Siemens SIMATIC ET 200SP HA 6DL1134-6UD00-0PK0 AI 4xI 2-/4-wire HART ISOL HA Analog Input Module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Choose the matching K0 or L0 terminal block; use L0 for redundancy.
- Set each channel to the correct current range and HART operating mode.
- Check sensor supply current and temperature derating for the assembled station.
SIEMENS SIMATIC ET 200SP HA • ISOLATED HART ANALOG INPUT
6DL1134-6UD00-0PK0 AI 4xI 2-/4-wire HART ISOL HA Analog Input Module
A four-channel, channel-isolated current input module for ET 200SP HA stations with HART support and 2-wire or 4-wire transmitters.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6DL1134-6UD00-0PK0 |
| Typus Producti | Modulus Ingressus Analogicus |
| Functio principalis | Isolated current acquisition with HART |
| Series Compatible | SIMATIC ET 200SP HA |
Four Current Inputs
Connects up to four analog current signals from 2-wire or 4-wire transmitters.
Isolatio Canalium
The four inputs are electrically isolated from one another and from the backplane and supply.
HART Integration
Supports standard, HART and MultiHART input address formats for device data.
Product Overview
6DL1134-6UD00-0PK0 est le module SIMATIC ET 200SP HA AI 4xI 2-/4-fil HART ISOL HA. Il lit quatre signaux de courant, prend en charge la communication HART et fournit des canaux isolés pour les instruments de processus.
Le module prend en charge les plages 0–20 mA et 4–20 mA et utilise des borniers de type K0 ou L0. Siemens spécifie L0 pour une disposition redondante de modules ; vérifiez la conception de la station et le type de bornier avant commande.
Key Functions
Acquisition de courant de processus
Convertit quatre signaux de transmetteur 0–20 mA ou 4–20 mA pour la station ET 200SP HA.
Alimentatio Transmitteris
Fournit quatre sorties électroniquement protégées de tension d’alimentation capteur 24 V pour les dispositifs connectés.
Accès aux données HART
Prend en charge l’ingénierie compatible HART avec les options standard, HART et MultiHART pour l’espace d’adresses.
Official Specifications
| Canali Analogici Input | 4 |
|---|---|
| Intervala Mensurae Currentis | 0–20 mA; 4–20 mA |
| Resolutio | 16 bit inclusu signo |
| Resistentia input | 250 Ω |
| Limite de destruction du courant d’entrée | 24 mA |
| Tensio nominalis supplicii | 24 V DC |
| AMPLITUDO ADMISSIBILIS FONDIS | 19,2–28,8 V CC |
| Exitus Alimentationis Sensorum | 4, protégé électroniquement contre les courts-circuits |
| Tension nominale d’alimentation capteur | 24 V DC |
| Maximum Sensor Supply Current | 23.5 mA per channel; 88 mA per module |
| Spatium Adressarum Input | 9 bytes standard; 29 bytes HART; 16 bytes MultiHART |
| Typus Blockus Terminalis | K0 or L0; L0 for redundancy |
| Maxima Longitudo Cavi Scutati | 800 m |
| Isolatio Electrica | 125 V AC / 150 V DC between channels, backplane and supply |
| Basic Error Limit | ±0.1% |
| Temperatura operativa | −40 to +70 °C, subject to derating |
| Dimensiones (L × H × D) | 22.5 × 115 × 138 mm |
| Pondus Approximatum | 163 g |
Quaestiones Frequenter Rogatae
Can 6DL1134-6UD00-0PK0 connect both 2-wire and 4-wire transmitters?
Yes. The module is designated for 2-wire and 4-wire current transmitters; use the documented terminal assignments for the selected wiring.
Which current ranges are available on 6DL1134-6UD00-0PK0?
The channel measuring ranges include 0–20 mA and 4–20 mA.
Which terminal block should I specify for a redundant pair?
Siemens specifies terminal block type L0 for a redundant module arrangement; K0 is also listed for nonredundant use.
Does this module supply connected transmitters?
It provides four 24 V sensor supply outputs with electronic short-circuit protection. Check each channel and total module current limits.
How much input address space should I reserve for HART?
The manual lists 9 bytes for standard mode, 29 bytes for HART mode and 16 bytes for MultiHART mode.
Are the four measurement channels electrically isolated?
Yes. Siemens specifies isolation between channels and toward the backplane and supply.
Can I use this module in a −40 °C cabinet?
The specified operating range starts at −40 °C. Check the manual’s temperature-dependent derating and the complete station configuration.