Siemens SIMATIC ET 200SP HA 6DL1134-6UD00-0PK0 AI 4xI 2-/4-wire HART ISOL HA Analog Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Choose the matching K0 or L0 terminal block; use L0 for redundancy.
- Set each channel to the correct current range and HART operating mode.
- Check sensor supply current and temperature derating for the assembled station.
SIEMENS SIMATIC ET 200SP HA • ISOLATED HART ANALOG INPUT
6DL1134-6UD00-0PK0 AI 4xI 2-/4-wire HART ISOL HA Analog Input Module
A four-channel, channel-isolated current input module for ET 200SP HA stations with HART support and 2-wire or 4-wire transmitters.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DL1134-6UD00-0PK0 |
| Product Type | Analog input module |
| Core Function | Isolated current acquisition with HART |
| Compatible Series | SIMATIC ET 200SP HA |
Four Current Inputs
Connects up to four analog current signals from 2-wire or 4-wire transmitters.
Channel Isolation
The four inputs are electrically isolated from one another and from the backplane and supply.
HART Integration
Supports standard, HART and MultiHART input address formats for device data.
Product Overview
6DL1134-6UD00-0PK0 is the SIMATIC ET 200SP HA AI 4xI 2-/4-wire HART ISOL HA module. It reads four current signals, supports HART communication and provides isolated channels for process instrumentation.
The module supports 0–20 mA and 4–20 mA ranges and uses terminal blocks of type K0 or L0. Siemens specifies L0 for a redundant module arrangement; check the station design and terminal block before ordering.
Key Functions
Process Current Acquisition
Converts four 0–20 mA or 4–20 mA transmitter signals for the ET 200SP HA station.
Transmitter Supply
Provides four electronically protected 24 V sensor supply outputs for connected devices.
HART Data Access
Supports HART-capable engineering with standard, HART and MultiHART address-space options.
Official Specifications
| Analog Input Channels | 4 |
|---|---|
| Current Measuring Ranges | 0–20 mA; 4–20 mA |
| Resolution | 16 bit including sign |
| Input Resistance | 250 Ω |
| Input Current Destruction Limit | 24 mA |
| Rated Supply Voltage | 24 V DC |
| Permissible Supply Range | 19.2–28.8 V DC |
| Sensor Supply Outputs | 4, electronically short-circuit protected |
| Rated Sensor Supply Voltage | 24 V DC |
| Maximum Sensor Supply Current | 23.5 mA per channel; 88 mA per module |
| Input Address Space | 9 bytes standard; 29 bytes HART; 16 bytes MultiHART |
| Terminal Block Types | K0 or L0; L0 for redundancy |
| Maximum Shielded Cable Length | 800 m |
| Electrical Isolation | 125 V AC / 150 V DC between channels, backplane and supply |
| Basic Error Limit | ±0.1% |
| Operating Temperature | −40 to +70 °C, subject to derating |
| Dimensions (W × H × D) | 22.5 × 115 × 138 mm |
| Approximate Weight | 163 g |
Frequently Asked Questions
Can 6DL1134-6UD00-0PK0 connect both 2-wire and 4-wire transmitters?
Yes. The module is designated for 2-wire and 4-wire current transmitters; use the documented terminal assignments for the selected wiring.
Which current ranges are available on 6DL1134-6UD00-0PK0?
The channel measuring ranges include 0–20 mA and 4–20 mA.
Which terminal block should I specify for a redundant pair?
Siemens specifies terminal block type L0 for a redundant module arrangement; K0 is also listed for nonredundant use.
Does this module supply connected transmitters?
It provides four 24 V sensor supply outputs with electronic short-circuit protection. Check each channel and total module current limits.
How much input address space should I reserve for HART?
The manual lists 9 bytes for standard mode, 29 bytes for HART mode and 16 bytes for MultiHART mode.
Are the four measurement channels electrically isolated?
Yes. Siemens specifies isolation between channels and toward the backplane and supply.
Can I use this module in a −40 °C cabinet?
The specified operating range starts at −40 °C. Check the manual’s temperature-dependent derating and the complete station configuration.