Siemens 6EP1331-5BA10 SITOP PSU100C 24 V 1.3 A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the 85–264 V AC or 110–300 V DC input range.
- Mount on EN 60715 35 × 7.5 mm or 35 × 15 mm DIN rail.
- Keep 50 mm clear above and below the supply.
- Reduce the output load above 60 °C.
- Use the recommended feeder breaker from 16 A characteristic B or 10 A characteristic C.
6EP1331-5BA10 SITOP PSU100C 24 V 1.3 A Power Supply
A 30 mm-wide PSU100C providing regulated 24 V DC at 1.3 A from a wide-range AC or DC input.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1331-5BA10 |
| Product Type | Stabilized DC power supply |
| Core Function | Isolated control-voltage conversion |
| Application | Compact industrial control panels |
Small installation width
The enclosure occupies 30 mm on the DIN rail.
Load-temperature planning
The output remains rated at 1.3 A up to 60 °C and is reduced to 1.2 A at 70 °C.
Output supervision
A green LED indicates that the output voltage is OK.
Product Overview
6EP1331-5BA10 provides a regulated 24 V DC supply for compact control circuits, with a nominal output current of 1.3 A and a typical delivered power of 30 W.
The PSU100C accepts single-phase AC or DC input and uses natural convection; its output adjustment, short-circuit shutdown and restart behavior support a defined low-power control-supply arrangement.
Key Functions
Convert a wide-range source
The supply accepts 85–264 V AC or 110–300 V DC and produces an isolated, regulated output.
Trim the control voltage
The front potentiometer adjusts the nominal 24 V output between 22.2 and 26.4 V.
Recover from output faults
Electronic shutdown protects the output during a short circuit and permits automatic restart.
Official Specifications
| AC Input Range | 85–264 V AC, single phase |
|---|---|
| DC Input Range | 110–300 V DC |
| Input Frequency | 47–63 Hz |
| Rated Output | 24 V DC, 1.3 A; 30 W typical delivered power |
| Output Adjustment | 22.2–26.4 V |
| Overall Voltage Tolerance | 3% |
| Output Residual Ripple | 200 mV maximum; 25 mV typical |
| Minimum Mains Buffering | 20 ms at 230 V input and rated output current |
| Input Current | 0.63 A at 100 V; 0.31 A at 230 V |
| Maximum Inrush Current | 34 A at 25 °C |
| Typical Efficiency and Rated-Load Loss | 86%; 4.5 W |
| Maximum Turn-On Delay | 0.6 s; typical voltage rise time 90 ms |
| Typical Output Current Limit | 1.4 A |
| Short-Circuit Response | Electronic shutdown with automatic restart |
| Output Safety and Protection Class | Isolated SELV output; Class I |
| Enclosure Protection | IP20 |
| Operating Temperature and Derating | −20 to +70 °C; above +60 °C derate by 0.8% per kelvin; 1.2 A at +70 °C |
| Required Ventilation Clearance | 50 mm above and below; 0 mm at either side |
| Electrical Terminations | Screw terminals for 0.5–2.5 mm² conductors |
| Dimensions and Net Weight | 30 × 80 × 100 mm (W × H × D); 0.17 kg |
Frequently Asked Questions
Will 6EP1331-5BA10 fit into a 30 mm-wide rail position?
The enclosure width is 30 mm.
Can I keep the housing of 6EP1331-5BA10 directly beside another compatible supply?
The specified lateral clearance is zero, while 50 mm remains required above and below.
At what temperature must I start reducing the load on 6EP1331-5BA10?
Output-current derating starts above 60 °C at 0.8% per kelvin.
What does the green LED on 6EP1331-5BA10 indicate?
The green indicator shows that the output voltage is OK.
Does 6EP1331-5BA10 require a protective-earth connection?
The power supply is Class I equipment and has an input PE terminal.
Can 6EP1331-5BA10 bridge a short interruption at a 230 V input?
The minimum mains buffering time at 230 V and rated output current is 20 ms.
How should a parallel arrangement of 6EP1331-5BA10 be started?
Up to two supplies may be paralleled for increased power, with startup limited to a single nominal load.