Siemens 6ES7134-4JB00-0AB0 SIMATIC ET 200S 2AI Thermocouple Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Configure the correct thermocouple or millivolt range for each channel.
- Provide the external reference-junction compensation required by the thermocouple connection.
- Choose integration and smoothing settings to suit the mains environment and process response.
- Use shielded signal cables within 50 m and the matching ET 200S terminal arrangement.
6ES7134-4JB00-0AB0 SIMATIC ET 200S 2AI Thermocouple Input Module
Two-channel 15 mm ET 200S thermocouple module with ±80 mV input, external reference-junction compensation and configurable smoothing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-4JB00-0AB0 |
| Product Type | Thermocouple analog input module |
| Core Function | Thermocouple and millivolt acquisition |
| Application | ET 200S temperature-measurement stations |
Thermocouple linearization
Types B, E, J, K, L, N, R, S and T are supported for temperature acquisition in Celsius.
Selectable interference rejection
Integrating conversion supports the stated 50 Hz or 60 Hz mains-frequency rejection settings.
Diagnostic and smoothing functions
Overflow, underflow, thermocouple wire-break detection and selectable smoothing support stable process values.
Product Overview
6ES7134-4JB00-0AB0 acquires two thermocouple or millivolt signals in an ET 200S station.
The module linearizes supported thermocouple types in degrees Celsius, provides configurable diagnostic functions and uses an external compensation box for each thermocouple reference junction.
Key Functions
Thermocouple linearization
Types B, E, J, K, L, N, R, S and T are supported for temperature acquisition in Celsius.
Selectable interference rejection
Integrating conversion supports the stated 50 Hz or 60 Hz mains-frequency rejection settings.
Diagnostic and smoothing functions
Overflow, underflow, thermocouple wire-break detection and selectable smoothing support stable process values.
Official Specifications
| Analog channel count | 2 |
|---|---|
| Millivolt range and resolution | ±80 mV; 15 bits plus sign |
| Thermocouple types | B, E, J, K, L, N, R, S and T |
| Temperature unit | Degrees Celsius |
| Reference-junction compensation | External compensation box per channel; no internal compensation |
| Nominal supply | 24 V DC from the power module; reverse-polarity protection |
| Supply current | 30 mA maximum from L+; 10 mA maximum from the 3.3 V backplane |
| Typical power loss | 0.6 W |
| Input address space | 4 bytes |
| Input resistance | 1 MΩ |
| Permanent input-voltage limit | 10 V |
| Maximum shielded cable | 50 m |
| Integration setting | 16.7 ms for 60 Hz; 20 ms for 50 Hz |
| Conversion time | 55 ms at 60 Hz; 65 ms at 50 Hz; wire-break check adds 20 ms |
| Smoothing factors | None: 1; low: 4; medium: 32; high: 64 conversion cycles |
| Error limits | Operational ±0.6%; basic ±0.4% at 25°C |
| Wire-break diagnostics | Supported for thermocouple inputs |
| Isolation | From backplane and L+; not between channels; 500 V DC test |
| Dimensions | 15 × 81 × 52 mm (W × H × D) |
| Approximate weight | 40 g |
Frequently Asked Questions
Does 6ES7134-4JB00-0AB0 provide internal cold-junction compensation?
Each thermocouple channel requires an external compensation box because internal reference-junction compensation is not provided.
Can 6ES7134-4JB00-0AB0 return thermocouple values directly in Fahrenheit?
Thermocouple values are provided in degrees Celsius.
How does wire-break monitoring affect the conversion time of 6ES7134-4JB00-0AB0?
Enabling the wire-break check adds 20 ms to the conversion time.
Can I use the wire-break function of 6ES7134-4JB00-0AB0 for every millivolt input?
The specified wire-break diagnostic applies to thermocouple inputs.
How should I choose the integration time on 6ES7134-4JB00-0AB0?
Select 20 ms for 50 Hz rejection or 16.7 ms for 60 Hz rejection.
How much smoothing can I apply to a noisy signal on 6ES7134-4JB00-0AB0?
The selectable smoothing factors are one, four, thirty-two or sixty-four conversion cycles.
How far can I run the shielded sensor lead to 6ES7134-4JB00-0AB0?
The maximum shielded signal-cable length is 50 m.