Siemens 6ES7223-1PL21-0XA0 SIMATIC S7-200 EM 223 16DI/16 Relay Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the module in the compatible S7-22X CPU expansion arrangement.
- Choose the input-group common polarity to suit the field sensors.
- Keep each relay load within both the permitted voltage range and the point-current limit.
- Keep the total current of each output group within 8 A.
- Provide external short-circuit protection and appropriate load suppression.
- Budget the 5 V bus current and the 24 V relay-coil supply, and use the correct removable terminal blocks.
6ES7223-1PL21-0XA0 SIMATIC S7-200 EM 223 16DI/16 Relay Output Module
An EM 223 expansion module combining sixteen 24 V DC sink/source inputs with sixteen relay outputs, arranged in separate groups of four circuits.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7223-1PL21-0XA0 |
| Product Type | Mixed digital expansion module |
| Core Function | Expanding sensor inputs and relay-switched outputs |
| Application | Compatible S7-22X CPU expansion systems |
Grouped sensor inputs
The input section uses four groups of four points with selectable common polarity.
Relay load circuits
Sixteen relay outputs form four groups, with the specified per-point and group current limits.
Removable field terminals
Detachable terminal blocks support wiring retention during module replacement.
Product Overview
6ES7223-1PL21-0XA0 adds grouped digital inputs and relay-switched output circuits to a compatible S7-200 expansion assembly.
The relay section accepts the specified AC or DC load-voltage range, while the field inputs use 24 V DC signaling and optical isolation; the installation must also provide external short-circuit protection.
Key Functions
Acquire the grouped 24 V DC input signals
Sixteen inputs are arranged as four groups of four, with common-positive or common-negative field wiring for each input group.
Switch AC or DC circuits through relay contacts
The relay section has sixteen output points in four groups, rated 2 A per output and 8 A per group at the stated operating temperatures.
Plan the replacement and expansion wiring
Removable field terminals and the integral module interconnection support the expansion assembly, with the required controller and relay-coil power budgets.
Official Specifications
| Input Circuits | 16 sink/source inputs in 4 groups of 4 |
|---|---|
| Input Voltage Levels | 24 V DC nominal; signal 1: 15–30 V DC; signal 0: 0–5 V DC |
| Signal-1 Input Current | 4 mA |
| Input Propagation Delay | 4.5 ms |
| Two-Wire Sensor Quiescent Current | 1 mA |
| Input Isolation Test | 500 V AC |
| Output Circuits | 16 relay outputs in 4 groups of 4 |
| Permissible Relay Load Voltage | 5–30 V DC or 20–250 V AC |
| Output and Group Current | 2 A per output and 8 A per group at 40 °C and 55 °C |
| Maximum Relay Switching Delays | 10 ms for both ON and OFF transitions |
| Mechanical Relay Life | 10 million operating cycles |
| Electrical Relay Life at Rated Load | 100000 operating cycles |
| Lamp-Load Capacity | 30 W DC or 200 W AC |
| Output Protection Arrangement | External short-circuit protection; no integrated switching-overvoltage limitation |
| Maximum Output-Cable Length | 150 m unshielded; 500 m shielded |
| Controller 5 V Bus Current | 150 mA |
| Relay-Coil Supply Current | 9 mA per energized output from the 24 V DC supply |
| Output Contact Isolation Test | 1500 V AC |
Frequently Asked Questions
Can the input groups of 6ES7223-1PL21-0XA0 use either common-positive or common-negative wiring?
The field-input groups support either common polarity.
May the relay outputs of 6ES7223-1PL21-0XA0 switch both AC and DC loads?
The permissible relay load range is 5 to 30 V DC or 20 to 250 V AC.
How much total current may one output group on 6ES7223-1PL21-0XA0 carry?
Each four-output group is limited to 8 A, with a 2 A limit for each output.
Does 6ES7223-1PL21-0XA0 include output short-circuit protection?
The relay circuits require external short-circuit protection.
What 5 V expansion-current budget should I reserve for 6ES7223-1PL21-0XA0?
Reserve 150 mA from the controller’s 5 V expansion bus.
What switching delay should I allow for the relays in 6ES7223-1PL21-0XA0?
Allow up to 10 ms for either the ON or OFF transition.
Can I retain field wiring when replacing 6ES7223-1PL21-0XA0?
The module uses removable terminal blocks, with the specified 12-pole block available as 6ES7292-1AE20-0AA0.