Siemens 6ES7131-4BB00-0AB0 SIMATIC ET 200S 2DI DC24V High Feature Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the exact terminal diagram for the installed TM-E15 base.
- Keep the 24 V DC supply and sensor load within the 500 mA rating.
- Preserve the application’s configured delay and process interrupts.
- Check the sensor’s OFF-state leakage against the 1.5 mA limit.
6ES7131-4BB00-0AB0 SIMATIC ET 200S 2DI DC24V High Feature Input Module
A two-channel 24 V DC High Feature input module with configurable signal filtering, process interrupts, readable diagnostics and an electronically protected sensor supply.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7131-4BB00-0AB0 |
| Product Type | Digital input electronics |
| Core Function | Acquiring switch and proximity-sensor states |
| Application | ET 200S modular input stations |
Configurable input response
Four nominal delay selections range from 0.1 to 15 ms for both input transitions.
Sensor power on the base
The module provides a rated 500 mA sensor supply with electronic short-circuit protection.
Channel and group indication
Green channel LEDs indicate input states, while a red SF LED identifies a group error.
Product Overview
6ES7131-4BB00-0AB0 acquires two 24 V DC input signals from switches and compatible proximity sensors in an ET 200S station.
The High Feature electronics combine selectable input delay and process interrupts with clock-synchronized operation, and the installed terminal-base version determines the field-sensor, ground and AUX1 connections.
Key Functions
Adapt input filtering to the field signal
Nominal delays of 0.1, 0.5, 3 and 15 ms can be configured for rising and falling signal transitions.
Acquire input events with station timing
Configurable process interrupts and clock-synchronized operation support applications that require coordinated input acquisition.
Supply and monitor connected sensors
The module supplies the sensor circuit through an electronically protected output and provides channel-state indication together with readable diagnostic data.
Official Specifications
| Input channel count | 2 |
|---|---|
| Rated module and input supply | 24 V DC |
| ON-state input voltage | 11–30 V |
| OFF-state input voltage | −30 to +5 V |
| Typical ON-state input current | 8 mA |
| Configurable input delays, both transitions | Nominal 0.1, 0.5, 3 or 15 ms; respective ranges 0.05–0.15, 0.4–0.6, 2.7–3.3 or 14.85–15.15 ms |
| Input characteristic | IEC 61131 type 1 |
| Maximum two-wire sensor quiescent current | 1.5 mA |
| Maximum signal-cable length | 600 m unshielded; 1,000 m shielded |
| Typical module power loss | 0.4 W |
| Sensor supply output | 500 mA rated; minimum loaded voltage L+ minus 0.5 V |
| Sensor supply protection | Electronic short-circuit protection, per module |
| Electrical isolation | Inputs isolated from backplane bus; no channel-to-channel isolation |
| Permissible inter-circuit potential difference | 75 V DC or 60 V AC |
| Isolation test voltage | 500 V DC |
| Status and diagnostic provision | Green LED per channel; red SF group-error LED; readable diagnostic data |
| Timing features | Configurable process interrupts and clock-synchronized operation |
| Dimensions (W × H × D) | 15 × 81 × 52 mm |
| Approximate module weight | 35 g |
Frequently Asked Questions
How do I connect three-wire sensors through a TM-E15S24-01 base for 6ES7131-4BB00-0AB0?
Connect channel 0 signal, sensor supply and ground to terminals 1, 2 and 3, and connect the corresponding channel 1 wires to terminals 5, 6 and 7.
May an unused 48 V wire be landed at terminal 4 or 8 of a TM-E15S24-01 base carrying 6ES7131-4BB00-0AB0?
No, those unused-wire positions are limited to circuits up to 30 V DC.
Which input-filter delay settings can I select for 6ES7131-4BB00-0AB0?
The configurable nominal delay settings are 0.1, 0.5, 3 and 15 ms for both rising and falling transitions.
Will a sensor output of 10 V be guaranteed to register as ON on 6ES7131-4BB00-0AB0?
No, the specified ON-state input-voltage range starts at 11 V.
Can I run an 800 m unshielded sensor cable to 6ES7131-4BB00-0AB0?
No, unshielded signal cable is limited to 600 m, while shielded cable is permitted up to 1,000 m.
How can I distinguish an active input from a group fault on 6ES7131-4BB00-0AB0?
A green LED indicates each channel’s input state, while the red SF LED indicates a group error.
Is short-circuit protection on the sensor supply of 6ES7131-4BB00-0AB0 independent for each channel?
No, the electronic sensor-supply short-circuit protection acts per module.