Overview
- Use the CPU 22x expansion system.
- Include 20 mA at 5 V and 60 mA at 24 V in the power budget.
- Keep voltage plus common-mode voltage within ±12 V.
- Select voltage or current measurement rather than direct temperature-sensor conversion.
6ES7231-0HC22-0XA8 S7-200 CN EM 231 Analog Input Module
Four differential analog inputs for voltage and current measurements, using 12-bit conversion in an S7-200 CN expansion system.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7231-0HC22-0XA8 |
| Product Type | Analog input expansion module |
| Core Function | Conversion of process measurements |
| Application | CPU 22x analog acquisition |
Four analog inputs
Differential channels acquire voltage or current process signals.
Fast conversion
Analog-to-digital conversion takes less than 250 µs.
Signal-reference planning
The inputs have no field-to-logic isolation.
Product Overview
6ES7231-0HC22-0XA8 adds four differential analog input channels to the SIMATIC S7-200 CN CPU 22x expansion system. Voltage and current measurement functions support process transmitters and other analog signal sources.
Input selection and signal grounding need to suit the common-mode limits of this non-isolated module. The 12-bit conversion system uses separate unipolar and bipolar numeric ranges for scaling in the controller program.
Key Functions
Acquire differential measurements
Four differential channels accept the selected voltage or current range, with high input impedance for voltage signals.
Convert process values
Conversion takes less than 250 µs and the analog step response reaches 95% in 1.5 ms.
Interface with current loops
The 0–20 mA current input presents a 250 Ω load to the connected loop.
Official Specifications
| Analog input channels | 4 differential inputs |
|---|---|
| Conversion resolution | 12 bits unipolar; 11 bits plus sign bipolar |
| Current input range | 0–20 mA |
| Voltage-input impedance | At least 2 MΩ |
| Current-input impedance | 250 Ω |
| Maximum input conversion time | Less than 250 µs |
| Analog step response | 1.5 ms to 95% |
| Input destruction limits | 30 V DC or 32 mA maximum |
| Signal and common-mode limit | Signal voltage plus common-mode voltage within ±12 V |
| Analog data scaling | 0–32000 unipolar; −32000 to +32000 bipolar |
| External supply range | 20.4–28.8 V DC |
| Supply-current requirements | 20 mA from the 5 V backplane; 60 mA from external 24 V DC |
| Field-to-logic isolation | None |
| Typical power loss | 2 W |
| Dimensions and weight | 71.2 × 80 × 62 mm (W × H × D); approximately 183 g |
Frequently Asked Questions
Can 6ES7231-0HC22-0XA8 acquire four analog signals without adding an output channel?
The EM 231 provides four differential analog inputs.
How much loop load does a current input on 6ES7231-0HC22-0XA8 add?
The current input adds a resistance of 250 Ω.
What is the conversion speed of 6ES7231-0HC22-0XA8 for an input channel?
Analog-to-digital conversion takes less than 250 µs.
How does 6ES7231-0HC22-0XA8 represent a unipolar full-scale signal in the PLC?
A unipolar full-scale input is represented by the value 32000.
Can I ignore ground-potential differences when wiring 6ES7231-0HC22-0XA8?
Signal voltage plus common-mode voltage must remain within ±12 V because the inputs are not isolated from logic.
Can 6ES7231-0HC22-0XA8 directly measure a resistance-temperature sensor?
The module supports voltage and current measurements rather than direct resistance or resistance-temperature measurement.
What supply range can I use for the external power connection of 6ES7231-0HC22-0XA8?
The external 24 V DC supply must stay between 20.4 and 28.8 V DC.