Overview

SIEMENS SIMATIC ET 200pro

6ES7144-4JF00-0AB0 SIMATIC ET 200pro 4 AI RTD High Feature Module

Acquire four RTD or resistance signals with selectable two-, three- or four-wire connections, programmable smoothing and channel-level wire-break diagnostics.

At a Glance

Brand Siemens
Model 6ES7144-4JF00-0AB0
Product Type RTD analog input electronics module
Core Function Measure field temperature and resistance
Application ET 200pro distributed I/O installations

Temperature acquisition

Platinum and nickel RTDs are linearized into process values.

Line-resistance compensation

Three- and four-wire connections compensate sensor lead resistance automatically.

Separate connector module

The electronics includes its bus module; the matching CM IO is ordered separately.

Product Overview

6ES7144-4JF00-0AB0 is a four-channel High Feature analog electronics module for ET 200pro. It measures floating resistances or resistance thermometers and provides selectable temperature characteristics for Pt and Ni sensors.

The module supports two-, three- and four-wire connection systems, linearization, configurable diagnostics and measured-value smoothing, with electrically separated field inputs and an eight-byte input address area.

Ordering focus: Select the matching CM IO connection module separately and configure the RTD characteristic, wiring method and interference-suppression frequency for each measurement.
Key Functions

Acquire RTD and resistance signals

The input ranges cover Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500 and Ni1000 sensors together with resistance ranges up to 3000 Ω.

Compensate lead resistance

Three- and four-wire measurement automatically compensates line resistance, while a two-wire connection includes the lead resistance in the measured value.

Report channel wiring faults

Channel diagnostics identify wire breaks, and configurable smoothing reduces fluctuations in the measured process values.

Official Specifications
Analog Channels 4 floating resistance or RTD inputs
Electronics Supply 24 V DC from 1L+ with reverse-polarity protection against destruction
Typical Current Consumption 27 mA from 1L+ and 10 mA from the backplane bus
Typical Power Dissipation 0.7 W
Input Address Space 8 bytes
Supported RTD Types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500 and Ni1000
Resistance Ranges 150 Ω, 300 Ω, 600 Ω and 3000 Ω
Resolution 15 bits for resistance; 15 bits plus sign for RTDs
Input Resistance 10 MΩ
Sensor Excitation Current Approximately 1.25 mA below 500 Ω and 0.5 mA at or above 500 Ω
Measuring Principle Integrating, with selectable 50 Hz or 60 Hz suppression
Integration Time 20 ms at 50 Hz; 16.667 ms at 60 Hz
Measured-Value Smoothing 4 settings with time constants of 1, 4, 16 or 64 module cycles
Operational Error Limit ±0.175% of the input range across the temperature range
Maximum Shielded Cable Length 30 m
Isolation Test Voltage 500 V DC
Electronics Dimensions 45 × 130 × 35 mm (W × H × D)
Approximate Electronics Weight 150 g
Frequently Asked Questions

Which resistance thermometers can I wire to 6ES7144-4JF00-0AB0?

The module accepts Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500 and Ni1000 sensors.

Does 6ES7144-4JF00-0AB0 support Line-resistance compensation for mobile equipment?

Yes, the matching CM IO from the 6ES7194-4..00-0AA0 family must be ordered separately.

How can I compensate sensor lead resistance when using 6ES7144-4JF00-0AB0?

Use a three- or four-wire connection for automatic compensation of the line resistance.

Will a two-wire RTD connection on 6ES7144-4JF00-0AB0 include the lead resistance?

Yes, the line resistance is also measured when a two-wire connection is used.

How can I stabilize a fluctuating measurement from 6ES7144-4JF00-0AB0?

Select one of the four smoothing settings with a time constant of 1, 4, 16 or 64 module cycles.

What input address space should I reserve for 6ES7144-4JF00-0AB0?

Reserve eight input bytes for the module.

How does 6ES7144-4JF00-0AB0 detect a disconnected RTD lead?

The channel wire-break diagnostics monitor terminals 1 and 3.

Compatibility & Ordering Notes
Before ordering 6ES7144-4JF00-0AB0: Choose the ET 200pro CM IO connector for the required sensor wiring and reserve the input address area, then configure the sensor characteristics and line-frequency rejection.

Compatibility Checklist for 6ES7144-4JF00-0AB0

  • Match the CM IO pin assignment to the selected two-, three- or four-wire connection.
  • Use shielded sensor cables within the 30 m limit.
  • Choose the correct Pt or Ni characteristic and temperature coefficient.
  • Enable the required channel diagnostics and smoothing during station configuration.
Hot Selling Models
PNOZ 3 5S / 1Ö 1W 474856
6ES7131-6BF00-0CA0
SDE3-V1S-B-WQ4-2P-M8-W5
45-SD-D/LA/SI
K2R-102/720-50767
C22-DL-W-K10-24-P1 RSC4.4T-0.22/TXL2013
SYJ3140-5MOZ-Q
B18U-M18-AP6X-H1141
SIES-Q5B-PS-KL
DILM40 XTCE040D
6ES7132-4HB01-0AB0
16-PE 3036165
CAD32BL 040708
GA9106.210
6ES7194-4DD00-0AA0

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.