- Use two-wire NAMUR sensors and retain the correct 20-pin field-wiring assignment.
- Evaluate the complete intrinsically safe circuit against its voltage, current, power, capacitance and inductance parameters.
- Include the 0.25 ms preparation time when selecting the input-delay setting.
- Keep unshielded input cables within 200 m and the module ambient at or below 60 °C.
6ES7321-7RD00-0AB0 SIMATIC S7-300 SM321 Four-Channel NAMUR Input Module
An isolated SM321 module with four two-wire NAMUR inputs, selectable delays, channel diagnostics and intrinsically safe terminal parameters.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7321-7RD00-0AB0 |
| Product Type | NAMUR digital input signal module |
| Core Function | Acquiring sensor states from intrinsically safe circuits |
| Application | Hazardous-area signal acquisition |
Connect two-wire NAMUR sensors
Four channels accept NAMUR/DIN 19234 signals using their internal field-circuit supply.
Set the input response
Input delays of 0.1, 0.5, 3, 15 or 20 ms are selectable, with an additional 0.25 ms preparation time.
Locate channel faults
Readable diagnostics and separate channel F, group SF and input-state indicators support fault identification.
Product Overview
6ES7321-7RD00-0AB0 acquires four NAMUR sensor signals through isolated channels. The module supplies the field-input circuits internally at 8.2 V and is designed for signals from hazardous areas.
Selectable input delays adapt the response to the process signal, while red channel-fault and group-error indicators complement the green input-state LEDs. The input circuit limits and required front connector form part of the installation selection.
Key Functions
Connect two-wire NAMUR sensors
Four channels accept NAMUR/DIN 19234 signals using their internal field-circuit supply.
Set the input response
Input delays of 0.1, 0.5, 3, 15 or 20 ms are selectable, with an additional 0.25 ms preparation time.
Locate channel faults
Readable diagnostics and separate channel F, group SF and input-state indicators support fault identification.
Official Specifications
| NAMUR input channels | 4 |
|---|---|
| Rated module load supply | 24 V DC, with reverse-polarity protection |
| Maximum supply currents | 50 mA from L+ without load; 80 mA from the 5 V backplane |
| Internal field-input supply | 8.2 V DC |
| Typical power loss | 1.1 W |
| Signal-zero current range | 0.35–1.2 mA |
| Signal-one current range | 2.1–7 mA |
| Maximum wire-break condition current | 0.1 mA |
| Maximum short-circuit condition current | 8.5 mA |
| Selectable input delays | 0.1, 0.5, 3, 15 or 20 ms, plus 0.25 ms preparation time |
| Maximum input frequency | 2 kHz with a 0.1 ms delay setting |
| Maximum unshielded signal cable | 200 m |
| Gas-group IIC terminal output limits | Uo 10 V; Io 14.1 mA; Po 33.7 mW, maximum values |
| Maximum permissible external capacitance Co | 3 µF for gas group IIC |
| Maximum permissible external inductance Lo | 100 mH for gas group IIC |
| Isolation arrangement | Individual channels isolated from each other, the backplane and L+; 60 V DC/30 V AC in hazardous-area use and 400 V DC/250 V AC in non-hazardous use |
| PTB test number | PTB Ex-96.D.2094X |
| Front connector | 20-pin |
| Maximum operating ambient | 60 °C |
| Module dimensions and approximate mass | 40 × 125 × 120 mm; 230 g |
Frequently Asked Questions
Should I wire a two-wire NAMUR sensor or a conventional 24 V field signal to 6ES7321-7RD00-0AB0?
The field inputs are designed for two-wire NAMUR sensors and use an internal 8.2 V supply.
Which input-delay settings can I select on 6ES7321-7RD00-0AB0?
Choose 0.1, 0.5, 3, 15 or 20 ms and allow an additional 0.25 ms preparation time.
Which delay setting permits a 2 kHz input on 6ES7321-7RD00-0AB0?
The 2 kHz maximum input frequency applies with the 0.1 ms delay setting.
How can I identify a channel fault on 6ES7321-7RD00-0AB0?
The affected channel has a red F fault indicator, alongside the red SF group-error and green input-state indications.
Can I retain a 40-pin connector when installing 6ES7321-7RD00-0AB0 in place of another input module?
The NAMUR module requires a 20-pin front connector.
Are the input channels of 6ES7321-7RD00-0AB0 isolated from each other?
Each input channel is isolated individually from the other channels, the backplane and the load supply.
Which gas-group IIC terminal limits apply to 6ES7321-7RD00-0AB0?
The maximum terminal values are Uo 10 V, Io 14.1 mA and Po 33.7 mW.