Siemens 6ES5464-8MF21 SIMATIC S5 Two-Channel Pt100 Analog Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Set the enabled channels and 50 or 60 Hz integration selection before commissioning.
- Choose Pt100 linearization and temperature compensation for the intended measurement mode.
- Use the appropriate two-wire or four-wire sensor circuit and observe the channel differential-voltage limit.
- The module uses the CPU bus supply and does not require an external L+ sensor-module supply.
6ES5464-8MF21 SIMATIC S5 Two-Channel Pt100 Analog Input Module
A selectable one- or two-channel input module with Pt100 linearization, integrating conversion and configurable wire-break monitoring.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES5464-8MF21 |
| Product Type | Temperature and voltage input module |
| Core Function | Acquiring Pt100 resistance and low-level voltage signals |
| Application | SIMATIC S5-100U I/O |
Pt100 temperature conversion
Selectable linearization converts Pt100 resistance into temperature values over the supported sensor range.
Integrating low-level acquisition
Dual-slope conversion measures resistance or ±500 mV signals with mains-frequency integration.
Selectable sensor monitoring
Wire-break monitoring can be enabled with a red diagnostic indicator.
Product Overview
6ES5464-8MF21 converts Pt100 resistance or low-level voltage signals for the S5-100U I/O system.
The module supports two-wire and four-wire sensor arrangements and can operate with channel 0 alone or both channels, with switch-selectable mains-frequency rejection and Pt100 linearization.
Key Functions
Pt100 temperature conversion
Selectable linearization converts Pt100 resistance into temperature values over the supported sensor range.
Integrating low-level acquisition
Dual-slope conversion measures resistance or ±500 mV signals with mains-frequency integration.
Selectable sensor monitoring
Wire-break monitoring can be enabled with a red diagnostic indicator.
Official Specifications
| Selectable input count | 1 channel or 2 channels |
|---|---|
| Resistance measuring range | 0–200 Ω; maximum 400 Ω |
| Voltage measuring range | −500 to +500 mV |
| Sensor connection | 2-wire or 4-wire |
| Pt100 linearized range | −100 to +850 °C in 0.5 °C steps |
| Digital representation | 12 bits plus sign; left-justified two’s complement |
| Conversion method | Integrating dual-slope voltage-time conversion |
| Integration time | 20 ms at 50 Hz; 16.6 ms at 60 Hz |
| Encoding time at 2,048 units | Maximum 60 ms per input at 50 Hz or 50 ms at 60 Hz |
| Encoding time at 4,095 units | Maximum 80 ms per input at 50 Hz or 66.6 ms at 60 Hz |
| Input isolation | Inputs isolated from ground; no isolation between channels |
| Maximum channel differential voltage | ±1 V |
| Basic and operating error | ±0.15% basic; ±0.4% over 0–60 °C |
| Pt100 linearization accuracy | ±0.5 °C within the rated range |
| Maximum shielded sensor cable | 200 m |
| CPU-bus supply consumption | 9 V DC; typically 100 mA |
| Typical dissipation | 0.9 W |
| Pt100 excitation current | 2.5 mA |
| Wire-break indication | Selectable monitoring with red LED |
| Approximate mass | 230 g |
Frequently Asked Questions
Can I connect a four-wire Pt100 sensor to 6ES5464-8MF21?
The input circuit supports both two-wire and four-wire sensor connections.
How do I operate only one input on 6ES5464-8MF21?
Set the channel-selection switches for channel 0 rather than the two-channel configuration.
Which temperature range is available when Pt100 linearization is enabled on 6ES5464-8MF21?
The linearized Pt100 range extends from −100 to +850 °C with 0.5 °C increments.
Why should I match the frequency switch on 6ES5464-8MF21 to the local power system?
The 50 or 60 Hz selection sets the integration period for the corresponding mains-frequency interference.
How long may the shielded sensor cable be on 6ES5464-8MF21?
The specified maximum shielded sensor-cable length is 200 m.
What happens when enabled wire-break monitoring detects an open sensor on 6ES5464-8MF21?
The module provides a red wire-break diagnostic indication.
Are the two measurement channels of 6ES5464-8MF21 isolated from one another?
The inputs are isolated from ground but are not isolated from each other.