Overview
- Provide the AC supply and 24 V DC input signals for this relay-output variant.
- Keep the program within the selected RUN-edit memory capacity.
- Match both RS485 ports to the existing PPI, MPI or Freeport settings.
- Calculate the expansion power budget and observe each attached module’s own ratings.
SIPLUS S7-200 • CPU 224XP
6AG1214-2BD23-2XB0 SIPLUS S7-200 CPU 224XP AC/DC/Relay Compact Controller
AC-powered CPU 224XP controller with fourteen 24 V DC inputs, ten relay outputs and integrated analog I/O.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6AG1214-2BD23-2XB0 |
| Product Type | Compact PLC controller |
| Core Function | Programmed machine control |
| Compatible Series | SIPLUS S7-200 |
Integrated digital and analog I/O
The CPU includes fourteen digital inputs, ten relay outputs, two analog inputs and one analog output.
Flexible user memory
Program capacity is 12 KB with RUN-mode editing or 16 KB without it, plus 10 KB of user data.
Serial automation network
Two RS485 communication ports support PPI, MPI slave and Freeport operating modes.
Product Overview
6AG1214-2BD23-2XB0 is the SIPLUS CPU 224XP AC/DC/relay controller in the S7-200 family. It combines an AC supply with DC sensor inputs, relay switching outputs and integrated analog channels.
STEP 7-Micro/WIN provides the engineering environment for the controller. Expansion modules, communication settings and user-program capacity should be selected together for the machine configuration.
Key Functions
Mixed-signal machine control
Onboard digital and analog channels handle discrete machine signals and analog process values.
CPU 224XP program execution
The processor executes Boolean instructions in 0.22 µs and provides configurable timers, counters and interrupts.
S7-200 communications and expansion
Two serial ports and support for up to seven expansion modules allow the CPU to form a larger S7-200 station within its power budget.
Official Specifications
| AC supply range | 85–264 V AC |
|---|---|
| Digital inputs | 14 at 24 V DC |
| Relay outputs | 10, up to 2 A per output |
| Relay switching voltage | 5–30 V DC or 5–250 V AC |
| Integrated analog channels | 2 inputs and 1 output |
| Program capacity with RUN-mode editing | 12,288 bytes |
| Program capacity without RUN-mode editing | 16,384 bytes |
| User-data capacity | 10,240 bytes |
| Boolean instruction execution | 0.22 µs per instruction |
| Available timers and counters | 256 timers and 256 counters |
| Timed interrupts | 2 with 1 ms resolution |
| Single-phase high-speed counting | 4 counters at 30 kHz and 2 at 200 kHz |
| Serial interfaces | 2 RS485 ports |
| PPI and MPI data rates | 9.6, 19.2 and 187.5 kbaud |
| Freeport data rates | 1.2–115.2 kbaud |
| Maximum expansion modules | 7 |
| Dimensions | 140 × 80 × 62 mm |
Frequently Asked Questions
Which software should I use to maintain a program in 6AG1214-2BD23-2XB0?
Use STEP 7-Micro/WIN for the S7-200 controller program and communication settings.
Can the relay outputs on 6AG1214-2BD23-2XB0 generate 100 kHz motion pulses?
High-speed pulse outputs require a DC transistor-output variant rather than the relay-output version.
How much program space remains when I enable RUN-mode editing on 6AG1214-2BD23-2XB0?
The program capacity is 12,288 bytes with RUN-mode editing compared with 16,384 bytes without it.
Can I add seven expansion modules to 6AG1214-2BD23-2XB0?
Up to seven expansion modules are allowed when the CPU and expansion-module power budget is sufficient.
Can I connect a SIWAREX MS weighing module to 6AG1214-2BD23-2XB0?
The CPU is a released SIWAREX MS host, while the weighing module retains its own environmental ratings.
Which serial modes can I use on 6AG1214-2BD23-2XB0?
The RS485 ports support PPI master or slave, MPI slave and configurable Freeport communication.
Does 6AG1214-2BD23-2XB0 provide analog I/O without an expansion module?
The CPU includes two analog inputs and one analog output.