Siemens 6ES7131-6BF61-0AA0 ET 200SP DI 8x24VDC SRC BA
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use CC02 labeling for the module-specific color identification.
- Provide AUX terminals or a potential distributor for three-wire sensors and a potential distributor for four-wire sensors.
- Allocate one byte of input address space.
- Use this Basic module for standard digital inputs rather than counter, oversampling, MSI or safety functions.
6ES7131-6BF61-0AA0 ET 200SP DI 8x24VDC SRC BA
Eight sourcing digital inputs for 24 V DC NPN sensors, with selectable input filtering and supply-voltage diagnostics in an ET 200SP station.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7131-6BF61-0AA0 |
| Product Type | Basic digital input module |
| Core Function | Acquisition of NPN sensor states |
| Application | Distributed machine input stations |
NPN inputs
M-reading, sourcing inputs with IEC 61131 Type 1 characteristics.
BaseUnit A0
Fits A0 BaseUnits and uses the CC02 module color code.
Selectable filtering
Offers eight delay settings from 0.05 ms to 20 ms.
Product Overview
6ES7131-6BF61-0AA0 provides eight sourcing digital inputs for NPN field signals in SIMATIC ET 200SP stations. This Basic module reads signals relative to L+ and fits BaseUnits of type A0.
Selectable input delays allow the input response to suit the connected sensors and cable installation. A green channel LED shows each input state, while PWR and DIAG indicators support supply and module checks during commissioning.
Key Functions
Read M-switching sensors
The sourcing inputs acquire NPN signals using IEC 61131 Type 1 input characteristics, with one byte of input address space for the module.
Adjust input filtering
Choose 0.05, 0.1, 0.4, 0.8, 1.6, 3.2, 12.8 or 20 ms of input delay, plus the cable-dependent additional delay of 30 to 500 µs.
Monitor the module supply
Parameterizable supply-voltage monitoring can generate a diagnostic alarm, with a green/red DIAG LED and a green PWR LED providing local indication.
Official Specifications
| Input channels | 8, parameterizable |
|---|---|
| Input supply | 24 V DC rated; permissible range 19.2–28.8 V DC |
| Input characteristic | Sourcing, NPN, M-reading; IEC 61131 Type 1 |
| Signal thresholds relative to L+ | Signal 0: +30 to −5 V; signal 1: −11 to −30 V |
| Input current at signal 1 | 6 mA typical |
| Input-delay settings | 0.05, 0.1, 0.4, 0.8, 1.6, 3.2, 12.8 or 20 ms; additional line-dependent delay 30–500 µs |
| Maximum sensor-cable length | 1,000 m shielded; 200 m unshielded |
| Two-wire sensor quiescent current | 1.5 mA maximum |
| Module current consumption | 4.5 mA rated; 53 mA maximum |
| Typical power loss | 1.5 W |
| Input address space | 1 byte |
| BaseUnit and identification | Type A0; color code CC02; mechanical coding type B |
| Engineering versions | TIA Portal V14 or later; STEP 7 V5.5 SP3 or later; PROFINET GSDML V2.3 |
| Diagnostic coverage | Supply-voltage monitoring and diagnostic alarm; no wire-break or short-circuit diagnostics |
| Electrical separation | Inputs isolated from backplane bus; no isolation between channels |
| Insulation test voltage | 707 V DC, type test |
| Operating temperature | Horizontal: −30 to +60 °C; vertical: −30 to +50 °C; operation below 0 °C from FS02 |
| Dimensions and weight | 15 × 73 × 58 mm (W × H × D); approximately 28 g |
Frequently Asked Questions
Can 6ES7131-6BF61-0AA0 read an NPN sensor that switches its signal to M?
The sourcing, M-reading inputs are designed for 24 V DC NPN signals with IEC 61131 Type 1 characteristics.
Which BaseUnit arrangement suits a three-wire sensor on 6ES7131-6BF61-0AA0?
Use a type A0 BaseUnit with AUX terminals or a potential distributor module for the three-wire connection.
How can I retain short pulses when configuring 6ES7131-6BF61-0AA0?
Select the required input delay from 0.05 to 20 ms and include the additional cable-dependent delay of 30 to 500 µs in the response calculation.
Will 6ES7131-6BF61-0AA0 identify a broken sensor wire automatically?
The module provides supply-voltage diagnostics but does not provide wire-break, short-circuit or individual channel diagnostics.
How far can I run a sensor cable to 6ES7131-6BF61-0AA0?
The maximum sensor-cable length is 1,000 m with shielding or 200 m without shielding.
Can a two-wire sensor with 2 mA leakage be used on 6ES7131-6BF61-0AA0?
A two-wire sensor must have a quiescent current no greater than 1.5 mA.
Can I use 6ES7131-6BF61-0AA0 in a cabinet operating below freezing?
Hardware from FS02 supports operation down to −30 °C, with upper limits of +60 °C horizontally and +50 °C vertically.