Overview
- Use the outdoor bus-module variant 6ES7195-7HD80-0XA0 for a redundant outdoor layout.
- Keep the station within the documented twelve-module capacity.
- Review link configuration before substituting a later BA70 interface.
SIEMENS SIMATIC ET 200M • IM 153-2 OUTDOOR
6ES7153-2BA82-0XB0 IM 153-2 Outdoor Interface Module
An outdoor IM 153-2 interface for PROFIBUS DP-connected ET 200M distributed I/O stations.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7153-2BA82-0XB0 |
| Product Type | IM 153-2 outdoor interface module |
| Core Function | PROFIBUS DP connection for distributed I/O |
| Compatible Series | SIMATIC ET 200M |
Outdoor Variant
The BA82 order number identifies the outdoor IM 153-2 version.
Expanded I/O Station
The BAx2 interface supports up to 12 ET 200M modules and 64-channel digital modules.
Redundant Layout
The outdoor station can use a paired IM 153-2 arrangement with the specified bus module.
Product Overview
6ES7153-2BA82-0XB0 is the outdoor IM 153-2 interface module for a SIMATIC ET 200M distributed I/O station on PROFIBUS DP. Siemens identifies this exact BA82 variant alongside the BA02 interface in its product information.
The BAx2 generation supports up to 12 I/O modules, 64-channel DI/DO modules and time stamping for up to 32 digital inputs per slot. Outdoor redundant station layouts use two IM 153-2 modules and the appropriate BM IM/IM bus module.
Key Functions
Distributed I/O Connection
Links an ET 200M station to a PROFIBUS DP master.
Expanded Module Capacity
Supports up to twelve I/O modules, including 64-channel digital modules.
Signal Time Stamping
Supports time stamps for up to 32 digital input signals per slot.
Official Specifications
| I/O Modules per Interface | Up to 12 |
|---|---|
| Digital Module Channel Capacity | 64-channel DI/DO modules supported |
| Timestamped Digital Inputs per Slot | Up to 32 |
| I/O Modules With Expanded Input Data | Supported |
| Slave-Initiated Frame Routing | Supported |
| Outdoor Operating Ambient Temperature | −25 to 60 °C |
Frequently Asked Questions
How many I/O modules can I connect behind 6ES7153-2BA82-0XB0?
The BAx2 interface generation supports up to twelve I/O modules in the ET 200M station.
Can 6ES7153-2BA82-0XB0 operate 64-channel digital modules?
The interface supports 64-channel digital input and output modules.
How many digital inputs can 6ES7153-2BA82-0XB0 time-stamp in one slot?
It supports time stamping of up to 32 digital input signals per slot.
Which bus module is used for an outdoor redundant station with 6ES7153-2BA82-0XB0?
The outdoor redundant layout uses BM IM/IM 6ES7195-7HD80-0XA0 with two interface modules.
Can I use 6ES7153-2BA82-0XB0 in a DP/PA Link?
The module is an IM 153-2 interface option for a DP/PA Link with the appropriate couplers.
What should I compare before replacing 6ES7153-2BA82-0XB0 with BA70?
The BA70 successor is documented as a spare-part replacement, but its application exceptions must be checked against the installed link.
Can I run 6ES7153-2BA82-0XB0 in a −25 °C installation?
The outdoor ET 200M configuration covers operation down to −25 °C.