Siemens 6ES7461-1BA01-0AA0 SIMATIC S7-400 IM 461-1 Receive Interface Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a 0.75 m 6ES7468-3AH50-0AA0 or 1.5 m 6ES7468-3BB50-0AA0 connecting cable.
- Match the rack-number coding to the intended expansion rack.
- Calculate the expansion modules’ total 5 V current demand within 5 A.
- Keep applications requiring C-bus transfer outside this coupling arrangement.
SIEMENS SIMATIC S7-400
6ES7461-1BA01-0AA0 SIMATIC S7-400 IM 461-1 Receive Interface Module
Receive interface for short-distance S7-400 expansion with P-bus transmission and power transfer from an IM 460-1, without C-bus transmission.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7461-1BA01-0AA0 |
| Product Type | IM 461-1 receive interface module |
| Core Function | Central expansion-rack coupling |
| Compatible Series / Application | S7-400 central expansion systems |
Matched sender
Use exclusively with the IM 460-1 in the central controller.
Short-distance coupling
Connect the expansion rack over a maximum of 1.5 m.
Rack power
Supply the expansion rack with 5 V at up to 5 A.
Product Overview
6ES7461-1BA01-0AA0 provides the receive side of a centrally coupled SIMATIC S7-400 expansion rack, operating with an IM 460-1 send interface in the central controller.
The connection transfers the P bus and the expansion-rack power supply, making a separate power-supply module unnecessary for the supported rack arrangement; C-bus transmission is not provided.
Key Functions
Central P-bus expansion
The interface carries P-bus data to a nearby expansion rack over a connection of up to 1.5 m.
Power transfer
The receiver supplies expansion modules with 5 V at a maximum of 5 A through the paired interface connection.
Rack identification and diagnostics
A coding switch sets the rack number, and three LEDs provide fault indication.
Official Specifications
| Maximum coupling distance | 1.5 m |
|---|---|
| Backplane current at 5 V DC | 120 mA maximum |
| Maximum module power loss | 600 mW |
| Expansion-rack power output | 5 V DC; maximum 5 A |
| Incoming cable interface | 1 input for a 468-3 connecting cable |
| Fault indicators | 3 LEDs |
| Rack-number selection | Coding switch |
| Permitted expansion racks | UR1, UR2, ER1 and ER2 |
| Module dimensions (W × H × D) | 25 × 290 × 217 mm |
| Approximate weight | 610 g |
Frequently Asked Questions
Which send interface must I pair with 6ES7461-1BA01-0AA0?
The receiver can only be used with an IM 460-1 in the central controller.
Can 6ES7461-1BA01-0AA0 extend a rack over 5 m?
The maximum central coupling distance for this receiver is 1.5 m.
Do I need a separate power supply in the expansion rack with 6ES7461-1BA01-0AA0?
The paired interface supplies the expansion rack with 5 V at up to 5 A, allowing its separate power-supply module to be omitted.
Can I transfer C-bus data through 6ES7461-1BA01-0AA0?
This receiver transfers the P bus without C-bus transmission.
Which racks accept 6ES7461-1BA01-0AA0?
The receiver can be inserted into UR1, UR2, ER1 and ER2 expansion racks.
Which cable lengths can I order for 6ES7461-1BA01-0AA0?
The 468-3 connection is available in 0.75 m and 1.5 m versions for the paired interfaces.
How do I assign the expansion-rack number on 6ES7461-1BA01-0AA0?
The module’s coding switch is used to set the rack number.