Siemens 6ES7193-4CC30-0AA0 SIMATIC ET 200S TM-P15C23-A1 Terminal Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Preserve the continuous AUX1 link across the group boundary.
- Use A4 and A8 for the planned shared auxiliary potential.
- Match the installed power module to its terminal assignment.
- Count one terminal base per delivery unit for this order number.
SIEMENS SIMATIC ET 200S
6ES7193-4CC30-0AA0 SIMATIC ET 200S TM-P15C23-A1 Terminal Module
A spring-terminal ET 200S power-module base with accessible A4/A8 auxiliary terminals and continuous AUX1 routing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-4CC30-0AA0 |
| Product Type | Power module base |
| Core Function | Potential group infeed |
| Application | ET 200S power distribution |
Accessible continuous AUX1
A4 and A8 give local access while maintaining the auxiliary connection to the group on the left.
Power-group infeed
The inserted power module introduces the next supply group for the downstream electronic modules.
Six Cage Clamp positions
The 2 × 3 spring-terminal pattern combines power-module wiring and auxiliary access.
Product Overview
6ES7193-4CC30-0AA0 is the TM-P15C23-A1 spring-terminal wiring base for an ET 200S power module.
It starts a new electronic-module power group and keeps AUX1 continuous, with A4 and A8 available to connect the shared auxiliary potential locally.
Key Functions
Feed the downstream power buses
The TM-P position receives the power module that supplies the electronic modules until the next power-module base.
Tap the shared auxiliary potential
A4 and A8 connect to the continuous AUX1 bus for protective-conductor or auxiliary potential wiring.
Provide spring-clamp field connections
The six-position terminal layout takes prepared conductors without screw tightening at each connection.
Official Specifications
| Terminal arrangement | 2 × 3 connections |
|---|---|
| Connection technology | Spring terminals (Cage Clamp) |
| AUX1 routing | Continuous to the potential group on the left |
| AUX1 terminal access | A4 and A8 |
| Bare solid and flexible conductor range | 0.14–2.5 mm² |
| Flexible conductor range with ferrule | 0.14–1.5 mm² |
| Wire stripping length | 11 mm |
| Conductors per connection | 1; alternatively 2 totaling up to 1.5 mm² in a shared ferrule |
| Maximum wire insulation diameter | 3.1 mm at 1.5 mm²; 3.8 mm at 2.5 mm² |
| Wiring tool | Screwdriver with 3 mm blade |
| Dimensions (W × H × D) | 15 × 132 × 43 mm |
| Approximate module weight | 65 g |
Frequently Asked Questions
Can I feed a new power group and still share AUX1 using 6ES7193-4CC30-0AA0?
Yes, the base starts a power potential group while preserving the AUX1 connection to the group on the left.
Does 6ES7193-4CC30-0AA0 support Power-group infeed for mobile equipment?
The -A1 version keeps AUX1 continuous, whereas the -A0 version interrupts AUX1 at the left-hand potential-group boundary.
Can I tap the shared auxiliary bus at the power position with 6ES7193-4CC30-0AA0?
Yes, A4 and A8 provide local terminal access to the continuous AUX1 bus.
Is 6ES7193-4CC30-0AA0 supplied with a power module already inserted?
The order number identifies the terminal base, so select the required power module separately for the station.
How should I plan the wiring around the six positions of 6ES7193-4CC30-0AA0?
Use the selected power module terminal assignment for its supply connections and reserve A4 and A8 for AUX1.
What tool should I pack for servicing the spring terminals of 6ES7193-4CC30-0AA0?
Use a screwdriver with a 3 mm blade to open the clamps for insertion of 11 mm stripped conductor ends.
Will one order of 6ES7193-4CC30-0AA0 provide five terminal bases?
No, this exact order number has a delivery quantity of one TM-P15C23-A1 terminal module.