- Provide two suitable DC supplies and size the load so the redundant supply arrangement meets the required operating condition.
- Allow for the approximately 0.6 V module drop when setting the supply voltage.
- Mount on a 35 mm DIN rail with 45 mm ventilation clearance above and below the module.
- Keep the connected circuits within the 10–58 V DC input range and the 20 A output limit.
6EP4346-7RB00-0AX0 SITOP RED1200 Redundancy Module
Compact redundancy module for two supplies up to 10 A each, with a 20 A output and a 12–48 V DC nominal system range.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP4346-7RB00-0AX0 |
| Product Type | DC supply redundancy module |
| Core Function | Decoupling of parallel DC power supplies |
| Application | Redundant industrial DC supply systems |
Dual-source decoupling
Two power-supply inputs, each rated for up to 10 A, feed one common DC output through the redundancy module.
Broad DC operating range
The 10–58 V input operating range covers nominal DC supply systems from 12 to 48 V.
Tool-friendly cabinet wiring
Push-in power terminals and a narrow DIN-rail body support compact redundant power assemblies.
Product Overview
6EP4346-7RB00-0AX0 decouples two DC supply inputs so that a redundant power arrangement can feed a common load without coupling the source outputs directly together.
The RED1200 handles a nominal 12–48 V DC system with up to 20 A at the output and uses push-in terminals in a 35 mm wide DIN-rail housing.
Key Functions
Dual-source decoupling
Two power-supply inputs, each rated for up to 10 A, feed one common DC output through the redundancy module.
Broad DC operating range
The 10–58 V input operating range covers nominal DC supply systems from 12 to 48 V.
Tool-friendly cabinet wiring
Push-in power terminals and a narrow DIN-rail body support compact redundant power assemblies.
Official Specifications
| Nominal DC system range | 12–48 V DC |
|---|---|
| Operating input voltage | 10–58 V DC |
| Input and output currents | Two inputs up to 10 A each; output up to 20 A |
| Typical output voltage drop | Approximately 0.6 V below input |
| Output voltage adjustment | Nonadjustable |
| Typical efficiency | 97.5% |
| Full-load power loss | 12 W typical at 24 V / 20 A |
| No-load power loss | 0.1 W maximum |
| Electrical construction | No input/output isolation; protection class III |
| Operating ambient | −40 to +70°C with natural convection |
| Storage and transport ambient | −40 to +85°C |
| Relative humidity | 5–95%, noncondensing |
| Input and output terminals | Push-in connections for 0.2–10 mm² conductors |
| Degree of protection | IP20 |
| Dimensions and weight | 35 × 135 × 125 mm (W × H × D); 0.47 kg |
| Required installation height | 225 mm, including 45 mm clearance above and below |
| Side clearance | 0 mm |
| Mounting rail | 35 × 7.5 mm or 35 × 15 mm DIN rail to EN 60715 |
Frequently Asked Questions
Can 6EP4346-7RB00-0AX0 connect two 10 A supplies to a common load?
The module accepts two inputs rated up to 10 A each and provides a common output rated up to 20 A.
How much voltage should I allow for 6EP4346-7RB00-0AX0 in a 24 V system?
Allow approximately 0.6 V of voltage drop between the input supply and the load output.
Will 6EP4346-7RB00-0AX0 maintain the load during a loss of both supplies?
The redundancy module decouples the supplies but does not provide energy storage for hold-up during a loss of both sources.
Can I adjust the output voltage on 6EP4346-7RB00-0AX0?
The output is nonadjustable and follows the input voltage minus the module voltage drop.
How much vertical ventilation space does 6EP4346-7RB00-0AX0 need?
Allow 45 mm above and 45 mm below the 135 mm housing for a total installation height of 225 mm.
Which wire sizes fit the power terminals of 6EP4346-7RB00-0AX0?
The push-in input and output terminals accept conductors from 0.2 to 10 mm².
Can 6EP4346-7RB00-0AX0 be used directly on an AC supply?
The module operates with DC inputs from 10 to 58 V and requires external DC power supplies.