Overview
- Match order number 6ES7151-8AB00-0AB0, hardware version 01 and firmware V2.7.0.
- Use STEP 7 V5.4 SP4 or a later compatible engineering release.
- Install a SIMATIC Micro Memory Card no larger than the verified 8 MB limit.
- Supply 20.4 to 28.8 V DC and include suitable external circuit protection.
- Use P1 R and P2 R for an MRP ring and keep P3 outside the ring domain.
- Add 6ES7138-4HA00-0AB0 when PROFIBUS DP master operation is required.
- Do not plan a firmware upgrade to V3.2 or later for this hardware generation.
Siemens · SIMATIC ET 200S
6ES7151-8AB00-0AB0 IM 151-8 PN/DP CPU
Siemens 6ES7151-8AB00-0AB0 is the hardware-version-01 IM 151-8 PN/DP CPU with firmware V2.7.0, 128 KB work memory and an integrated three-port PROFINET interface.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7151-8AB00-0AB0 |
| Product Type | PN/DP CPU Interface Module |
| Core Function | Executes local S7 control while coordinating networked I/O |
| Application or Compatible Series | SIMATIC ET 200S distributed I/O systems |
Exact Hardware Generation
Match hardware version 01 and firmware V2.7 because later IM 151-8 article numbers have different memory and performance values.
Memory and Engineering
Prepare STEP 7 V5.4 SP4 or later and install a suitable SIMATIC Micro Memory Card before commissioning.
Network Architecture
Plan the three-port PROFINET topology and add the dedicated DP master module only when PROFIBUS DP is required.
Product Overview
Siemens 6ES7151-8AB00-0AB0 is the hardware-version-01 IM 151-8 PN/DP CPU with firmware V2.7.0, 128 KB work memory and an integrated three-port PROFINET interface.
The CPU executes the user program within the ET 200S station and coordinates the connected I/O. An integrated switch supports PROFINET IO controller communication through three RJ45 ports. A separate DP master module adds PROFIBUS DP master operation and S7 routing.
Key Functions
Local S7 Program Execution
The CPU executes the user program within the ET 200S station and coordinates the connected I/O.
Three-Port PROFINET Controller
An integrated switch supports PROFINET IO controller communication through three RJ45 ports.
Optional PROFIBUS Extension
A separate DP master module adds PROFIBUS DP master operation and S7 routing.
Official Specifications
| Hardware and Firmware Version | Hardware 01; firmware V2.7.0 |
|---|---|
| Engineering Software | STEP 7 V5.4 SP4 or later |
| Work Memory | 128 KB, not expandable |
| Retentive Data-Block Capacity | 64 KB |
| Load Memory | SIMATIC Micro Memory Card, 8 MB maximum |
| Memory-Card Data Retention | At least 10 years after final programming |
| Instruction Execution Times | Bit 0.1 µs, word 0.2 µs, fixed-point 2 µs and floating-point 3 µs |
| Available S7 Counters and Timers | 256 counters and 256 timers |
| S7 Timer Range | 10 ms to 9990 s |
| Maximum Address Area | 2048 bytes for inputs and 2048 bytes for outputs |
| Process Image | Adjustable from byte 0 to 2047; preset byte 0 to 127 |
| Ethernet Connection | Three RJ45 ports with an internal PROFINET switch |
| IRT Capability | PROFINET V2.2 IRT with high flexibility from firmware V2.7 |
| Open IE Communication | Eight access points for TCP and ISO-on-TCP, with up to 8192-byte data length where specified |
| Web-Server Clients | Five HTTP clients |
| Optional PROFIBUS DP Capacity | Up to 32 DP slaves at up to 12 Mbaud through 6ES7138-4HA00-0AB0 |
| Time Synchronization | NTP client on PROFINET; DP time master or slave with the DP master module |
| Diagnostics Buffer | 500 entries maximum, with the last 100 retained after power cycling |
| Supply and Consumption | 20.4 to 28.8 V DC; typically 320 mA at 24 V or 380 mA at 20 V; 5.5 W typical loss |
| Dimensions and Weight | 120 × 119.5 × 75 mm; approximately 320 g |
Frequently Asked Questions
Which STEP 7 version is required for 6ES7151-8AB00-0AB0?
Use STEP 7 V5.4 SP4 or a later compatible release for hardware version 01 and firmware V2.7.
Does 6ES7151-8AB00-0AB0 require a memory card?
A SIMATIC Micro Memory Card is required, and the verified maximum load-memory capacity is 8 MB.
Can 6ES7151-8AB00-0AB0 be upgraded to firmware V3.2?
No, this hardware generation cannot be upgraded to firmware V3.2 or later.
Which network ports should form a redundancy ring on 6ES7151-8AB00-0AB0?
Use P1 R and P2 R as media-redundancy ring ports, while P3 remains outside the redundancy domain.
How is PROFIBUS DP added to 6ES7151-8AB00-0AB0?
Add DP master module 6ES7138-4HA00-0AB0, which permits up to 32 DP slaves at up to 12 Mbaud.
What I/O address capacity is available on 6ES7151-8AB00-0AB0?
The maximum configured address space is 2048 bytes for inputs and 2048 bytes for outputs.
Can a later CPU replace 6ES7151-8AB00-0AB0 in an existing STEP 7 project?