- Use a compatible TM-E15 terminal module in the required spring, screw or Fast Connect design.
- Keep the aggregate output current within 4 A.
- Do not use parallel channels to increase load capability.
- Account for the possible 50 µs pulse when load power is switched by a mechanical contact.
6ES7132-4BD31-0AA0 ET 200S 4DO 24VDC 2A ST Module
Four 24 V DC transistor outputs rated at 2 A each, with a 4 A module limit and an extended vertical operating range up to 55 °C.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4BD31-0AA0 |
| Product Type | Standard digital output module |
| Core Function | Switching of field actuators |
| Application | Distributed valve and contactor circuits |
2 A channels
Four output channels drive solenoid valves, DC contactors or indicators.
4 A total
The combined module output current remains limited to 4 A.
Local status
A green LED indicates each output state.
Product Overview
6ES7132-4BD31-0AA0 provides four standard digital outputs for an ET 200S station. The module is suited to solenoid valves, DC contactors and indicator lights, with a 2 A rated current per output and a 4 A maximum module total.
Per-channel short-circuit protection limits output faults, while the green LEDs indicate output states without a diagnostic function. The vertical installation temperature limit reaches 55 °C.
Key Functions
Operate DC actuators
The four output channels switch 24 V DC loads, with a minimum ON-state output voltage of L+ minus 1 V.
Protect individual output circuits
Per-channel short-circuit protection has a typical pickup threshold from 2.8 to 7.2 A.
Support compact addressing
The normal output address space is one byte, or four bits when packed addressing is used.
Official Specifications
| Output channels | 4 |
|---|---|
| Rated load voltage | 24 V DC from the power module |
| Rated output and module current | 2 A per channel; 4 A maximum per module |
| Permitted signal-1 current | 7 mA–2.4 A |
| Signal-0 leakage current | 0.5 mA maximum |
| Minimum signal-1 voltage | L+ minus 1 V |
| Maximum resistive-load delay | 200 µs on; 1.3 ms off |
| Load-resistance range | 12 Ω–3.4 kΩ |
| Maximum lamp load | 10 W |
| Switching rates | 100 Hz resistive; 2 Hz with a 0.5 H inductive load; 10 Hz lamp load |
| Short-circuit pickup threshold | 2.8–7.2 A typical, per channel |
| Internal inductive interruption limit | Typically L+ minus 55–60 V |
| Maximum cable length | 1,000 m shielded; 600 m unshielded |
| Output address and parameter allocation | 1 byte output space or 4 bits packed; 1 byte parameters |
| Maximum no-load consumption | 5 mA per channel from load voltage L+ |
| Typical power dissipation | 1.6 W |
| Electrical isolation and test | No channel isolation; isolated from backplane bus; tested at 500 V DC |
| Permissible circuit potential difference | 75 V DC or 60 V AC |
| Vertical operating temperature | 0 to +55 °C |
| Module width and weight | 15 mm; approximately 40 g |
Frequently Asked Questions
Can all four channels of 6ES7132-4BD31-0AA0 supply 2 A simultaneously?
The module total is limited to 4 A even though each channel has a 2 A rating.
Which output terminals on 6ES7132-4BD31-0AA0 correspond to channels 0 and 1?
Channel 0 uses terminal 1 and channel 1 uses terminal 5.
Can 6ES7132-4BD31-0AA0 operate vertically at 55 °C?
The extended vertical operating range is 0 to +55 °C.
How should I allocate packed output addresses for 6ES7132-4BD31-0AA0?
Packed addressing occupies four output bits instead of the normal one-byte output allocation.
Can the LEDs on 6ES7132-4BD31-0AA0 report a short-circuit diagnostic?
The green LEDs indicate output states and the module does not provide a diagnostic function.
Can I parallel two channels of 6ES7132-4BD31-0AA0 to drive a larger actuator?
Parallel connection is allowed for redundant triggering within one module but not for increasing output capability.
What startup pulse should a high-speed receiver tolerate when powered through 6ES7132-4BD31-0AA0?
Switching the power-module load supply through a mechanical contact can produce an approximately 50 µs signal-1 pulse on the outputs.