Siemens SIMATIC S7-300 SM 326 F-DI Digital Input Module 6ES7326-1BK02-0AB0
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the module only in a released SIMATIC S7 F-system hardware configuration.
- Match every safety channel, sensor-supply group and discrepancy or test parameter.
- Repeat the required safety validation and acceptance procedure after hardware exchange.
SIEMENS · SIMATIC S7-300 Safety Integrated
6ES7326-1BK02-0AB0 SIMATIC S7-300 SM 326 F-DI Digital Input Module
The SM 326 F-DI module provides twenty-four 24 V DC fail-safe digital inputs, four isolated sensor-supply outputs and diagnostic signaling for SIMATIC S7 F-systems.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7326-1BK02-0AB0 |
| Product Type | fail-safe 24-channel digital input module |
| Core Function | Acquires 24 V DC safety-related input signals with integrated diagnostics |
| Application or Compatible Series | SIMATIC S7 F-systems requiring up to SIL 3 or Performance Level e input evaluation |
Exact Identification
Match 6ES7326-1BK02-0AB0 character by character and confirm the complete SIMATIC S7-300 SM 326 F-DI Digital Input Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The SM 326 F-DI module provides twenty-four 24 V DC fail-safe digital inputs, four isolated sensor-supply outputs and diagnostic signaling for SIMATIC S7 F-systems.
Twenty-four digital inputs support safety-related signal evaluation up to SIL 3 and Performance Level e. Four isolated sensor-supply outputs provide up to 400 mA rated output current. Readable diagnostics, a diagnostic alarm and local LEDs support fault localization during commissioning and service.
Key Functions
Fail-Safe Signal Acquisition
Twenty-four digital inputs support safety-related signal evaluation up to SIL 3 and Performance Level e.
Integrated Sensor Supplies
Four isolated sensor-supply outputs provide up to 400 mA rated output current.
Channel and Group Diagnostics
Readable diagnostics, a diagnostic alarm and local LEDs support fault localization during commissioning and service.
Official Specifications
| Rated Supply | 24 V DC |
|---|---|
| Reverse Polarity Protection | Yes |
| Maximum Load-Supply Current Without Load | 450 mA |
| Maximum Backplane Current at 5 V DC | 100 mA |
| Sensor-Supply Outputs | 4 isolated outputs |
| Rated Sensor-Supply Output Current | 400 mA |
| Typical Power Loss | 10 W |
| Digital Inputs | 24 |
| Signal 0 Voltage Range | -30 to +5 V |
| Signal 1 Voltage Range | +11 to +30 V |
| Typical Signal 1 Input Current | 10 mA |
| Maximum Input Delay | 3.4 ms for both switching directions |
| Maximum Cable Length | 200 m shielded or 100 m unshielded |
| Channel Isolation Grouping | 12 inputs per isolated group |
| Isolation Test Level | 500 V DC or 350 V AC |
| Highest Safety Integrity | SIL 3 and Performance Level e |
| Required Front Connector | 40-pin |
| Dimensions | 80 x 125 x 120 mm |
Frequently Asked Questions
How many safety inputs can I wire to 6ES7326-1BK02-0AB0?
The module provides twenty-four 24 V DC fail-safe digital inputs.
Which safety level can 6ES7326-1BK02-0AB0 support?
A correctly engineered safety function can reach SIL 3 and Performance Level e.
Can 6ES7326-1BK02-0AB0 supply connected sensors?
Yes; four isolated sensor-supply outputs are available with a rated current of 400 mA.
Which front connector is required for 6ES7326-1BK02-0AB0?
Use the specified 40-pin front connector.
How long can input cables be for 6ES7326-1BK02-0AB0?
The maximum is 200 m with shielded wiring or 100 m with unshielded wiring.
Which local indicators help diagnose 6ES7326-1BK02-0AB0?
A fail-safe operation indicator and the red group-error LED provide local status information.
What must I preserve before replacing 6ES7326-1BK02-0AB0?
Back up the F-project and retain the channel assignments, sensor wiring, test settings and safety acceptance records.