Overview
SIEMENS SIMATIC HMI Multi Panels - 10.4-inch touch-operated Multi Panel
6AV6643-0CD01-1AX1 SIMATIC MP 277 10-inch Touch Multi Panel
Siemens specifies this MP 277 10-inch Touch Multi Panel with a 10.4-inch TFT display, 6 MB application memory, Ethernet, RS422/RS485 and two USB host ports.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6AV6643-0CD01-1AX1 |
| Product Type | 10.4-inch touch-operated Multi Panel |
| Core Function | Provides local operator visualization and machine control |
| Application or Compatible Series | Existing SIMATIC MP 277 operator stations using WinCC flexible projects |
Product Overview
Siemens specifies this MP 277 10-inch Touch Multi Panel with a 10.4-inch TFT display, 6 MB application memory, Ethernet, RS422/RS485 and two USB host ports.
The panel is intended for existing MP 277 operator stations using WinCC flexible projects. Replacement planning must preserve the display resolution, mounting cutout, supply, network interfaces and saved HMI project.
Key Functions
Touch HMI Operation
A 10.4-inch resistive analog touchscreen provides 640 x 480 visualization with 64K colors.
Automation Connectivity
Ethernet and RS422/RS485 interfaces connect the panel to supported SIMATIC controllers and field networks.
Peripheral Expansion
Two USB 1.1 host ports support approved low-speed and full-speed peripheral devices.
Official Specifications
| Active Display Area | 211.2 x 158.4 mm |
|---|---|
| Display Technology | LCD TFT |
| Resolution | 640 x 480 pixels |
| Display Colors | 64K |
| Brightness Control | Supported |
| Input Technology | Resistive analog touchscreen |
| Application Memory | 6 MB |
| Serial Interface | 1 x RS422/RS485, maximum 12 Mbit/s |
| USB Interfaces | 2 x USB host, USB 1.1 low/full speed |
| Maximum USB Load | 500 mA |
| Ethernet Interface | 1 x RJ45, 10/100 Mbit/s |
| Permissible Supply Range | 20.4 to 28.8 V DC |
| Maximum Supply Transient | 35 V for 500 ms |
| Minimum Time Between Transients | 50 s |
| Current Consumption | Approximately 700 mA typical; maximum 1,100 mA |
| Power-On Inrush Energy | Approximately 1 A²s |
| Buffered Real-Time Clock | Approximately 6 weeks |
| Front Dimensions | 335 x 275 mm |
| Mounting Cutout and Installation Depth | 310 x 248 mm cutout; 61 mm installation depth |
| Weight Without Packaging | Approximately 2,650 g |
Frequently Asked Questions
What display settings should a replacement project use for 6AV6643-0CD01-1AX1?
Use 640 x 480 pixels with the 64K-color TFT display.
Which operator input is built into 6AV6643-0CD01-1AX1?
The panel uses a resistive analog touchscreen without physical function keys.
How much application memory is available in 6AV6643-0CD01-1AX1?
The panel provides 6 MB of application memory.
Which controller networks can connect to 6AV6643-0CD01-1AX1?
Use the 10/100 Mbit/s Ethernet interface or the RS422/RS485 interface at rates up to 12 Mbit/s.
What panel cutout is needed for 6AV6643-0CD01-1AX1?
Prepare a 310 x 248 mm opening and allow 61 mm mounting depth.
What current capacity should the power supply provide for 6AV6643-0CD01-1AX1?
Plan for up to approximately 1,100 mA within the permitted 20.4 to 28.8 V DC range.
How long can the clock retain time after power is removed from 6AV6643-0CD01-1AX1?
The buffered real-time clock has an approximate bridging time of six weeks.
Compatibility & Ordering Notes
Compatibility Checklist for 6AV6643-0CD01-1AX1
- Match SIMATIC MP 277 10-inch Touch Multi Panel and the full article number character by character.
- Verify display technology: LCD TFT.
- Confirm input technology: Resistive analog touchscreen.
- Preserve the approved settings and connection records used in Existing SIMATIC MP 277 operator stations using WinCC flexible projects.