Siemens 6ES7132-4BD02-0AA0 SIMATIC ET 200S 4DO DC24V/0.5A ST Digital Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the chosen TM-E15 terminal layout to the four channel assignments.
- Keep individual actuator current within the output rating.
- Do not parallel outputs to increase capacity.
- Include the brief power-on output pulse in fast-counter applications.
6ES7132-4BD02-0AA0 SIMATIC ET 200S 4DO DC24V/0.5A ST Digital Output Module
A four-channel standard output module for 24 V DC actuators, with 0.5 A rated current per channel and short-circuit protection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4BD02-0AA0 |
| Product Type | Digital output module |
| Core Function | Discrete actuator switching |
| Application | ET 200S distributed I/O stations |
Four actuator channels
Switch solenoid valves, DC contactors or indicator lamps from the distributed I/O station.
Packed process data
The four output bits can be packed instead of allocating a complete byte to each module.
Visible channel state
A green LED at each output shows its commanded output state.
Product Overview
6ES7132-4BD02-0AA0 switches four DC load circuits within an ET 200S station, drawing its load voltage from the associated power module.
The standard module supports isochronous operation and provides short-circuit-protected outputs, with separate limits for resistive, inductive and lamp switching.
Key Functions
Drive distributed DC loads
Each output carries a rated 0.5 A, with a total output current of 2 A per module.
Reduce output address allocation
Packed configuration uses four output bits, while the normal allocation uses one byte.
Monitor output activation locally
The four green channel LEDs indicate active outputs without requiring a diagnostic message.
Official Specifications
| Output channel count | 4 |
|---|---|
| Rated load voltage | 24 V DC from the power module |
| Rated output current per channel | 0.5 A; permissible signal-1 range 7–600 mA |
| Total output current per module | 2 A |
| Maximum lamp load | 5 W |
| Load resistance range | 48 Ω–3.4 kΩ |
| Minimum signal-1 output voltage | L+ minus 1 V |
| Maximum turn-on and turn-off delays | 50 µs and 120 µs respectively, with resistive load |
| Maximum resistive-load switching rate | 800 Hz |
| Inductive and lamp-load switching rates | 2 Hz and 10 Hz respectively |
| Maximum unshielded and shielded cable lengths | 600 m and 1000 m respectively |
| Output address allocation | 1 byte normally; 4 bits when packed |
| Parameter length | 1 byte |
| Maximum no-load current from L+ | 10 mA per channel |
| Typical module power dissipation | 0.8 W |
| Channel isolation arrangement | No isolation between channels; isolation from backplane bus |
| Permissible inter-circuit potential difference | 75 V DC or 60 V AC |
| Insulation test voltage | 500 V DC |
| Module width | 15 mm |
| Approximate module weight | 40 g |
Frequently Asked Questions
Can 6ES7132-4BD02-0AA0 operate four 0.5 A valves at the same time?
Yes, the rated 0.5 A per output and 2 A total module current permit that combination when the installation and load conditions remain within their limits.
Can I parallel the outputs of 6ES7132-4BD02-0AA0 to supply a larger actuator?
No, connecting outputs in parallel to increase output capacity is not permitted.
How quickly can 6ES7132-4BD02-0AA0 repeatedly switch an inductive load?
The specified switching rate for inductive loads is 2 Hz, compared with up to 800 Hz for resistive loads.
How much output address space does 6ES7132-4BD02-0AA0 require when packed?
Packed configuration occupies four output bits instead of the normal one-byte allocation.
Will 6ES7132-4BD02-0AA0 report a diagnostic fault for a failed actuator?
No, this standard module has channel status LEDs but no diagnostic function.
Which field terminals carry the four signals on 6ES7132-4BD02-0AA0?
The outputs are assigned to terminals 1, 5, 2 and 6 for channels 0, 1, 2 and 3 respectively.
What transient should I consider when energizing the power group of 6ES7132-4BD02-0AA0 through a mechanical contact?
Depending on the circuit, the outputs can carry a signal-1 pulse of approximately 50 µs when the rated load voltage is connected through a mechanical contact.