Specifications
|
Parameter |
Value |
|
Model |
PM856AK01 3BSE066490R1 |
|
Type |
Processor Unit |
|
Dimensions (L x W x H) |
155 x 130 x 200 mm |
|
Weight |
1.1 kg |
|
Processor Type |
MPC860 |
|
Clock Frequency |
24 MHz |
|
Redundancy |
No |
|
High Integrity |
No |
|
Memory |
16 MB (from 800xA 5.1 FP4) |
|
RAM Available for Application |
10.337 MB (from 800xA 5.1 FP4) |
|
Flash Memory |
Yes |
|
Flash PROM for Firmware |
2 MB |
|
Power Supply |
24 V DC (19.2–30 V DC) |
|
Power Consumption |
180 mA typical / 300 mA max |
|
Power Dissipation |
4.32 W (7.2 W max) |
|
Backup Battery |
Lithium 3.6 V (memory backup included) |
|
Applications per Controller |
32 |
|
Programs per Application |
64 |
|
Diagrams per Application |
128 |
|
Tasks per Controller |
32 |
|
Cycle Time |
Down to 1 ms |
|
Number of Cycle Times |
32 |
|
Communication Interfaces |
Ethernet (IEEE 802.3, 10 Mbit/s), 2 × RS-232C |
|
Protocols |
MMS, IAC |
|
CEX Bus Modules |
Up to 12 modules |
|
ModuleBus Capacity |
Max 96 I/O modules |
|
ModuleBus Scan Rate |
0–100 ms |
|
Electrical ModuleBus Supply |
24 V: max 1.0 A; 5 V: max 1.5 A |
|
Clock Synchronization |
1 ms between AC 800M controllers (CNCP protocol) |
|
Event Queue Capacity |
Up to 3000 events per OPC client |
|
OPC Transmission Rate |
36–86 events/sec; 113–143 data messages/sec |
|
Real-Time Clock Stability |
100 ppm (~1 hour/year) |
Description
The CPU board contains the microprocessor and RAM memory, a real-time clock, LED indicators, INIT push button, and a CompactFlash interface.
The base plate of the PM856AK01 3BSE066490R1 controller has two RJ45 Ethernet ports (CN1, CN2) for connection to the Control Network, and two RJ45 serial ports (COM3, COM4). One of the serial ports (COM3) is an RS-232C port with modem control signals, whereas the other port (COM4) is isolated and used for the connection of a configuration tool.
Simple DIN rail attachment / detachment procedures, using the unique slide & lock mechanism. All base plates are provided with a unique Ethernet address which provides every CPU with a hardware identity. The address can be found on the Ethernet address label attached to the TP830 base plate.
Environment and certification
|
Parameter |
Value |
|
Operating Temperature |
0°C to +55°C (+32°F to +131°F) |
|
Storage Temperature |
-40°C to +70°C (-40°F to +158°F) |
|
Temperature Change Rate |
3°C/min (IEC/EN 61131-2) |
|
Pollution Degree |
Degree 2 (IEC/EN 61131-2) |
|
Corrosion Protection |
G3 (ISA 71.04 compliant) |
|
Relative Humidity |
5–95% RH (non-condensing) |
|
Noise Emission |
< 55 dB(A) |
|
Vibration |
10–50 Hz: 0.0375 mm; 50–150 Hz: 0.5 g; 5–500 Hz: 0.2 g |
|
Rated Isolation Voltage |
500 V AC |
|
Dielectric Test Voltage |
50 V |
|
Protection Class |
IP20 (EN 60529, IEC 529) |
|
Altitude |
Up to 2000 m (IEC/EN 61131-2) |
|
Emission Standards |
EN 61000-6-4 |
|
Immunity Standards |
EN 61000-6-2 |
|
Environmental Category |
Industrial |
|
CE Mark |
Yes |
|
Electrical Safety Standards |
EN 50178, IEC 61131-2, UL 61010-1, UL 61010-2-201 |
|
Hazardous Location Approval |
cULus Class 1, Zone 2; AEx nA IIC T4; Ex nA IIC T4Gc X |
|
Marine Certifications |
ABS, BV, DNV-GL, LR |
|
TÜV Approval |
No |
|
RoHS Compliance |
EU RoHS, UAE RoHS, CN RoHS |
|
WEEE Compliance |
Directive 2012/19/EU |
Applications
Chemical plants: Complex sequential control of multi-unit reactors.
Pharmaceutical plants: Refined process control conforming to GAMP standards.
Food plants: Automated batching systems and large-scale filling line management.
Steel mills (metallurgical plants): Auxiliary production lines, cooling water systems, and energy monitoring.
Water treatment plants: Distributed PLC networking and centralized scheduling throughout the plant.
Features and benefits
Reliability and simple fault diagnosis procedures
Modularity, allowing for step-by-step expansion
IP20 Class protection without the requirement for enclosures
The controller can be configured with 800xA control builder
The controller has full EMC certification
Hardware based on standards for optimum communication connectivity (Ethernet, PROFIBUS DP, etc.)
FAQ
Q: What hardware does the PM856AK01 3BSE066490R1 include?
A: The PM856AK01 3BSE066490R1 includes a PM856A CPU module and a TP830 socket terminal unit.
Q: Is its part number PM856AK01 3BSE066490R1 unique?
A: Yes, the PM856AK01 3BSE066490R1 uses 3BSE066490R1 as a unique ABB order code to identify this specific kit.
Q: Does the PM856AK01 3BSE066490R1 support CPU redundancy?
A: No. The PM856AK01 3BSE066490R1 does not support CPU redundancy. For redundancy, PM861 or PM864 and later models are recommended.
Q: How much more memory does the PM856AK01 3BSE066490R1 have compared to PM851?
A: The PM856AK01 3BSE066490R1 has 16MB memory, which is twice the PM851’s 8MB capacity.
Q: Does the PM856AK01 3BSE066490R1 support hot-swapping?
A: The CPU of the PM856AK01 3BSE066490R1 can technically be removed from the socket while powered, but this is not recommended during production; the socket connection must remain secure.