Siemens 6ES7194-4AN00-0AA0 ET 200pro CM IM PN DP M12 7/8-Inch Connection Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use b-coded M12 connectors for PROFIBUS DP and d-coded M12 connectors for PROFINET.
- Use five-wire 7/8-inch power cables for the separate 1L+ and 2L+ supply circuits.
- Limit incoming 1L+ and 2L+ current to 8 A each and retain the separate internal busbar limits.
- P1 R and P2 R support the CPU ring arrangement from firmware V3.2.
- Switch off both supply circuits before removing any 7/8-inch power connector.
- Terminate the PROFIBUS subnet at its ends with the appropriate external M12 terminating connector.
- Fit caps to every unused socket and keep the CPU RJ45 socket sealed when it is not used.
6ES7194-4AN00-0AA0 ET 200pro CM IM PN DP M12 7/8-Inch Connection Module
A CPU connection module with four M12 network connections and two 7/8-inch power connections for the ET 200pro IM 154-8 PN/DP CPU.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7194-4AN00-0AA0 |
| Product Type | CPU network and power connection module |
| Core Function | Routes field network and supply connections to the CPU |
| Application | ET 200pro IM 154-8 PN/DP CPU assemblies |
Two field networks
The module provides the M12 connections for PROFINET and PROFIBUS DP.
Power in and through
Five-pin 7/8-inch connectors feed and loop through the electronics and load supplies.
Protected field connection
Unused sockets must be closed with the matching caps to maintain the assembled protection rating.
Product Overview
6ES7194-4AN00-0AA0 provides the field-network and supply connections for an ET 200pro IM 154-8 PN/DP CPU assembly.
The CM IM PN DP M12, 7/8-inch module brings the two PROFINET ports, incoming and outgoing PROFIBUS DP connections, and 24 V supply connections to field connectors; the separate RJ45 programming connection remains on the CPU.
Key Functions
Connect PROFINET and PROFIBUS DP
Two d-coded M12 connections serve PROFINET, while b-coded M12 connections carry incoming and outgoing PROFIBUS DP.
Feed and loop through the 24 V supplies
The 7/8-inch connectors provide the incoming and outgoing connections for the electronics/encoder supply 1L+ and load supply 2L+.
Maintain the field connection enclosure
Correctly engaged connectors and suitable caps on unused sockets maintain the assembled IP65, IP66 or IP67 protection.
Official Specifications
| PROFINET field ports | Two d-coded M12 sockets, X02 P1 R and P2 R |
|---|---|
| PROFIBUS DP field ports | Two b-coded M12 connections: X01 DP1 with male contacts and DP2 with socket contacts |
| Power-connector arrangement | Two five-pin 7/8-inch connections: X03 incoming supply and X04 feed-through |
| Supply circuit voltage | 24 V DC for electronics/encoder supply 1L+ and load supply 2L+ |
| Maximum incoming supply current | 8 A for 1L+ and 8 A for 2L+ |
| Internal busbar-current limits | 5 A for 1L+ and 10 A for 2L+ |
| Power-connector pin assignment | 1: 2M; 2: 1M; 3: functional ground; 4: 1L+; 5: 2L+ |
| PROFIBUS DP signal pins | 2: data A; 4: data B; 5 and thread: functional ground |
| Field-network cable media | PROFIBUS DP: shielded two-wire cable; PROFINET: shielded four-wire cable |
| Connector tightening torque | 1.5 N·m for the connector knurled screws |
| Assembled ingress protection | IP65, IP66 or IP67 with correctly connected plugs and caps on all unused sockets |
| Dimensions (W × H × D) | 90 × 130 × 51 mm |
| Approximate connection-module weight | 565 g |
Frequently Asked Questions
Which PROFINET ports on 6ES7194-4AN00-0AA0 are designated for a ring topology?
P1 R and P2 R are the ring ports when used with an IM 154-8 PN/DP CPU with firmware version 3.2 or later.
Can the same M12 connector coding be used for both networks on 6ES7194-4AN00-0AA0?
PROFIBUS DP uses b-coded M12 connectors, while PROFINET uses d-coded M12 connectors.
May the 7/8-inch power connector be removed from 6ES7194-4AN00-0AA0 during operation?
Switch off both the electronics/encoder supply 1L+ and load supply 2L+ before removing a 7/8-inch connector.
If 8 A enters the 1L+ feed of 6ES7194-4AN00-0AA0, can all 8 A pass through the internal busbar?
The internal 1L+ busbar is limited to 5 A, leaving 3 A for external feed-through in the 8 A input example.
How are unused sockets on 6ES7194-4AN00-0AA0 protected?
Close every unused M12 and 7/8-inch socket with the matching cap to maintain the assembled ingress protection.
Does 6ES7194-4AN00-0AA0 contain the CPU RJ45 programming socket?
The RJ45 programming connection is on the IM 154-8 PN/DP CPU rather than on this field connection module.
Can pin 1 of the PROFIBUS connector on 6ES7194-4AN00-0AA0 power another station?
The P5V2 voltage on pin 1 is only for the external terminating resistor and must not be looped through to the next connector.