- Overview
- Specifications
- Description
- Applications
- Notable Features
- FAQ
- Recommended Products
Overview
Place of Origin: |
USA |
Brand Name: |
HONEYWELL |
Model Number: |
8C-TAIMA1 51307171-175 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Part Number |
8C-TAIMA1 51307171-175 |
|
Part Type |
Analog Input Module |
|
Dimensions |
12x6.2x22.2cm |
|
Weight |
0.34kg |
|
Redundancy |
Non-redundant |
|
Coating |
Yes |
|
Input Type |
Thermocouple (TC) and / or RTD |
|
Voltage Rating |
24 V DC |
|
Module Current Rating |
120 mA |
|
Input Channels |
16 fully isolated (channel-to-channel, channel-to-IOL, channel-to-power supply common) |
|
Input Scan Rate |
1 second fixed (up to 16 channels/sec max) |
|
Channel Bandwidth |
0 to 4.7 Hz (-3 dB) |
|
Nominal Input Range (TC only) |
-20 to +100 mV |
|
Max Normal Mode Input (TC) |
-10 to +10 V |
|
Max Normal Mode Input (RTD) |
-1 to +2 V @ 100 mA |
|
Gain Error (TC millivolt range) |
0.050% full scale max |
|
Temperature Stability (TC/mV) |
±20 ppm/°C max |
|
Temperature Stability (RTD) |
±20 ppm/°C max |
|
Long Term Drift |
500 ppm |
|
Input Impedance (TC only) |
1 MΩ at DC |
|
CMV (Channel to Shield) |
±250 VDC or VAC RMS |
|
CMV (Channel to Channel) |
±33 VDC or VAC RMS |
|
CMRR (50/60 Hz, 1000 Ω source max) |
120 dB min |
|
NMRR at 50/60 Hz |
60 dB min |
|
Crosstalk (DC to 60 Hz) |
80 dB (120 dB at 50/60 Hz) |
|
Line Frequency Integration |
Selectable 50 Hz or 60 Hz |
|
RTD Sensor Excitation Current |
1 mA |
|
Cold Junction Compensation Range |
-20°C to +60°C (±0.5°C typical) |
|
TC Linearization Accuracy |
±0.05 Ω/°C |
|
Open Thermocouple Detection |
≤1000 Ω no-trip; ≥1500 Ω trip |
|
RTD Max Lead Resistance |
15 Ω |
|
Surge Protection (Sensor Terminals) |
EN 61000-4-5 (1 kV line-line, 2 kV line-ground) |
|
Surge Protection (Power/Serial) |
EN 61000-4-5 (1 kV line-line, 2 kV line-ground) |
|
Supported Millivolt Types |
-20 to +100 mV |
Description
Honeywell 8C-TAIMA1 51307171-175 is an analog input module within the Experion PKS Series 8 I/O family. The module provides multiple fully isolated input channels capable of directly interfacing with both thermocouple and resistance temperature detector sensors.
Applications
Power plant: Boiler tube temperature, turbine bearing temperature, fermentation unit temperature.
Chemical plant: Hydrogenation reactor temperature, heat exchanger tube temperature, distillation tray temperature.
Refinery: Furnace temperature, catalytic cracking line temperature, oil tank temperature.
Metallurgy plant: Blast furnace body temperature, converter flue gas temperature, furnace lining, molten steel temperature.
Notable Features
TC and RTD operation
Remote Cold Junction compensation capability
1 Second PV scanning with OTD protection
Configurable OTD protection (See below)
Temperature points can be added in 16 point increments
FAQ
Q: What channels does 8C-TAIMA1 51307171-175 module have and does it support redundancy?
A: 16 fully isolated channels, non-redundant, coated.
Q: What signal inputs and scan rate does 8C-TAIMA1 51307171-175 support?
A: Supports thermocouple (TC) and resistance temperature detector (RTD), fixed scan rate 1 second.
Q: What is the channel-to-channel isolation withstand voltage and crosstalk of 8C-TAIMA1 51307171-175?
A: Channel isolation ±33 VDC/VAC RMS, crosstalk 80 dB.
Q: What are the operating voltage and module current of 8C-TAIMA1 51307171-175?
A: Operating voltage 24 V DC, rated current 120 mA.
Q: What is the cold junction compensation range and maximum gain error of 8C-TAIMA1 51307171-175?
A: Cold junction compensation -20°C to +60°C, maximum gain error 0.050% F.S.