Siemens 6ES7132-4BF50-0AA0 ET 200S Eight-Channel Sink Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Apply 100 Hz, 0.5 Hz and 10 Hz limits to resistive, inductive and lamp loads respectively.
- Allow 1,000 m shielded or 600 m unshielded cable at most.
- Use green LEDs for local output-state checks.
- Keep output circuits within their channel and 4 A module limits.
6ES7132-4BF50-0AA0 ET 200S Eight-Channel Sink Output Module
A compact eight-output sink module with selectable station addressing, green output-state LEDs and load-dependent switching rates.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4BF50-0AA0 |
| Product Type | Digital output electronics module |
| Core Function | Sinking control of DC loads |
| Application | Distributed actuator stations |
Load-dependent rates
Resistive, inductive and lamp loads have different maximum switching rates.
Local output indication
Green LEDs show output states without a module diagnostic function.
15 mm assembly
The electronics module measures 15 × 81 × 52 mm.
Product Overview
6ES7132-4BF50-0AA0 controls eight DC actuator circuits using sinking transistor outputs in an ET 200S distributed station. The 15 mm-wide module supports isochronous operation and occupies no more than one byte of output address space.
Load selection affects the permitted operating rate: resistive circuits can switch faster than inductive circuits. Green LEDs provide local channel-state indication, while channel-to-channel isolation and a diagnostic function are not provided.
Key Functions
Match the switching duty
Maximum switching rates are 100 Hz for resistive loads, 0.5 Hz for inductive loads and 10 Hz for lamp loads.
Connect extended field wiring
Maximum cable lengths are 1,000 m with shielding and 600 m without shielding.
Separate field and backplane potentials
The outputs are isolated from the backplane bus, with insulation tested at 500 V DC.
Official Specifications
| Output channels | 8 transistor sink outputs |
|---|---|
| Rated load voltage | 24 V DC from the power module |
| Channel current | 0.5 A rated; permissible signal-1 range 5–600 mA |
| Maximum module current | 4 A |
| Maximum signal-0 residual current | 5 µA |
| Short-circuit protection threshold | 1.5 A typical |
| Inductive shutdown-voltage limit | 47 V typical |
| Maximum lamp load | 5 W |
| Load-resistance range | 48–3,400 Ω |
| Maximum resistive-load delay | 300 µs from 0 to 1; 600 µs from 1 to 0 |
| Maximum switching frequency | Resistive: 100 Hz; inductive: 0.5 Hz; lamp: 10 Hz |
| Maximum cable length | 1,000 m shielded; 600 m unshielded |
| Maximum internal currents | 5 mA from load voltage L+ without load; 10 mA from the 3.3 V backplane |
| Typical power loss | 1.5 W |
| Maximum output address space | 1 byte |
| Electrical isolation | No isolation between channels; isolation from backplane bus |
| Insulation test voltage | 500 V DC |
| Output indication and diagnostics | Green status indicator; no diagnostic function |
| Dimensions and weight | 15 × 81 × 52 mm (W × H × D); approximately 40 g |
Frequently Asked Questions
How often can 6ES7132-4BF50-0AA0 switch an inductive actuator?
The maximum inductive-load switching frequency is 0.5 Hz.
Can 6ES7132-4BF50-0AA0 switch a resistive circuit at 100 Hz?
The maximum switching frequency for a resistive load is 100 Hz.
What can I learn from the green indicators on 6ES7132-4BF50-0AA0?
Each green indicator shows the corresponding digital-output state.
Are neighboring output channels on 6ES7132-4BF50-0AA0 electrically isolated?
There is no electrical isolation between the output channels.
How long can an unshielded actuator cable be on 6ES7132-4BF50-0AA0?
The maximum unshielded cable length is 600 m.
Can two outputs on 6ES7132-4BF50-0AA0 provide redundant control of one load?
Parallel connection for redundant control is permitted within the same module, while current uprating is not permitted.
Will 6ES7132-4BF50-0AA0 reserve more than one output byte?
The maximum address space is one byte per module.