Siemens 6ES7288-0CD10-0AA0 PM207 24V 3A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use 35 mm EN 60715 DIN-rail or permitted wall mounting.
- Maintain 20 mm spacing on every side rather than mounting the housings flush together.
- Apply the 3.5% per kelvin derating above +55 °C.
- Connect protective earth for the Class I supply.
6ES7288-0CD10-0AA0 PM207 24V 3A Power Supply
A PM207 supply with wide-range single-phase input and a regulated 24 V DC, 3 A output adjustable between 22.8 and 26.4 V.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7288-0CD10-0AA0 |
| Product Type | Regulated power supply |
| Core Function | Isolated DC power conversion |
| Application | Controller and control-panel supplies |
72 W output
The nominal 24 V DC output provides up to 3 A.
Wide-range input
Accepts 85–264 V AC or 88–370 V DC.
Thermal planning
Output-current derating begins above +55 °C.
Product Overview
6ES7288-0CD10-0AA0 provides regulated and isolated DC power for SIMATIC S7-200 SMART and other control-panel loads. The PM207 converts a wide-range AC or DC input to a nominal 24 V DC output rated at 3 A.
A potentiometer adjusts the output from 22.8 to 26.4 V, and a green LED indicates the normal 24 V condition. Constant-current short-circuit behavior and output overvoltage protection support the connected DC circuits.
Key Functions
Supply regulated control power
The output provides 24 V DC at up to 3 A, with a typical delivered power of 72 W and 89% efficiency.
Ride through brief mains interruptions
At a 170 V input and rated output current, the minimum mains buffering time is 20 ms.
Limit output faults
The output has a constant-current short-circuit characteristic, a typical 4 A current limit and overvoltage protection below 28.8 V.
Official Specifications
| Rated AC input | 100–240 V AC, single phase |
|---|---|
| Permissible input range | 85–264 V AC or 88–370 V DC |
| Line-frequency range | 47–63 Hz |
| Rated output | 24 V DC, 3 A; 72 W typical output power |
| Output adjustment | 22.8–26.4 V via potentiometer |
| Overall voltage tolerance | 0.5% |
| Maximum output ripple peak | 50 mV; 25 mV typical |
| Minimum mains buffering | 20 ms at 170 V input and rated output current |
| Typical efficiency and loss | 89%; 9 W at rated output |
| Input current | 1.65 A at 120 V; 0.75 A at 230 V |
| Maximum inrush current | 30 A at 25 °C |
| Output current limiting | 3.6–4.4 A; 4 A typical, constant-current characteristic |
| Overvoltage protection | Below 28.8 V |
| Maximum turn-on delay | 0.5 s; typical output rise time 50 ms |
| Input-output insulation and class | Galvanically isolated SELV output; protection Class I |
| Housing protection | IP20 |
| Operating temperature and derating | −25 to +70 °C with natural convection; above +55 °C derate output by 3.5% per kelvin |
| Required ventilation clearance | 20 mm above, below, left and right |
| Terminal conductor sizes | Input: 0.5–6 mm² solid or 0.5–4 mm² fine-stranded; output: 0.5–4 mm² |
| Dimensions and net weight | 45 × 100 × 81 mm (W × H × D); 0.46 kg |
Frequently Asked Questions
Can I power 6ES7288-0CD10-0AA0 from a 230 V AC mains circuit?
The rated AC input range is 100–240 V, with a permissible range of 85–264 V AC.
Can I trim the output of 6ES7288-0CD10-0AA0 above 24 V?
The potentiometer adjusts the output between 22.8 and 26.4 V.
Will 6ES7288-0CD10-0AA0 deliver the full 3 A at 65 °C?
Above +55 °C, the permissible output current decreases by 3.5% per kelvin.
How much space should I leave around 6ES7288-0CD10-0AA0?
Provide 20 mm clearance on all four sides for the specified installation arrangement.
Can two 6ES7288-0CD10-0AA0 supplies be paralleled for increased output capacity?
Up to two supplies can be connected in parallel to increase available power.
What feeder protection is recommended for 6ES7288-0CD10-0AA0?
The recommended feeder protection is a 10 A miniature circuit breaker with characteristic C.
What happens at the output of 6ES7288-0CD10-0AA0 during a short circuit?
The output follows a constant-current characteristic with a typical current limit of 4 A.