, using the EM 232 output format and a compact 46 mm housing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7232-0HB22-0XA8 |
| Product Type | EM 232 analog output module |
| Core Function | Converts PLC values to field analog signals |
| Application | SIMATIC S7-22X CPUs |
Two analog channels
Separate channel terminals provide voltage or current output wiring.
Scaled process values
Voltage and current commands use different numerical ranges.
S7-22X expansion
The CN module is specified for the S7-22X CPU family.
Product Overview
6ES7232-0HB22-0XA8 adds two analog output channels to a compatible S7-22X installation.
The EM 232 output arrangement supports bipolar voltage commands and unipolar current commands, with separate load limits and settling times for the two signal types.
Key Functions
Generate bipolar voltage commands
The voltage output covers −10 to +10 V and uses a signed process-word range.
Drive current-command circuits
The current output covers 0–20 mA and uses a nonnegative process-word range with a separate loop-resistance limit.
Match the analog load dynamics
The settling time is 100 µs for voltage output and 2 ms for current output.
Official Specifications
| Analog Output Channels | 2 |
|---|---|
| Voltage Output Range | −10 to +10 V DC |
| Current Output Range | 0–20 mA |
| Output Resolution | Voltage: 12 bits including sign; current: 11 bits |
| Process-Word Scaling | Voltage: −32000 to +32000; current: 0 to +32000 |
| Voltage-Output Settling Time | 100 µs |
| Current-Output Settling Time | 2 ms |
| Voltage-Output Load Resistance | 5 kΩ minimum |
| Current-Output Load Resistance | 500 Ω maximum |
| External Supply Voltage | 24 V DC nominal; 20.4–28.8 V DC |
| Output Accuracy | Typical ±0.5% of full scale at 25 °C; worst case ±2% over 0–55 °C |
| Field-to-Logic Isolation | None |
| Typical Power Loss | 2 W |
| Overall Dimensions | 46 × 80 × 62 mm (W × H × D) |
Frequently Asked Questions
Can I connect 6ES7232-0HB22-0XA8 to an S7-21X CPU?
The module is specified only for S7-22X CPUs.
Which process-word range should I write for a voltage command on 6ES7232-0HB22-0XA8?
Use a signed value from −32000 to +32000 for the bipolar voltage range.
Which process-word range should I use for current output on 6ES7232-0HB22-0XA8?
Use values from 0 to +32000 for the 0–20 mA output range.
How much loop resistance can the current output of 6ES7232-0HB22-0XA8 drive?
The permitted current-output load resistance is 500 Ω maximum.
How low can the voltage-output load resistance be on 6ES7232-0HB22-0XA8?
The voltage output requires a load resistance of at least 5 kΩ.
Does 6ES7232-0HB22-0XA8 settle equally fast in voltage and current operation?
The voltage output settles in 100 µs, while the current output settles in 2 ms.
Which channel terminals should I distinguish when wiring 6ES7232-0HB22-0XA8?
Each channel provides its M common, V voltage-output terminal and I current-output terminal.