- Use the specified three-phase AC network and the required connected three-pole feeder protection.
- Keep the adjusted voltage and load within the maximum 480 W output power.
- Set the overload characteristic and parallel-operation arrangement for the application.
- Snap onto the specified 35 mm DIN rail and maintain top and bottom ventilation clearances.
6EP1436-3BA10 SITOP PSU300M Three-Phase 24 V 20 A Power Supply
A modular three-phase supply with an adjustable DC output, short-duration power boost and selectable overload behavior.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1436-3BA10 |
| Product Type | Stabilized industrial power supply |
| Core Function | Supplying regulated control-circuit power |
| Application | Industrial control-cabinet DC loads |
Adjustable regulated output
The output can be set from 24 to 28.8 V while maintaining the stated maximum power.
Temporary overload reserves
Short-duration current boost and a time-limited 150% overload allowance support transient loads.
Selectable fault response
The protection arrangement provides constant-current behavior or latching shutdown.
Product Overview
6EP1436-3BA10 converts a three-phase AC input into isolated, regulated DC power for control loads.
The adjustable output, parallel-operation option and temporary overload reserves support the chosen control-power arrangement, while local LEDs and a relay contact report operating condition.
Key Functions
Adjustable regulated output
The output can be set from 24 to 28.8 V while maintaining the stated maximum power.
Temporary overload reserves
Short-duration current boost and a time-limited 150% overload allowance support transient loads.
Selectable fault response
The protection arrangement provides constant-current behavior or latching shutdown.
Official Specifications
| AC input network | Three-phase; 400–500 V nominal, 320–575 V range |
|---|---|
| Input frequency | 47–63 Hz |
| Rated input current | 1.2 A at 400 V; 1 A at 500 V |
| Maximum inrush | 18 A at 25 °C; I²t 0.8 A²s |
| Rated output | 24 V DC, 20 A |
| Output adjustment | 24–28.8 V; maximum 480 W |
| Mains-failure buffering | At least 15 ms at 400 V input and rated output current |
| Output ripple and peaks | Maximum 100 mV ripple and 200 mV peaks |
| Typical efficiency and loss | 93%; 36 W loss at rated output |
| Short current boost | Typically 60 A for 25 ms during operating short circuit |
| Timed overload | 150% rated output current for up to 5 s per minute |
| Overload protection characteristic | Approximately 23 A constant current or latching shutdown |
| Parallel operation | Up to 2 units for increased power |
| Output overvoltage protection | Below 35 V |
| Output condition signal | Normally open relay contact rated 60 V DC, 0.3 A |
| Enclosure and safety class | IP20; Class I; isolated safety-extra-low-voltage output |
| Operating temperature | −25 to +70 °C; 3%/K derating from +60 to +70 °C |
| Storage and transport | −40 to +85 °C |
| Installation clearances | 50 mm above and below; no side clearance required |
| Dimensions and net mass | 70 × 125 × 125 mm; 1.2 kg |
Frequently Asked Questions
Can I keep the full 20 A output when adjusting 6EP1436-3BA10 above 24 V?
The adjustable output remains subject to a maximum output-power limit of 480 W.
Can I connect two 6EP1436-3BA10 units in parallel for increased power?
The stated maximum parallel arrangement is two units.
How much space must remain above and below 6EP1436-3BA10?
Maintain 50 mm clearance above and below the power supply.
Must I derate 6EP1436-3BA10 above a 60 °C ambient temperature?
The output-current derating is 3% per kelvin between +60 and +70 °C.
Can I read a remote 24 V OK indication from 6EP1436-3BA10?
A normally open relay contact provides the signal with a 60 V DC and 0.3 A rating.
Does 6EP1436-3BA10 provide a selectable latching overload response?
The short-circuit protection can use either an approximately 23 A constant-current characteristic or latching shutdown.
Which feeder protection arrangement is required for 6EP1436-3BA10?
The feeder requires a three-pole connected 6–16 A characteristic-C breaker or one of the specified 3RV circuit breakers.