Overview
- Use a 24 V DC load supply and stay within 0.5 A per channel and 4 A per group up to 55 °C.
- Order the required I/O connection module separately from the included bus module.
- Do not parallel outputs for increased current; the supported parallel case is redundant control of a load.
- Observe the different switching-frequency limits for resistive, inductive and lamp loads.
- Keep shielded or unshielded field cables within 30 m.
- When driving a digital input, jumpering 1M and 2M removes the separation between 1L+ and 2L+.
6ES7142-4BF00-0AA0 ET 200pro 8 DO 24 V DC 0.5 A Electronics Module
An eight-output ET 200pro electronics module with 0.5 A per channel, module diagnostics and an included bus module, requiring a separate I/O connection module.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7142-4BF00-0AA0 |
| Product Type | Digital output electronics module |
| Core Function | Switches DC actuators through current-sourcing outputs |
| Application | SIMATIC ET 200pro distributed I/O stations |
Eight sourcing outputs
Each output switches up to 0.5 A from the 24 V DC load supply.
Module diagnostics
A red SF indicator identifies group errors, with green output-status indication.
Separate field connector
The bus module is included, while the compatible I/O connection module is ordered separately.
Product Overview
6ES7142-4BF00-0AA0 switches eight current-sourcing digital outputs in a SIMATIC ET 200pro station.
The electronics provide electronic short-circuit protection per channel and module-level fault diagnostics, with 0.5 A rated current per output and a maximum group current of 4 A up to 55 °C; the field-wiring connection module is a separate component.
Key Functions
Switch DC loads through eight outputs
The current-sourcing outputs supply DC loads at up to 0.5 A per channel.
Limit and report output faults
Electronic short-circuit protection operates per channel, while short-circuit-to-ground diagnostics are reported at module level.
Show local channel and group status
Green indicators show output status and the red SF indicator identifies a group error.
Official Specifications
| Rated load supply 2L+ | 24 V DC |
|---|---|
| Maximum electronics current draw | 30 mA from 2L+ without load and 30 mA from the 3.3 V backplane bus |
| Typical power dissipation | 2 W |
| Output address space | 1 byte maximum |
| Output-current limits | 0.5 A per channel; 4 A total per group up to 55 °C in all mounting positions |
| Typical short-circuit response threshold | 0.7 A |
| Inductive shutdown-voltage limit | 2L+ minus 47 V |
| Maximum lamp load | 5 W |
| Load resistance | 48 Ω to 4 kΩ |
| Minimum high-state output voltage | 2L+ minus 0.8 V |
| Maximum off-state residual current | 0.5 mA |
| Maximum resistive-load switching frequency | 100 Hz |
| Maximum inductive-load switching frequency | 0.5 Hz |
| Maximum lamp-load switching frequency | 1 Hz |
| Maximum field-cable length | 30 m for shielded or unshielded cable |
| Isolation test voltage | 707 V DC, type test |
| Output isolation arrangement | No isolation between channels; isolation between channels and the backplane bus |
| Local indicators | Red SF group-error indicator and green digital-output status indicators |
| Dimensions (W × H × D) | 45 × 130 × 35 mm |
| Approximate weight | 140 g |
Frequently Asked Questions
Can two outputs of 6ES7142-4BF00-0AA0 be paralleled to increase the load current?
Parallel operation is not permitted for increasing current capacity.
How fast can 6ES7142-4BF00-0AA0 switch an inductive load?
The maximum switching frequency for an inductive load is 0.5 Hz.
Does 6ES7142-4BF00-0AA0 identify short circuits by individual diagnostic channel?
Short circuits from outputs to ground are diagnosed module by module rather than as individual channel diagnostic messages.
Is the field connection module included with 6ES7142-4BF00-0AA0?
The bus module is included, but the compatible I/O connection module must be ordered separately.
How long may a field cable connected to 6ES7142-4BF00-0AA0 be?
The maximum field-cable length is 30 m for either shielded or unshielded cable.
Can all outputs of 6ES7142-4BF00-0AA0 carry their rated current at the same time?
The outputs may each carry 0.5 A within the 4 A group limit up to 55 °C in all mounting positions.
Are the output channels of 6ES7142-4BF00-0AA0 galvanically isolated from each other?
The output channels share a potential, while isolation is provided between the channels and the backplane bus.