- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Use 35 mm EN 60715 DIN-rail or permitted wall mounting.
- Mantere spatium 20 mm in omni latere potius quam coniungere caulas ad se invicem.
- Applicare deductionem 3.5% per kelvin supra +55 °C.
- Coniungere terram protectricem pro suppeditatione Classis I.
6ES7288-0CD10-0AA0 PM207 24V 3A Power Supply
A PM207 supply with wide-range single-phase input and a regulated 24 V DC, 3 A output adjustable between 22.8 and 26.4 V.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7288-0CD10-0AA0 |
| Typus Producti | Regulated power supply |
| Functio principalis | Isolated DC power conversion |
| Applicatio | Controller and control-panel supplies |
72 W output
The nominal 24 V DC output provides up to 3 A.
Introductio lati campi
Accepts 85–264 V AC or 88–370 V DC.
Thermal planning
Output-current derating begins above +55 °C.
Product Overview
6ES7288-0CD10-0AA0 provides regulated and isolated DC power for SIMATIC S7-200 SMART and other control-panel loads. The PM207 converts a wide-range AC or DC input to a nominal 24 V DC output rated at 3 A.
A potentiometer adjusts the output from 22.8 to 26.4 V, and a green LED indicates the normal 24 V condition. Constant-current short-circuit behavior and output overvoltage protection support the connected DC circuits.
Key Functions
Supply regulated control power
The output provides 24 V DC at up to 3 A, with a typical delivered power of 72 W and 89% efficiency.
Ride through brief mains interruptions
At a 170 V input and rated output current, the minimum mains buffering time is 20 ms.
Limit output faults
The output has a constant-current short-circuit characteristic, a typical 4 A current limit and overvoltage protection below 28.8 V.
Official Specifications
| Ingressus nominatus AC | 100–240 V AC, single phase |
|---|---|
| Intervallo ingressus permissum | 85–264 V AC or 88–370 V DC |
| Line-frequency range | 47–63 Hz |
| Classificatus exitus | 24 V DC, 3 A; 72 W typical output power |
| Regulatio Output | 22.8–26.4 V via potentiometer |
| Overall voltage tolerance | 0.5% |
| Maximum output ripple peak | 50 mV; 25 mV typical |
| Bufferisation minimal del rete | 20 ms at 170 V input and rated output current |
| Typical efficiency and loss | 89%; 9 W at rated output |
| Correntia input | 1.65 A at 120 V; 0.75 A at 230 V |
| Maxima Currus Inrumpens | 30 A at 25 °C |
| Output current limiting | 3.6–4.4 A; 4 A typical, constant-current characteristic |
| Overvoltage praesidium | Below 28.8 V |
| Maximalis accensionis mora | 0,5 s; typica ascensus temporis output 50 ms |
| Insulatio inter input et output et classis | Output SELV galvanice isolatus; protectio Classis I |
| Protectiō Corporis | IP20 |
| Temperatura operativa et diminutio potestatis | −25 ad +70 °C cum convectione naturali; supra +55 °C diminuere output per 3,5 % per kelvin |
| Spatium ventilationis necessarium | 20 mm supra, infra, ad sinistram et ad dexteram |
| Magnitudines conductorum terminalium | Input: 0,5–6 mm² solidus aut 0,5–4 mm² subtiliter intortus; output: 0,5–4 mm² |
| Dimensiones et pondus netum | 45 × 100 × 81 mm (L × A × P); 0.46 kg |
Quaestiones Frequenter Rogatae
Num possum alimentare 6ES7288-0CD10-0AA0 ex circuitu 230 V AC?
Intervalum nominale ingressus AC est 100–240 V, cum intervalo permisso 85–264 V AC.
Num possum regulare output 6ES7288-0CD10-0AA0 supra 24 V?
Potentiometrum regit output inter 22.8 et 26.4 V.
Num 6ES7288-0CD10-0AA0 praebet integros 3 A ad 65 °C?
Supra +55 °C, currentus output permisus decrescit 3.5% per kelvin.
Quanta spatium circum 6ES7288-0CD10-0AA0 relinquendum est?
Praebere 20 mm spatium in omnibus quattuor lateribus pro disposita ordinatione installationis.
Can two 6ES7288-0CD10-0AA0 supplies be paralleled for increased output capacity?
Up to two supplies can be connected in parallel to increase available power.
What feeder protection is recommended for 6ES7288-0CD10-0AA0?
The recommended feeder protection is a 10 A miniature circuit breaker with characteristic C.
What happens at the output of 6ES7288-0CD10-0AA0 during a short circuit?
The output follows a constant-current characteristic with a typical current limit of 4 A.