Siemens 6SL3210-1KE14-3UB2 SINAMICS G120C Compact Inverter
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a controller or serial interface configured for the USS/MODBUS RTU drive version.
- Select the motor duty and current using the supply-voltage-dependent rating.
- Keep motor cables within 150 m and braking-resistor wiring within 15 m.
- Wire motor-temperature sensing and the required machine control inputs before configuring the drive control mode.
6SL3210-1KE14-3UB2 SINAMICS G120C Compact Inverter
USS/MODBUS RTU compact drive for 380–480 V supplies, rated 1.5 kW at low overload or 1.1 kW at high overload.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6SL3210-1KE14-3UB2 |
| Product Type | Compact frequency inverter |
| Core Function | Adjustable-speed motor control |
| Application | Three-phase industrial drive applications |
Serial drive networking
USS/MODBUS RTU communication connects the compact inverter to a compatible control system.
Integrated control terminals
Six standard digital inputs, a fail-safe digital input, analog input/output and relay plus transistor outputs support local machine wiring.
Sensorless motor regulation
V/f, FCC, ECO and sensorless vector modes provide control options for the selected motor and load profile.
Product Overview
6SL3210-1KE14-3UB2 combines the drive control and power stage in a compact SINAMICS G120C inverter with USS/MODBUS RTU communication.
The frame AA drive provides digital and analog control connections, a fail-safe digital input and motor-temperature sensing, with a choice of low-overload or high-overload motor sizing.
Key Functions
Serial drive networking
USS/MODBUS RTU communication connects the compact inverter to a compatible control system.
Integrated control terminals
Six standard digital inputs, a fail-safe digital input, analog input/output and relay plus transistor outputs support local machine wiring.
Sensorless motor regulation
V/f, FCC, ECO and sensorless vector modes provide control options for the selected motor and load profile.
Official Specifications
| Supply voltage and frequency | 3 AC 380–480 V, +10%/−20%; 47–63 Hz |
|---|---|
| Rated power by duty | 1.50 kW low overload; 1.10 kW high overload |
| Rated input current | 5.50 A low overload; 4.50 A high overload |
| Output current at 440–480 V | 4.10 A low overload; 3.10 A high overload; 6.20 A maximum |
| Serial communication | USS / MODBUS RTU |
| Pulse frequency | 4 kHz |
| Output frequency limits | 240 Hz vector; 550 Hz V/f |
| Low-overload cycle | 150% for 3 s, then 110% for 57 s per 300 s |
| High-overload cycle | 200% for 3 s, then 150% for 57 s per 300 s |
| Digital inputs | 6 standard inputs and 1 fail-safe input |
| Digital outputs | 1 changeover relay and 1 transistor output, each 30 V DC / 0.5 A resistive |
| Analog connections | 1 differential analog/digital input, 10-bit resolution; 1 nonisolated analog output |
| Motor-temperature sensing | PTC, KTY or ThermoClick; ±5°C accuracy |
| Efficiency and power loss | 97%; 60.3 W |
| Operating ambient | −10 to +40°C |
| Installation altitude | 1000 m maximum |
| Motor cable length | 150 m maximum, shielded or unshielded |
| Braking-resistor cable | 15 m maximum |
| Protection and frame | IP20; frame AA |
| Dimensions and weight | 73 × 173 × 155 mm (W × H × D); 1.40 kg |
Frequently Asked Questions
Which network protocol version is 6SL3210-1KE14-3UB2?
This compact inverter uses USS/MODBUS RTU communication.
Can 6SL3210-1KE14-3UB2 control a motor without encoder feedback?
The inverter provides sensorless vector control as well as V/f, FCC and ECO control modes.
How many standard digital commands can I wire to 6SL3210-1KE14-3UB2?
Six standard digital inputs are available in addition to one fail-safe digital input.
Can 6SL3210-1KE14-3UB2 read a motor temperature sensor?
The temperature connection accepts PTC, KTY and ThermoClick sensors.
What motor size should I select for high-overload duty on 6SL3210-1KE14-3UB2?
The high-overload power rating is 1.10 kW, while the low-overload rating is 1.50 kW.
How far can I place a braking resistor from 6SL3210-1KE14-3UB2?
The braking-resistor cable may be up to 15 m long.
Can I switch a 24 V DC resistive control load from 6SL3210-1KE14-3UB2?
The relay and transistor outputs are each rated for resistive loads up to 30 V DC and 0.5 A.