Overview
- Apply the contact rating for the actual load voltage and load type.
- Respect the two-channel group current and temperature limits.
- Include the specified fan subassembly when using its higher group-current allowance.
- Provide the external circuit protection required by the installation design.
- Keep the minimum load and load-dependent switching-frequency limits in the application check.
6ES7422-1HH00-0AA0 SIMATIC S7-400 SM 422 16 Relay Output Module
A sixteen-channel relay output module with 5 A rated outputs, isolation in groups of two and load-dependent switching limits.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7422-1HH00-0AA0 |
| Product Type | Relay digital-output module |
| Core Function | Switching AC or DC field loads |
| Application | S7-400 automation racks |
Sixteen relay channels
Relay contacts switch field loads within their specified voltage and current limits.
Grouped load budget
The permissible group current depends on temperature and the use of a fan subassembly.
Local status display
A green LED indicates the state of each digital output.
Product Overview
6ES7422-1HH00-0AA0 provides sixteen relay outputs for a SIMATIC S7-400 rack. The load-voltage ranges cover 1–60 V DC and 2–264 V AC, with contact current limits that depend on the connected load and voltage.
The outputs are isolated from the backplane bus and arranged in isolated groups of two. The module has local channel-state LEDs, while short-circuit protection and a diagnostic function are not integrated.
Key Functions
Switch AC and DC circuits
Relay contacts operate field loads within the specified load-voltage and contact-capacity limits.
Support grouped field circuits
Isolation is provided in two-channel groups and between the outputs and backplane bus.
Indicate commanded output states
Green LEDs provide local status indication for all sixteen channels.
Official Specifications
| Digital outputs | 16 relay outputs |
|---|---|
| Permitted DC load-voltage range | 1–60 V DC; rated value 60 V DC |
| Permitted AC load-voltage range | 2–264 V AC; rated value 230 V AC |
| Maximum 5 V backplane current | 1 A |
| Typical power loss | 4.5 W |
| Rated output current and minimum load | 5 A; minimum load current 11 mA |
| Maximum incandescent-lamp load | 60 W |
| Maximum controlled motor-starter size | NEMA size 5 |
| Maximum switching frequencies | Resistive 10 Hz; inductive AC-15/DC-13 1 Hz; lamp 1 Hz; mechanical 20 Hz |
| Maximum group current without fan | 10 A up to 40 °C; 5 A up to 60 °C, all mounting positions |
| Maximum group current with fan subassembly | 10 A up to 60 °C, all mounting positions |
| Relay operating life | 100000 operations for AC-15/DC-13 loads; 3000000 mechanical operations |
| Maximum inductive contact current | 5 A at 30 V DC or 230 V AC |
| Resistive contact current within permitted load ranges | 5 A at 30 V DC or 230 V AC; 1.2 A at 60 V DC |
| Maximum cable length | 1000 m shielded; 600 m unshielded |
| Protection and diagnostics | No integrated short-circuit protection or diagnostic function |
| Channel status indication | Green LED per output |
| Electrical separation and test voltage | Isolation in groups of two and from the backplane bus; tested at 1500 V AC |
| Dimensions | 25 × 290 × 210 mm (W × H × D) |
| Approximate weight | 700 g |
Frequently Asked Questions
Can I parallel outputs of 6ES7422-1HH00-0AA0 to increase load current?
Paralleling for increased current is not permitted, while redundant control is allowed only with outputs using the same load voltage.
How does a fan affect the group-current limit of 6ES7422-1HH00-0AA0 at 60 °C?
A fan subassembly permits 10 A per group at 60 °C instead of the 5 A limit without a fan.
Which minimum load is required by 6ES7422-1HH00-0AA0?
The specified minimum load current is 11 mA.
Can every resistive DC load use the 5 A rating of 6ES7422-1HH00-0AA0?
The resistive contact limit is 5 A at 30 V DC but 1.2 A at 60 V DC.
Does 6ES7422-1HH00-0AA0 protect its outputs against short circuits?
The module has no integrated output short-circuit protection.
Are all sixteen outputs of 6ES7422-1HH00-0AA0 individually isolated?
Electrical separation is arranged in groups of two channels.
Do the green LEDs on 6ES7422-1HH00-0AA0 provide module diagnostics?
The green LEDs show output status and the module has no diagnostic function.