Overview
- Keep each output within its 0.5 A rated current.
- Respect the 2 A output-group total and load-dependent switching limits.
- Match 24 V DC sensors to the input thresholds.
- Select no more than 12 additional ET 200S modules and exclude fail-safe modules.
6ES7151-1CA00-3BL0 ET 200S IM151-1 COMPACT 16 DI 16 DQ Electronics Block
The mixed-I/O IM151-1 COMPACT electronics block combines 16 digital inputs and 16 transistor outputs with expandable PROFIBUS station functionality.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7151-1CA00-3BL0 |
| Product Type | Mixed-I/O electronics block |
| Core Function | PROFIBUS distributed signal exchange |
| Application | ET 200S compact automation stations |
Mixed onboard I/O
Sixteen inputs and sixteen transistor outputs serve the compact station.
Protected outputs
The 24 V DC outputs include short-circuit protection.
Expansion capacity
Up to 12 additional ET 200S modules can be connected, excluding fail-safe modules.
Product Overview
6ES7151-1CA00-3BL0 provides a mixed-I/O IM151-1 COMPACT electronics block with 16 inputs and 16 outputs. Each output has a rated current of 0.5 A, subject to the output-group total-current limit.
The PROFIBUS DP interface supports transmission rates up to 12 Mbit/s, while input and output indicators assist with local signal checks during station commissioning.
Key Functions
Combined sensing and switching
The onboard inputs acquire 24 V DC signals and the transistor outputs switch 24 V DC loads.
Load-dependent output control
Resistive, inductive and lamp loads have different maximum switching frequencies, with a 5 W maximum lamp load.
Expandable compact I/O
The block couples the local channels and additional ET 200S modules to PROFIBUS DP at up to 12 Mbit/s.
Official Specifications
| Onboard channel arrangement | 16 digital inputs and 16 transistor outputs |
|---|---|
| Rated supply voltage | 24 V DC; reverse-polarity protection |
| Maximum supply current | 100 mA |
| Typical power loss | 3 W |
| Digital input thresholds | Logic 0: −30 to +5 V; logic 1: 13 to 30 V |
| Typical input current | 3 mA at logic 1 |
| Input delay in either direction | 1.2 to 4.8 ms; typically 3 ms |
| Rated output current per channel | 0.5 A |
| Output ON voltage | At least L+ − 0.8 V |
| Maximum OFF leakage current | 0.5 mA |
| Maximum output-group current | 2 A up to 60 °C |
| Maximum lamp load | 5 W |
| Maximum output switching frequency | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp loads |
| Maximum output delay | 0.5 ms ON; 1.3 ms OFF |
| Maximum PROFIBUS transmission rate | 12 Mbit/s |
| Isolation test voltage | 500 V DC |
| Dimensions (W × H × D) | 120 × 81 × 58 mm |
| Electronics-block weight | Approximately 230 g |
Frequently Asked Questions
Can I load every output in a group on 6ES7151-1CA00-3BL0 to 0.5 A simultaneously?
The individual 0.5 A output rating remains subject to a maximum total of 2 A per output group up to 60 °C.
What lamp size can I switch with 6ES7151-1CA00-3BL0?
The maximum permitted lamp load is 5 W.
Can 6ES7151-1CA00-3BL0 switch an inductive load at 10 Hz?
The maximum specified inductive-load switching frequency is 2 Hz.
How much voltage drop should I allow across an ON output of 6ES7151-1CA00-3BL0?
The output ON voltage is at least the load supply voltage minus 0.8 V.
Will 6ES7151-1CA00-3BL0 capture a pulse substantially shorter than 1 ms reliably?
Its input delay ranges from 1.2 to 4.8 ms, so substantially shorter pulses fall outside that input timing.
Does the 230 g weight of 6ES7151-1CA00-3BL0 include the complete station assembly?
The approximately 230 g value applies to the electronics block only.
Can I expand 6ES7151-1CA00-3BL0 with standard and fail-safe ET 200S modules together?
The station permits up to 12 additional ET 200S modules but does not permit fail-safe modules.