siemens 6es7223 1pl21 0xa0 simatic s7 200 em 223 16di 16 relay output module-0

For SIEMENS

Home >  Products >  For SIEMENS

Siemens 6ES7223-1PL21-0XA0 SIMATIC S7-200 EM 223 16DI/16 Relay Output Module

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Hot Selling Models
  • Recommended Products
Overview
SIEMENS SIMATIC S7-200

6ES7223-1PL21-0XA0 SIMATIC S7-200 EM 223 16DI/16 Relay Output Module

An EM 223 expansion module combining sixteen 24 V DC sink/source inputs with sixteen relay outputs, arranged in separate groups of four circuits.

At a Glance

Brand Siemens
Model 6ES7223-1PL21-0XA0
Product Type Mixed digital expansion module
Core Function Expanding sensor inputs and relay-switched outputs
Application Compatible S7-22X CPU expansion systems

Grouped sensor inputs

The input section uses four groups of four points with selectable common polarity.

Relay load circuits

Sixteen relay outputs form four groups, with the specified per-point and group current limits.

Removable field terminals

Detachable terminal blocks support wiring retention during module replacement.

Product Overview

6ES7223-1PL21-0XA0 adds grouped digital inputs and relay-switched output circuits to a compatible S7-200 expansion assembly.

The relay section accepts the specified AC or DC load-voltage range, while the field inputs use 24 V DC signaling and optical isolation; the installation must also provide external short-circuit protection.

Ordering focus: Match the input common polarity and relay load voltage, and account for group current, external protection and the CPU’s 5 V expansion-current budget.
Key Functions

Acquire the grouped 24 V DC input signals

Sixteen inputs are arranged as four groups of four, with common-positive or common-negative field wiring for each input group.

Switch AC or DC circuits through relay contacts

The relay section has sixteen output points in four groups, rated 2 A per output and 8 A per group at the stated operating temperatures.

Plan the replacement and expansion wiring

Removable field terminals and the integral module interconnection support the expansion assembly, with the required controller and relay-coil power budgets.

Official Specifications
Input Circuits 16 sink/source inputs in 4 groups of 4
Input Voltage Levels 24 V DC nominal; signal 1: 15–30 V DC; signal 0: 0–5 V DC
Signal-1 Input Current 4 mA
Input Propagation Delay 4.5 ms
Two-Wire Sensor Quiescent Current 1 mA
Input Isolation Test 500 V AC
Output Circuits 16 relay outputs in 4 groups of 4
Permissible Relay Load Voltage 5–30 V DC or 20–250 V AC
Output and Group Current 2 A per output and 8 A per group at 40 °C and 55 °C
Maximum Relay Switching Delays 10 ms for both ON and OFF transitions
Mechanical Relay Life 10 million operating cycles
Electrical Relay Life at Rated Load 100000 operating cycles
Lamp-Load Capacity 30 W DC or 200 W AC
Output Protection Arrangement External short-circuit protection; no integrated switching-overvoltage limitation
Maximum Output-Cable Length 150 m unshielded; 500 m shielded
Controller 5 V Bus Current 150 mA
Relay-Coil Supply Current 9 mA per energized output from the 24 V DC supply
Output Contact Isolation Test 1500 V AC
Frequently Asked Questions

Can the input groups of 6ES7223-1PL21-0XA0 use either common-positive or common-negative wiring?

The field-input groups support either common polarity.

May the relay outputs of 6ES7223-1PL21-0XA0 switch both AC and DC loads?

The permissible relay load range is 5 to 30 V DC or 20 to 250 V AC.

How much total current may one output group on 6ES7223-1PL21-0XA0 carry?

Each four-output group is limited to 8 A, with a 2 A limit for each output.

Does 6ES7223-1PL21-0XA0 include output short-circuit protection?

The relay circuits require external short-circuit protection.

What 5 V expansion-current budget should I reserve for 6ES7223-1PL21-0XA0?

Reserve 150 mA from the controller’s 5 V expansion bus.

What switching delay should I allow for the relays in 6ES7223-1PL21-0XA0?

Allow up to 10 ms for either the ON or OFF transition.

Can I retain field wiring when replacing 6ES7223-1PL21-0XA0?

The module uses removable terminal blocks, with the specified 12-pole block available as 6ES7292-1AE20-0AA0.

Compatibility & Ordering Notes
Before ordering 6ES7223-1PL21-0XA0: Choose the sixteen-input, sixteen-relay-output EM 223 for the compatible CPU, and match the grouped common wiring, relay load ratings and expansion power budget.

Compatibility Checklist for 6ES7223-1PL21-0XA0

  • Use the module in the compatible S7-22X CPU expansion arrangement.
  • Choose the input-group common polarity to suit the field sensors.
  • Keep each relay load within both the permitted voltage range and the point-current limit.
  • Keep the total current of each output group within 8 A.
  • Provide external short-circuit protection and appropriate load suppression.
  • Budget the 5 V bus current and the 24 V relay-coil supply, and use the correct removable terminal blocks.
Hot Selling Models
CA2KN403P7
PFA 20.000 IP55 Type12 RAL 7035
3RU1126-1DB0
AES 1135 1170036
10002368907/03
8WA2011-3KE00
CH10.A250-600.FT2 AT16F03366/900
3LD3354-0TK53
700321-1BL00
4.4T-5/S3060 U-47795