Overview
Siemens • SIMATIC ET 200SP HA
6DL1136-6AA00-0PH1 ET 200SP HA F-AI 8xI HART Fail-Safe Analog Input Module
The F-AI 8xI module provides eight 16-bit, two-wire or four-wire HART current inputs with channel diagnostics, redundant-operation support and fail-safe use up to SIL 3 or PL e.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DL1136-6AA00-0PH1 |
| Product Type | Fail-safe analog input module |
| Core Function | Acquires safety-related process measurements for protective functions |
| Application or Compatible Series | ET 200SP HA and PCS 7 safety applications |
Exact Identification
Match 6DL1136-6AA00-0PH1 character by character and confirm the complete ET 200SP HA F-AI 8xI HART Fail-Safe Analog Input Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The F-AI 8xI module provides eight 16-bit, two-wire or four-wire HART current inputs with channel diagnostics, redundant-operation support and fail-safe use up to SIL 3 or PL e.
Eight channels support safety-related current measurement for process transmitters. HART communication and per-channel diagnostics support device access and maintenance. The module can be used redundantly with the documented F1 terminal block arrangement.
Key Functions
Fail-Safe Current Acquisition
Eight channels support safety-related current measurement for process transmitters.
HART and Channel Diagnostics
HART communication and per-channel diagnostics support device access and maintenance.
Redundant Station Option
The module can be used redundantly with the documented F1 terminal block arrangement.
Official Specifications
| Firmware Version | V1.0 |
|---|---|
| Firmware Update | Supported |
| Usable Terminal Blocks | H1, F1, H0 and N0 |
| Module Color Code | CC00 |
| Identification and Maintenance Data | I&M0 to I&M3 |
| Redundant Operation | Supported with F1 terminal block |
| Rated Supply Voltage | 24 V DC |
| Permissible Supply Range | 19.2 to 28.8 V DC |
| Reverse-Polarity Protection | Supported |
| Rated Current Consumption | 90 mA without sensor supply |
| Sensor Supply Outputs | 8, short-circuit protected |
| Maximum Sensor-Supply Current per Channel | 30 mA |
| Backplane-Bus Power | 90 mW |
| Power Loss | 2.8 W typical; 3.3 W maximum |
| Address Space | 22 input bytes and 5 output bytes |
| Analog Input Channels | 8 |
| Current Input Destruction Limit | 35 mA |
| Supported Input Ranges | 0 to 20 mA and 4 to 20 mA |
| Input Resistance | 150 Ω |
| HART Role | Primary master |
Frequently Asked Questions
Which terminal blocks can I use with 6DL1136-6AA00-0PH1?
Use an approved H1, F1, H0 or N0 terminal block according to the station design.
How do I configure redundant operation for 6DL1136-6AA00-0PH1?
Use the documented F1 terminal-block arrangement and the corresponding redundant hardware configuration.
Can 6DL1136-6AA00-0PH1 power connected transmitters?
Yes; each of the eight short-circuit-protected sensor supplies can deliver up to 30 mA.
Which current ranges are accepted by 6DL1136-6AA00-0PH1?
Configure supported channels for 0 to 20 mA or 4 to 20 mA measurement.
Does 6DL1136-6AA00-0PH1 act as a HART primary master?
Yes; assign the HART communication and device parameters for each applicable channel.
What safety information should I archive before replacing 6DL1136-6AA00-0PH1?
Retain the PCS 7 project, F parameters, signatures, channel assignments, terminal-block type and acceptance records.
What validation is required after installing 6DL1136-6AA00-0PH1?
Test channel wiring, transmitter supply, range scaling, diagnostics, HART communication, redundancy and the approved safety functions.
Compatibility & Ordering Notes
Compatibility Checklist
- Use the terminal block and redundancy mode defined by the approved station design.
- Preserve the safety program, F parameters and acceptance documentation.
- Validate every analog channel and diagnostic path before returning the safety function to service.